60 MM INTRINSICALLY SAFE BARRIER RELAYS
ISD Series
The ISD Series of Intrinsically Safe Barrier Relays provide a safe and reliable
method to control up to four loads (motor starters, relays, etc.) with up to four input
devices (switches, sensors, etc.) located in a hazardous area.
intrinsically safe barrier relays | din rail
ISDUM4
Approved for use in these
Hazardous Locations:
Class I, Div 1 (Zones 0 and 1
Canada), Groups A, B, C, D
Class II, Div 1 (Zones 20 and 21
Canada), Group E, F, G
Class III, Div 1
4-Channel
Terminals support 2-wire inputs
Isolated 5A relay outputs
Pluggable terminals offer easy
installation & replacement
Universal input voltage of 102132V AC & 10-125V DC
Compact 60mm wide enclosure for
both DIN-rail or panel-mount
Standard & inverse logic
Instantaneous & delayed response
times
LED status indicator
ISDUR4
The ISD Series relays utilize a compact 60mm wide enclosure that can be both
mounted on 35mm DIN rail or panel-mounted with two screws. Terminals for the
input devices from the hazardous area are on the bottom of the unit for easy access
in the enclosure to incoming eld wiring from the hazardous area. Pluggable terminal
blocks on both the input and output sides allow for easy initial wiring of the unit as
well as replacement without having to remove any wires.
Each input has two terminals supporting direct connection of 2-wire input devices
eliminating the need to mount a separate terminal block. Each output relay is isolated
with two wiring terminals providing a true normally-open contact. This allows the output
contacts to be used in complex control circuits and allows for each output to switch
different voltages with respect to other outputs and the input voltage. A universal input
voltage of 102-132V AC & 10-125V DC covers a variety of applications with one
device.
Operation
Each ISD Series product consists of 4 intrinsically safe inputs and four
corresponding normally-open relay outputs. With input voltage applied, the V LED
will be ON (GREEN) to indicate power is applied. When the input device is closed,
the input LED is ON (GREEN). When the output relay is closed, the output LED is
ON (ORANGE). The ISD series offers four user-selectable congurations built in.
ISDUR4 has a two-position DIP-switch that selects a single conguration for all
channels.
ISDUM4 has an eight-position DIP-switch that selects a conguration for each
channel, independently.
Congurations
Standard Logic (DIP Switch set to “STD”):
When the input device is closed, the corresponding output contact is closed. When
the input device is open, the corresponding output contact is open.
Inverse Logic (DIP Switch set to “INV”):
When the input device is open, the corresponding output contact is closed. When
the input device is closed, the corresponding output contact is open.
No Time Delay (DIP Switch set to “0 S”):
The output contact changes state immediately in response to a change in input
device state.
UL913 8th Edition
2 Second Delay (DIP Switch set to “2 S”):
The output contact will delay 2 seconds before changing state in response to a
change in input device state.
INPUT
VOLTAGE
102-132V
AC
(50/60Hz)
and
10-125V
DC
NUMBER
OF
CHANNELS
4
CONFIGURATION
SELECTED FOR
ALL CHANNELS
SELECTED FOR
EACH CHANNEL
CATALOG
NUMBER
ISDUR4
ISDUM4
WIRING
DIAGRAM 814
4

60 MM INTRINSICALLY SAFE BARRIER RELAYS
Application data
ISD Series
Input Voltage: 102-132V AC (50/60Hz.) & 10-125V DC
Load (Burden): 5VA Maximum
Input Switch Open Circuit Voltage: 10V DC
Output Contacts:
SPST-NO (Form A) 3A Resistive @ 125V AC @60°C &
30V DC Resistive, Pilot Duty Rating D300
SPST-NO (Form A) 5A Resistive @ 125V AC @40°C &
30V DC Resistive, Pilot Duty Rating D300
Life:
Electrical: 50,000 Closures @ Full Load AC
Mechanical: 5 Million Closures @ No Load
Response Times:
Standard (DIP Switch set to “0S”): < 50ms
Delay (DIP Switch set to “2S”): Fixed 2 Seconds
Temperature:
Operating: -28° to + 60° C (-18° F to +140° F)
Storage: -55° to +85° C (-67° to 185° F)
LED Indication:
V: ON (Green); Inputs: ON (Green); Outputs: ON (Orange)
Insulation Voltage:
1500 V AC between coil & contacts
750 V AC between open contacts
1500 V AC between contacts of different output channels
1500 V AC between hazardous and safe circuits
Wire Sizes:
One #14-24 AWG Conductor or
Two #16 or 18 AWG Conductors
Mounting:
Mounts on 35mm DIN-rail or panel-mounted with two #8 screws
when DIN-rail clips are fully extended from under the enclosure.
Control Drawing:
See Instruction Sheet 901-0000-328, which includes Control
Drawing ISD1A04.
Approvals:
E318075
intrinsically safe barrier relays | din rail
Accessories
Terminal Kit Part # 70700: Replacement kit for Intrinsically Safe
Barrier Relay plugable terminals, includes 1 black and 1 blue
block.
Input Voltage: 102-132V AC and 10-125V DC
Output: 5A
Dimensions
2.60
(66)
4.36
(111)
2.36
(60)
4.36
(111)
Kit Part # 70700
2.36
(66)
Ø 0.167 [#8]
(4.2)
4.02
(102)
All Dimensions in Inches (Millimeters)
Ø 0.167 [#8]
(4.2)
Panel Mount Template