Macromatic TD-8 Series Catalog Page

PROGRAMMABLE | SINGLE FUNCTION
DIP-Switch | Digital-Set | TD-8 Series
The TD-8 Series time delay relays offer an easy and accurate method to select any time delay between 100ms and 1,023 hours. Programming is accomplished through the use of a 10-position DIP-switch. Each position is marked with a binary time increment. The required delay is selected by moving the switch of each increment to the ON position and adding their corresponding values (see examples below). This method provides a greater setting accuracy than is found on other units with an analog potentiometer. An LED indicates relay status.
INPUT VOLTAGE PRODUCT WIRING/ FUNCTION
ON DELAY 12V DC TD-80226-** 24V AC/DC TD-80228-** 8 PIN OCTAL 240V AC TD-80221-** 70169-D
INTERVAL ON 120V AC/DC TD-80522-** 12V DC TD-80526-** 24V AC/DC TD-80528-** 240V AC TD-80521-**
REPEAT CYCLE * 120V AC/DC TD-83122-** (OFF Time First Followed 12V DC TD-83126-** 8 PIN OCTAL By ON Time 24V AC/DC TD-83128-** and Repeating) 240V AC TD-83121-** DIAGRAM 1
REPEAT CYCLE * 120V AC/DC TD-85122-** (ON Time First Followed 12V DC TD-85126-** By OFF Time 24V AC/DC TD-85128-** and Repeating) 240V AC TD-85121-**
OFF DELAY 120V AC/DC TD-81622-** 11 PIN OCTAL Control Switch Trigger 12V DC TD-81626-** 70170-D 24V AC/DC TD-81628-** 240V AC TD-81621-**
SINGLE SHOT 120V AC/DC TD-81522-** Control Switch Trigger 12V DC TD-81526-** 24V AC/DC TD-81528-** 240V AC TD-81521-**
50/60Hz. NUMBER ** SOCKETS
120V AC/DC TD-80222-**
Dual ModeSingle Mode
DIP-Switches for accurate
digital set of time delay
100ms - 1,023 hours program-
mable time delay
Uses industry-standard 8 or 11
pin octal sockets
10A DPDT output contacts
LED indicates relay status
Pilot duty rating
with appropriate
socket
time delay relays | plug-in
DIAGRAM 2
See “Def nitions of Timing Functions”. * ese functions are the same. See
OFF time ranges.
for information on how to order a unit with different ON &
Time Delays
**TIMING RANGE TABLE
COMPLETE PRODUCT NUMBER
USING TWO DIGIT CODE BELOW:
i.e., TD-80222-40
Time Delay Range Code
0.1 - 102.3 Sec. 40 1 - 1,023 Sec. 41 10 - 10,230 Sec. 42 1 - 1,023 Min. 43 10 - 10,230 Min. 44 1 - 1,023 Hr. 45
Sockets & Accessories available
Build your Time Delay Relays with the Online Product Builder
31