Macromatic ATP Series Catalog Page

alternating relays | plug-in
Control triplex soads Works with 3 Switch inputs-
LEAD, LAG & LAG2
allows use as standard Triplexor or as Duplexor until system expansion requires additional third Load
Control voltages of 120V AC or
24V AC/DC
Plug-in enclosure utilizes
industry-standard 8 Pin octal or 12 Pin square sockets
Input Switch Failure Indication
TRIPLEXOR
ATP Series
Macromatic ATP Series Triplexors are used in three load applications requiring both the optimization of load usage by equalizing the run time of multiple loads and additional capacity in case of excess load requirements.
As standard, these products operate as a normal Triplexor with three inputs. An optional version with an 8-position rotary switch is offered. This allows the unit to operate as either a:
(a) standard Triplexor (b) Triplexor locking Load 1, 2 or 3 as the fi rst to be
energized (Lead Load)
(c) standard Duplexor until system expansion requires
control for a third Load
(d) Duplexor locking Load 1 or 2 as the fi rst to be energized
(Lead Load). All versions offer an indication of a switch failure (out-of­sequence) - LEDs will fl ash if any switch closes out of sequence. Also, if power is lost and returns with more than just the LEAD Switch closed, there is a fi xed 10 second delay between energization of the fi rst output and subsequent outputs to prevent all Loads from coming on at the same time.
CONTROL PRODUCT
FUNCTION VOLTAGE NUMBER WIRING/SOCKET
TRIPLEXOR/ 120V AC ATP120A1 8 Pin Octal DUPLEXOR 24V AC/DC ATP024A1 70169-D
w/o Switch
TRIPLEXOR/ 120V AC ATP120A1R DUPLEXOR 24V AC/DC ATP024A1R w/ Switch
with appropriate
socket
800.238.7474
www.macromatic.com
sales@macromatic.com
DIAGRAM 184 TRIPLEXOR/ 120V AC ATP120A7R 12 Pin Square
DUPLEXOR 24V AC/DC ATP024A7R SD12-PC
w/ Switch
DIAGRAM 185