Macromatic ARP SERIES Installation Guide

INSTALLATION INSTRUCTIONS
ARP ALTERNATING RELAYS
901-0000 -060 Rev F
READ INSTRUCTIONS BEFOR E INSTALLING OR OPERATING T HIS DEVICE. KEEP FOR F UTUR E REFE RENCE .
Warning
Potentially hazardous voltages are present. Turn off all power supplying this equipment before connecting or disconnecting wiring.
(Replaces Rev E Dated Nov ember 2009)
1. Mount the appropriate 8, 11 or 12 pin socket in an enclosure.
2. Wire the socket per one of the diagrams below corresponding to your product. Any type of switch (float, manual, timing relay, pressure, or one with an isolated contact) can be used.
NOTE: If you are using the same control voltage for both the Alternating Relay and the two loads, you must add a jumper between Terminals 1 & 5 on the SPDT unit or T erminals 2, 6 & 10 on the 11 pin DPDT unit. If using multiple
switches on the DPDT cross-wired units, check to see the proper sequence of switch closures is followed, i.e., LEAD before LAG , STOP before LEAD, etc.
3. Set the low-profile selector switch to “AL TERNA TE” for normal operation. In this mode, the unit will operate as a normal Alternating Relay, alternating between the two loads on each subsequent closing and open of the control switch. Setting the selector switch to either “LOAD 1” or LOAD 2” will lock the unit to either one of the loads. By locking the Alternating Relay to one load, the other load can be removed for service without rewiring the first load for continuous operation. WA RNING: When the selector switch is locked in either the LOAD 1 or LOAD 2 position, it does not disconnect voltage from the equipment to be serviced.
4. Plug into socket.
January 2010
SPDT
(A6 and A6R suffix)
DPDT
(A2 and A2R suffix)
DPDT Cross Wired
(A3 and A3R suffix)
DPDT
(A4 and A4R suffix)
DPDT Cross Wired
(A5 and A5R suffix)
DPDT Cross Wired
for 3 Switches
(A8 and A8R suffix)