Application data
AC OVERCURRENT & UNDERCURRENT
CAH, COH & CUH Series
Input Voltage Tolerance:
AC Operation: +10/-15% of nominal at 50/60 Hz.
DC Operation: +10/-15% of nominal
Load (Burden): 2VA for all voltages
Current Sensing:
Ranges: Separate 0.5-5A, 2-20A & 5-50A
Type: Toroidal, through hole wiring
Setting Accuracy: Min: +0%, -50%; Max: +10%, -0%
Maximum Allowable Current:
0.5-5A Range: Steady-25A Turns; 150A Turns Inrush for
10 Seconds
2-20A & 5-50A Ranges: Steady-50A Turns; 300A Turns Inrush for
10 Seconds
Trip Point Hysteresis: -5% Overcurrent sensing
+5% Undercurrent sensing
Response Times:
Sensing Delay on Start-up: Fixed values from 0-6 seconds in one
second increments
Time Delay on Trip (Relay ON): Adjustable 0.5-50 seconds or
0.1-7 seconds
Time Delay on Reset (Relay OFF): 100ms
Reset Time: 400ms
Output Contacts:
10 Amperes @ 240VAC, General Purpose
8 Amperes @ 28VDC, Resistive
1/4HP @ 120/240VAC
B300
Life:
Mechanical: 10,000,000 operations
Full Load: 100,000 operations
Temperature: Operating: -28o to 65oC (-18o to 149oF)
Storage: -40o to 85oC (-40o to 185oF)
Indicator LED: Red ON Steady when Fault occurs
Mounting:
Surface mount with two (2) #6 screws
Termination:
0.25” male quick-connect terminals
Approvals:
File #E109466
current sensing relays | encapsulated