OVER/UNDER VOLTAGE | ADJUSTABLE TIME DELAY ON DROP-OUT
voltage monitor relays | plug-in
Monitors AC single phase and
DC voltages
Wide range of user-adjustable
Adjustable time delay on drop-
out of 0.5 - 10 seconds
LED indicates output relay
status
Compact plug-in case utilizing
industry standard 8 pin octal socket
10A DPDT output contacts

(with appropriate socket)
12-120V | VA Series
Over/Under Voltage Relays provide protection to equipment where an over or un­der voltage condition is potentially damaging. They are designed to operate when the operating voltage reaches a preset value and drop-out when the operating voltage drops to a level below the preset value.
The pick-up voltage setting is user-adjustable from 85-115% of the nominal voltage rating. As standard, the VAP Series has a drop-out voltage setting xed at 95% of the pick-up voltage setting. An adjustable drop-out setting of 75-95% of the pick-up setting is available on the VAKP Series. The relay energizes when the monitored voltage is above the pick-up setting. The relay de-energizes when the monitored voltage is below the drop-out setting for a period longer than the drop­out time delay (t), which is adjustable from 0.5-10 seconds for VA Series products.
Adjustable Pick-Up, Fixed Drop-Out Settings *
Adjustable Time Delay on Drop-out from 0.5 - 10 Seconds
PICK-UP DROP-OUT MONITORED VOLTAGE VOLTAGE PRODUCT WIRING/ VOLTAGE RANGE RANGE* NUMBER SOCKET
24V AC 21-27V AC 20-26V AC VAP024A 8 Pin Octal
120V AC 102-138V AC 97-131V AC V AP120A 70169-D
12V DC 10-14V DC 9-13V DC VAP012D 24V DC 21-27V DC 20-26V DC VAP024D 48V DC 41-55V DC 39-52V DC VAP048D 110V DC 94-126V DC 89-121V DC VAP110D
DIAGRAM 20
* Drop-out Voltage is fi xed at 95% of the adjusted Pick-up Setting.
Adjustable Pick-Up & Drop-Out Settings **
Adjustable Time Delay on Drop-out from 0.5 - 10 Seconds
PICK-UP DROP-OUT MONITORED VOLTAGE VOLTAGE PRODUCT WIRING/ VOLTAGE RANGE RANGE* NUMBER SOCKET
24V AC 21-27V AC 16-26V AC VAKP024A 8 Pin Octal
120V AC 102-138V AC 77-131V AC V AKP120A 70169-D
12V DC 10-14V DC 8-13V DC VAKP012D 24V DC 21-27V DC 16-26V DC VAKP024D 48V DC 41-55V DC 32-52V DC VAKP048D 110V DC 94-126V DC 71-121V DC VAKP110D DIAGRAM 20
** Drop-out Voltage is adjustable from 75-95% of the adjusted Pick-up Setting.
800.238.7474
Sockets & Accessories available
www.macromatic.com
sales@macromatic.com
4