PHASE REVERSAL
Application Data
Voltage Requirements:
RANGE
(50/60Hz +5%)
190-500V AC 156V AC 550V AC PCPU
460-600V AC 390V AC 660V AC PCP575
MIN
VOLTAGE
MAX
VOLTAGE
PRODUCT
NUMBER
PCP Series
Life: Mechanical: 10,000,000 operations; Full Load: 100,000
operations
o
Temperature: Operating: -28
Storage: -40o to 85oC (-40o to 185oF)
Mounting: Uses an 8 pin octal socket. Requires a 600V-rated
socket when used on system voltages greater than 300V such as
Macromatic Catalog Number 70169-D.
to 65oC (-18o to 149oF)
three-phase monitor relays | plug-in
Power Consumption: Less than 40VA
Phase Reversal (Sequence):
Unit trips if rotation (sequence) of the three phases is anything
other than A-B-C. It will not work on C-B-A.
Response Times:
Power Up & Restart After Fault: 50ms fi xed
Drop-out Due to Phase Reversal: 200ms fi xed
Output Contacts: 10 A @ 277V AC / 7A @ 30V DC;
1HP @ 250V AC, 1/2HP @ 125V AC,
C300 Pilot Duty
Status LED: Green solid when sequence is correct and relay is ON;
Red solid when sequence is incorrect and relay is OFF.
Reset:
As standard, reset is automatic upon correction of fault.
Approvals:
File #E109466
EN60947-1,
EN60947-5-1,
EN60255-1
with
appropriate
socket
File #E109466
Dimensions
All Dimensions in
Inches (Millimeters)
800.238.7474 | www.macromatic.com | sales@macromatic.com
5