Macromatic VWKP Series Catalog Page

voltage monitor relays | plug-in
VOLTAGE BAND (WINDOW)
12-480V | VWKP Series
Voltage Band Relays provide protection to equipment that is required to operate within an upper and lower voltage limit. As long as the operating voltage remains within an Over and Under Voltage range, the internal relay stays energized. If the operating voltage falls outside this range, the relay will drop-out.
12-120V
Monitors AC single phase and DC
voltages
Provides voltage band
(window) protection
ensures more accurate sensing
Wide range of user-adjustable
Over Voltage and Under Voltage settings
Adjustable time delay on drop-out
of 0.1-10 seconds
LED indicates output relay status
Compact plug-in case utilizing indus-
try standard 8 pin octal socket
Pilot duty rating
10A output contacts
with
appropriate
socket
240-480V
The over voltage setting (U table below. The under voltage setting (Umin) is adjustable from 75-95% of the over voltage setting (Umax). The relay energizes (and the LED is Red) when the monitored voltage is between the over and under voltage settings. The relay de-energizes (and the LED is Green) when the monitored voltage falls outside the over or under voltage settings for a period longer than the drop-out time delay (t), which is adjustable from
0.1-10 seconds. The relay re-energizes when the monitored voltage returns to a value between the over and under voltage settings for a period longer than the
pick-up time delay, which is xed at 0.5 seconds.
Adjustable Overvoltage & Undervoltage Settings
Adjustable Time Delay on Drop-Out of 0.1 - 10 Seconds
OVER UNDER NOMINAL VOLTAGE VOLTAGE PRODUCT WIRING/ VOLTAGE (UMAX) (UMIN) NUMBER SOCKET
\ 12V DC 9-15V DC 7-14V DC VWKP012D
24V DC 18-30V DC 14-28V DC VWKP024D 48V DC 36-60V DC 27-57V DC VWKP048D 110V DC 83-138V DC 62-130V DC VWKP110D
max) is adjustable across the full range as shown in the
8 Pin Octal
70169-D
DIAGRAM 214
8 Pin Octal
70169-D
120V AC 90-150V AC 68-142V AC VWKP120A
DIAGRAM 213
8 Pin Octal
240V AC 180-300V AC 135-285V AC VWKP240A 480V AC 360-600V AC 270-570V AC VWKP480A
p
Requires a 600V-rated socket
Sockets & Accessories available
p
70169-D
DIAGRAM 150
6
VOLTAGE BAND (WINDOW)
12-480V | VWKP Series
Application data
Voltage Tolerance:
+50% of nominal AC (50-60Hz, +5%) or DC voltage No separate input voltage required since unit is powered by monitored voltage.
Load (Burden): Less than 2VA (12-120V); 30VA (240V & 480V)
Voltage Settings:
Over Voltage selection table Under Voltage (Umin): 75-95% of Over/Under Voltage Setting
Setting Accuracy: Maximum Setting (Adjustable): +5%, -0% Minimum Setting (Adjustable): +0%, -50% Fixed Voltage Setting: +2%
Repeatability: <1%
Sensing Accuracy: Constant conditions within specications: +2%
Variable conditions within specications: +5% (percent base on nominal voltage)
Temperature: Operating: -28o to 65oC (-18o to 149oF) Storage: -40o to 85oC (-40o to 185oF)
Indicator LED: Red when Relay is energized; Green when Relay is Off.
(Umax): Across full range as shown in the product
Reset: Automatic
Response Times:
Restart: 1 second (240 & 480V only) Pick-up: 0.5 Seconds Drop-out (t): Adjustable 0.1 -10 Seconds
Output Contacts:
10A @ 240V AC, 7A @ 30V DC, 1/4HP @ 120/240V AC, C300
Life:
Mechanical: 10,000,000 operations Full Load: 100,000 operations
Transient Protection:
2000V per IEC 61000-4-5 Level 3 (+2kV)
Approvals:
File #E109466
with
appropriate
socket
File #E109466
voltage monitor relays | plug-in
Dimensions
All Dimensions in
Inches (Millimeters)
| |
7