Macromatic ISP Series Catalog Page

PLUG-IN INTRINSICALLY SAFE BARRIER RELAYS
ISP Series
The ISP Series of Intrinsically Safe Barrier Relays provide a safe and reliable method to control a single load (motor starters, relays, etc.) with a single input device (switches, sensors, etc.) located in a hazardous area.
intrinsically safe barrier relays | PLUG-IN
Approved for use in these
Hazardous Locations:
Class III, Div 1
1-Channel
Terminals support 2-wire inputs
Isolated 10A relay output
Plug-in design for easy
installation and replacement
LED status indicator
The ISP Series relay must be installed following Macromatic Control Drawing Number ISR2A01D as shown in Instruction Sheet 901-0000-260.
The ISP Series relays utilize an 8 pin plug-in design with socket (included) that can be both mounted on 35mm DIN rail or panel-mounted with two screws.
Operation
Each ISP Series relay consists of an intrinsically safe input and a corresponding normally-open relay output. There is one LED for status indication. With input voltage applied, the LED will be OFF. When the input device is closed, the output contact is closed and the LED is ON (Green). When the input device is open, the output contact is open and the LED will be OFF.
INPUT NUMBER
VOLTAGE OF CATALOG WIRING/ 50/60Hz CHANNELS NUMBER SOCKETS
120V AC SINGLE ISP120A
UL913
DIAGRAM 160
The appropriate 8 pin socket is included with the plug-in relay.
8
PLUG-IN INTRINSICALLY SAFE BARRIER RELAYS
Application data
Input Voltage:
120V AC, +10%, 50/60Hz
Load (Burden):
1.25 VA
Input Switch Open Circuit Voltage:
6V DC
Output Contacts:
SPST-NO 10A @ 120V AC Resistive
Life:
Mechanical: 10,000,000 operations Full Load: 100,000 operations
Response Times:
Operate: 11 ms Release: 4 ms
ISP Series
Temperature:
Operate: -20o to 60oC (-4o to 140oF) Storage: -45o to 85oC (-49o to 185oF)
Insulation Voltage: 2,000 volts (between coil and contacts)
LED Indicator:
Green ON when output contact is closed and OFF when output contact is open.
Mounting:
The socket can be both mounted on 35 mm DIN rail or panel­mounted with two #8 screws.
Control Drawing:
See Instruction Sheet 901-0000-260, which includes Control Drawing ISR2A01D
Approvals:
E318075
intrinsically safe barrier relays | PLUG-IN
Dimensions
1.77 (45)
2.48 (63)
2.05 (52)
ISP Series
1.39 (35)
2.90 (74)
1.89 (48)
0.25 (6)
1.30 (33)
1.61 (41)
0.16 (4)
. Socket Provided with Relay
All Dimensions in Inches (Millimeters)
0.83 (21)
1.61 (41)
. Panel Mount Template