Macromatic ISD Series Catalog Page

60 MM INTRINSICALLY SAFE BARRIER RELAYS
ISD Series
The ISD Series of Intrinsically Safe Barrier Relays provide a safe and reliable method to control up to four loads (motor starters, relays, etc.) with up to four input devices (switches, sensors, etc.) located in a hazardous area.
intrinsically safe barrier relays | din rail
ISDUM4
Approved for use in these
Hazardous Locations:
Class I, Div 1 (Zones 0 and 1 Canada), Groups A, B, C, D
Class II, Div 1 (Zones 20 and 21 Canada), Group E, F, G
Class III, Div 1
4-Channel
Terminals support 2-wire inputs
Isolated 5A relay outputs
Pluggable terminals offer easy
installation & replacement
Universal input voltage of 102­132V AC & 10-125V DC
Compact 60mm wide enclosure for both DIN-rail or panel-mount
Standard & inverse logic
Instantaneous & delayed response
times
LED status indicator
ISDUR4
The ISD Series relays utilize a compact 60mm wide enclosure that can be both mounted on 35mm DIN rail or panel-mounted with two screws. Terminals for the input devices from the hazardous area are on the bottom of the unit for easy access in the enclosure to incoming eld wiring from the hazardous area. Pluggable terminal blocks on both the input and output sides allow for easy initial wiring of the unit as well as replacement without having to remove any wires.
Each input has two terminals supporting direct connection of 2-wire input devices eliminating the need to mount a separate terminal block. Each output relay is isolated with two wiring terminals providing a true normally-open contact. This allows the output contacts to be used in complex control circuits and allows for each output to switch different voltages with respect to other outputs and the input voltage. A universal input voltage of 102-132V AC & 10-125V DC covers a variety of applications with one device.
Operation
Each ISD Series product consists of 4 intrinsically safe inputs and four corresponding normally-open relay outputs. With input voltage applied, the V LED will be ON (GREEN) to indicate power is applied. When the input device is closed, the input LED is ON (GREEN). When the output relay is closed, the output LED is ON (ORANGE). The ISD series offers four user-selectable congurations built in.
ISDUR4 has a two-position DIP-switch that selects a single conguration for all channels.
ISDUM4 has an eight-position DIP-switch that selects a conguration for each channel, independently.
Congurations
Standard Logic (DIP Switch set to “STD”):
When the input device is closed, the corresponding output contact is closed. When the input device is open, the corresponding output contact is open.
Inverse Logic (DIP Switch set to “INV”):
When the input device is open, the corresponding output contact is closed. When the input device is closed, the corresponding output contact is open.
No Time Delay (DIP Switch set to “0 S”):
The output contact changes state immediately in response to a change in input device state.
UL913 8th Edition
2 Second Delay (DIP Switch set to “2 S”):
The output contact will delay 2 seconds before changing state in response to a change in input device state.
INPUT
VOLTAGE
102-132V
AC
(50/60Hz)
and
10-125V
DC
NUMBER
OF
CHANNELS
4
CONFIGURATION
SELECTED FOR
ALL CHANNELS
SELECTED FOR EACH CHANNEL
CATALOG
NUMBER
ISDUR4
ISDUM4
WIRING
DIAGRAM 814
4
60 MM INTRINSICALLY SAFE BARRIER RELAYS
Application data
ISD Series
Input Voltage: 102-132V AC (50/60Hz.) & 10-125V DC
Load (Burden): 5VA Maximum
Input Switch Open Circuit Voltage: 10V DC
Output Contacts:
SPST-NO (Form A) 3A Resistive @ 125V AC @60°C & 30V DC Resistive, Pilot Duty Rating D300
SPST-NO (Form A) 5A Resistive @ 125V AC @40°C & 30V DC Resistive, Pilot Duty Rating D300
Life:
Electrical: 50,000 Closures @ Full Load AC Mechanical: 5 Million Closures @ No Load
Response Times:
Standard (DIP Switch set to “0S”): < 50ms Delay (DIP Switch set to “2S”): Fixed 2 Seconds
Temperature:
Operating: -28° to + 60° C (-18° F to +140° F) Storage: -55° to +85° C (-67° to 185° F)
LED Indication:
V: ON (Green); Inputs: ON (Green); Outputs: ON (Orange)
Insulation Voltage:
1500 V AC between coil & contacts 750 V AC between open contacts 1500 V AC between contacts of different output channels 1500 V AC between hazardous and safe circuits
Wire Sizes:
One #14-24 AWG Conductor or Two #16 or 18 AWG Conductors
Mounting:
Mounts on 35mm DIN-rail or panel-mounted with two #8 screws when DIN-rail clips are fully extended from under the enclosure.
Control Drawing:
See Instruction Sheet 901-0000-328, which includes Control Drawing ISD1A04.
Approvals:
E318075
intrinsically safe barrier relays | din rail
Accessories
Terminal Kit Part # 70700: Replacement kit for Intrinsically Safe Barrier Relay plugable terminals, includes 1 black and 1 blue block.
Input Voltage: 102-132V AC and 10-125V DC
Output: 5A
Dimensions
2.60 (66)
4.36
(111)
2.36 (60)
4.36
(111)
Kit Part # 70700
2.36 (66)
Ø 0.167 [#8]
(4.2)
4.02
(102)
All Dimensions in Inches (Millimeters)
Ø 0.167 [#8]
(4.2)
Panel Mount Template
5