Macromatic ATP Series Data Sheet

Page 1
TRIPLEXOR
ATP Series
Application data
Voltage Tolerances: +10%/-15% at 50/60Hz. (AC); +10%/-15% of control voltage (DC)
C300 Pilot Duty; 1/6HP @ 24/120VAC
Life:
Mechanical: 10,000,000 operations; Full Load: 100,000 operations
o
Temperature: Operating: -28 Storage: -40o to 85oC (-40o to 185oF)
Time Delay: If power is lost & returns with more than just the LEAD Switch closed, there is a fi xed 10 second delay between energization of the second output (Triplex & Duplex mode) & third output (Triplex mode only) to prevent all Loads from coming on at the same time.
Dimensions
to 65oC (-18o to 149oF)
LED Indication: One of the Red LEDs will be steady ON to indicate which Load will be energized fi rst; all will fl ash (3 in Triplex mode or 2 only in Duplex mode) to indicate a switch out-of-sequence error.
Optional Selector Switch Settings:
Allows unit to operate as standard Triplexor or Duplexor, or lock selected Loads to operate fi rst (Lead Load) each time:
Triplex Duplex Triplex--Lead 1 Duplex--Lead 1 Triplex--Lead 2 Duplex--Lead 2
Triplex--Lead 3
Approvals:
File #E109466
with appropriate socket
File #E109466
alternating relays | plug-in
2.4
(60)
3.5
(89)
1.7
(43)
8 Pin Products Only
3.9
(99)
All Dimensions in
Inches (Millimeters)
Typical installations
3 Switch 3 Pump
All three switches are open and all loads are off. When the LEAD Switch closes, it energizes Load 1. As long as the LEAD Switch remains closed, Load 1 remains energized. If the LAG Switch closes, Load 2 is energized. If the LAG2 Switch closes, it energizes Load 3. Each load is turned off in sequence as the switches are opened. The entire cycle is then repeated, but with Load 2 energized fi rst followed by Load 3 and then Load
1. NOTE: power for outputs is supplied from L connection, not through input switches (see drawing at right).
2.4
(60)
4.0
(102)
1.7
(43)
12 Pin Products
Only
Drawing references terminal numbers on 8 pin products
4.4
(112)
800.238.7474 | www.macromatic.com | sales@macromatic.com