Macurco™ Control Panel
DVP-120
Detection and Ventilation
Detection and Ventilation Control Panel
The DVP-120 exhaust fan controller, in conjunction with Macurco™ gas transducers, provides automatic controls
to help maintain an acceptable environment in parking garages or other facilities. The DVP-120 system is designed
to meet specifications for safety in enclosed parking garages, including the Uniform Building Code and OSHA
50ppm CO requirements. The DVP-120 can control up to twelve gas sensors in any combination.
Features
• External keypad for user selection of the transducer/alarm display and setting the configuration
• Externally visible LCD display showing the status of each transducer and relay
• Externally visible system, alarm and relay status indicators
• Compatible with all Macurco™ 6-Series gas sensors
• Twelve analog (current loop) input channels
• Three 10A, 240 VAC SPDT fan/alarm relays
• Drivers for external Horn and Strobe
• Fail safe operation can be implemented
• Lockable NEMA 1 type enclosure
• Modular input and output connectors
• ETL Listed to UL 508A, CAN/CSA-C22.2 No. 14-13, LADBS Approved
• Up to three ventilation control zones can be defined
• Each zone can be controlled based on transducer signals and/or time of day
• Each relay is configurable for delay before activation and minimum on time
Manufactured by Aerionics, Inc. Sioux Falls, SD – Phone: 1-877-367-7891 – Email: info@aerionicsinc.com – www.macurco.com
DVP-120 Specifications
• Power Input: 90 – 250 VAC, 1 Amp, 47 – 63 Hz, single phase
• Size: 10.5” x 12.5” x 2.” (267 mm x 318 mm x 51 mm)
• Weight: 6 ½ lb (2.9 kg)
• Enclosure: NEMA 1 Type
• Operating Temperature: 32 to 104°F (0° to 40°C )
• Operating Humidity: 0% to 95% RH non-condensing
• Relay Rating (3): SPDT, 120/240 VAC, 10 A resistive
• LCD Display: 2 rows of 16 characters with backlight
• Audible indicator: Internal buzzer, 90 dBA at 1ft
• External Drivers (2): 24VDC, maximum 250 mA
• Relay On Delay: 0 – 15 minutes in 1 second increments
• Relay Off Delay: 0 – 15 minutes in 1 second increments
• Status Indicators (LED): Power, ALARM/warning, Hush,
Relay 1, Relay 2 & Relay 3
Installation & Connection
Gas detection and exhaust fan control is provided by a Macurco™ DVP-120 system. System wiring includes
the main power connection for the DVP-120, 4-20mA current loop and 24VDC power connections between the
remote sensors and the DVP-120, the fan control connections and alarm connections from the DVP-120 to the
building ventilation and automation systems. All power and signal connections for the sensors are provided from
the DVP-120 control panel, via unshielded four conductor cable. The DVP-120 control panel provides three
relays which can be used for ventilation fan control or alarm signaling. The ventilation control function operates
independently from the alarm function. It provides the ability to configure the DVP-120 for control of one to three
zones. Each zone can respond to gas levels at one or more of the sensors, with configurable rising and falling
concentrations for each gas type. Each zone can also be controlled based on the time of day.
TYPICAL CONNECTION OF THE DVP-120 CONTROL PANEL COVERAGE UP TO 60,000 SQAURE FEET
12 Input Channels
N.C.
N.O.
COM
24 V RET
-1 LOOP
+1 LOOP
+24 VDC
24 V RET
-1 LOOP
+1 LOOP
+24 VDC
8 7 6 5 4 3 2 1
power
– +
output
power
– +
output
Exhaust Fans
120VAC
Power
120VAC
ALARM
coil
coil
STARTER RELAYS
120VAC COILS
Main Fan Power
Gnd
4
1
3
2
- Horn
- Strobe
+ Horn
+ Strobe
Panel Power
120/250 VAC
LN
1 13 3 4 5 6 7 8 92
MACURCO™ DVP-120
DETECTION AND VENTILATION
CONTROL PANEL
Relay 1
N.C.
N.O.
Relay 2 Relay 3
N.C.
N.O.
COM
COM