Macromatic THL-1 Series Catalog Page

time delay relays | encapsulated
ON DELAY | INLINE (SERIES CONNECTION)
Solid State Output | Analog-Set | THL-1 Series
Universal input voltage:
24-240V AC & 12-48V DC
Onboard & remote adjustable
or f xed time delays from 0.01 seconds to 100 hours
T wo-terminal series-connection
with the load
Cost effective design &
compact 2” x 2” enclosure are ideal for volume OEM applications
Microprocessor-based design
for greater performance & maximum f exibility
Encapsulated for protection
against harsh environments
Output rated 1A continuous/10A
inrush pilot duty is perfect for high duty cycle/long life applications
INPUT PRODUCT FUNCTION VOL TAGE NUMBER ** WIRING
ON DELAY 12-48V DC Fixed Time Delay
Remote Time Delay
See “Def nitions of Timing Functions”. ** Complete Product Number using two-digit Code from Table below.
24-240V AC & THL-1024U-** Onboard Adjustable or
DIAGRAM 329
DIAGRAM 330
16
Time Delays
THL-1 Series Products have three time delay options: Onboard Adjustable Time Delay--complete Prod-
uct Number by adding two-digit Code from Table at right, i.e., THL-1024U-30 is an On Delay with a time delay range of 0.1-10 seconds.
Code with suff x “F” followed by delay [0.1 ... 100] followed by (S) seconds, (M) minutes or (H) hours, i.e., THL-1024U-F5S is an On Delay with a time delay f xed at 5 seconds.
Remote Time Delay--THL-1 Series products can
be built with two terminals for remote adjustable or f xed time delays.
Build your Time Delay Relays with the Online Product Builder
** TIMING RANGE TABLE
Time Delay Range Code
0.01 - 1 Sec. 02
0.05 - 5 Sec. 04
0.1 - 10 Sec. 30 1 - 100 Sec. 31 10 - 1,000 Sec. 36
0.1 - 10 Min. 32 1 - 100 Min. 33 10 - 1,000 Min. 37 1 - 100 Hr. 35
THL-1 SERIES
Solid State Output | Analog-Set
Application Data
Voltage Tolerance:
AC Operation: +10 to -15% of nominal voltage, 50/60 Hz DC Operation: +10 to -15% of nominal voltage
Load (Burden): Maximum of 1 VA for all voltages
Setting Accuracy:
Maximum Setting (Adjustable): +5%, -0% Minimum Setting (Adjustable): +0%, -50% Fixed Time Delay: +2% or 50ms, whichever is greater
Repeat Accuracy (constant voltage and temperature): +0.1% or + 0.01 seconds, whichever is greater
Reset Time: 50ms
Start-up Time:
(Time from when power is applied until unit is timing)
0.02 Seconds
Maintain Function Time:
(Time unit continues to operate after power is removed)
0.01 Seconds
Temperature: Operating: -28 Storage: -40
o
to 65oC (-18o to 149oF)
o
to 85oC (-40o to 185oF)
Output Contacts:
Normally Open Solid State 1A Continuous, 10A Inrush @ 65
Life:
No predictable failure if used within operating parameters.
Leakage Current (OFF-State): < 5ma @ 240V AC
Minimum Load Current: 20ma
Effective Voltage Drop (ON-State): Maximum 3V @ 1A for all voltages
Compatibility:
Using a solid state switch to initiate the time sequence is acceptable. See or contact Macromatic for information regarding leakage current limits and other solid state design considerations.
Mounting:
Surface with one #8 or #10 screw
Termination:
0.25” male quick-connect terminals
Approvals:
File #E236146
o
C, Pilot Duty
time delay relays | encapsulated
Dimensions
All Dimensions in
Inches (Millimeters)
Remote Time Delay
THL-1 Series products can be built with two terminals for remote adjustable or f xed time delays. To order a product with a remote time delay, complete the Product Number by adding the two-digit Code from the Table shown on the appropriate product selection page followed by the suff x “R1”, i.e., THL-1024U-30R1.
Adjustable Time Delay
A 100K ohm potentiometer is required to obtain the maximum time delay for all standard ranges. To use other values of remote potentiometers, contact Macromatic.
Fixed Time Delay
A f xed time delay can be set by connecting a resistor across the two terminals. To determine the resistor value required, use the following equation:
T
R =
T
max
x 100,000
Example: Using time range 0.1-10 seconds, what resistor value is required for a f xed time delay of 5 seconds:
5
R =
x 100,000
10
R = Resistance value required to obtain T T
= Desired time delay
= Maximum time delay of range
T
max
= 50,000 ohms (50K ohms)