Lynx LYNXR, LYNXR24, LYNXR-EN Installation And Setup Manual

/<1;56HULHV
6HFXULW\6\VWHPV
,QVWDOODWLRQDQG6HWXS*XLGHIRU
/<1;5/<1;5DQG/<1;5(1
OFF
AWAY
STAY
AUX
®
K5963 5/01
®
RECOMMENDATIONS FOR PROPER PROTECTION
The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide Proper Coverage for the Protected Premises.
Recommendations for Smoke and Heat Detectors
With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted b e low.
Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of the household as follows: For minimum protection a smoke detector should be installed outside of each separate sleeping area, and on each additional floor of a multi-floor family living unit, including basements. T he installation of smoke detectors in kitchens, attics (finished or unfinished), or in garages is not normally recommended.
For additional protection the NFPA recommends that you install heat room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms, basements and attached garages.
or smoke detectors in the living room, dining
In addition, we recommend the following:
Install a smoke detector inside every bedroom where a smoker sleeps.
• Install a smoke detector inside every bedroom where someone sleeps with the door partly or completely closed. Smoke could be blocked by the closed door. Also, an alarm in the hallway outside may not wake up the sleeper if the door is closed.
• Install a smoke detector insid e bedrooms where electrical appliances (such as po rtable heaters, air conditioners or humidifiers) are used.
Install a smoke detector at both ends of a hallway if the hallway is more than 40 feet (12 meters) long.
• Install smoke detectors in any room where an alarm control is located, or in any room where alarm control connections to an AC source or phone lines are made. If detectors are not so located, a fire within the room could prevent the control from reporting a fire or an intrusion.
THIS CONTROL COMPLIES WITH NFPA REQUIREMENTS FOR TEMPORAL
PULSE SOUNDING OF FIRE NOTIFICATION APPLIANCES.
KITCHEN
DINING
LIVING ROOM
BEDROOM
BEDROOMBEDROOM
LIVING ROOM
BEDROOM
BASEMENT
KTCHN
TO
BEDROOMBEDROOM
BEDROOM
CLOSED
.
DOOR
TV ROOM
BEDROOM
Smoke Detectors for Minimum Protection Smoke Detectors for Additional Protection Heat-Activated Detectors
GARAGE
KITCHEN
DINING
LIVING ROOM
BEDROOM BEDROOM
01000-002-V0
Recommendations For Proper Intrusion Protection
For proper intrusion coverage, sensors should be located at every possible point of entry to a home or premises. This would include any skylights that may be present, and the upper windows in a multi-level building.
In addition, we recommend that radio b ackup be used in a securit y system. This will ensure that alarm signal s can be sent to the alarm monitoring station in the event that the telephone lines are out of order (alarm signals are normally sent over the phone lines, if connected to an alarm monitoring station).
–2–
Table of Contents
SYSTEM FEATURES....................................................................................................................... 4
MOUNTING THE CONTROL ......................................................................................................... 5
WIRING CONNECTIONS................................................................................................................ 6
AC POWER AND BACKUP BATTERY.........................................................................................9
INSTALLING WIRELESS ZONES................................................................................................ 11
MECHANICS OF PROGRAMMING............................................................................................. 14
ZONE RESPONSE TYPE DEFINITIONS...................................................................................... 15
DATA FIELD DESCRIPTIONS.....................................................................................................17
*56 ENHANCED ZONE PROGRAMMING MODE ..................................................................... 24
*80 DEVICE PROGRAMMING MENU MODE ........................................................................... 29
*81 ZONE LIST MENU MODE..................................................................................................... 32
*83 ENHANCED SEQUENTIAL MODE ...................................................................................... 33
*84 ASSIGN ZONE VOICE DESCRIPTORS................................................................................ 35
*85 RECORD CUSTOM VOICE DESCRIPTORS ........................................................................ 37
REMOTE PROGRAMMING/CONTROL (DOWNLOADING).................................................... 38
SYSTEM OPERATION .................................................................................................................. 39
TESTING THE SYSTEM................................................................................................................ 44
SYSTEM COMMUNICATION ...................................................................................................... 45
TROUBLESHOOTING GUIDE...................................................................................................... 47
REGULATORY AGENCY STATEMENTS.................................................................................. 49
SPECIFICATIONS.......................................................................................................................... 50
LYNXR/LYNXR24 PROGRAMMING DEFAULT TABLES....................................................... 51
LYNXR-EN PROGRAMMING DEFAULT TABLES................................................................... 52
INDEX............................................................................................................................................. 55
LIMITATIONS OF THIS SYSTEM STATEMENT....................................................................... 57
WARRANTY................................................................................................................................... 58
SUMMARY OF CONNECTIONS DIAGRAM.............................................................................. 59
–3–
System Features
LYNXR and LYNXR-EN are not intended for UL985 Household Fire applications
8
/
The LYNXR-Series controls are self-contained, rechargeable wireless control/communicators that feature easy installation and usage. A built-in speaker provides voice annunciation of system status along with voice descriptors of each zone (LYNXR-EN if programmed). The following illustration highlights the main features of this system.
ZONES and DEVICES
1 hardwire zone
Up to 24 wireless zones
(5800 Series Transmitters)
Up to 16 wireless button zones
Up to 8 Powerline Carrier Devices
Supports wireless keypads
8 USER CODES
Installer code
Master code
5 Secondary codes
Duress code
3 Panic functions
unless a 24-hour backup battery (P/N LYNXRCHKIT-HC) is installed. Powerline Carrier Devices are not UL Listed for fire or burglary functions and are intended
for home automation.
FEATURES
Real-time Clock display and Fixed-Word display
Message Center (for user recorded messages)
Voice announcement of system and zone status
Voice chime
Alarm Clock
Reminder
X-10 Scheduling
Latch Key Reports
Automatic Stay Arming
SYSTEM POWER
Primary Power: Ademco
1332/1332X10 Plug-in Transformer, 110VAC to 9VAC, 15VA output (1332CN in Canada)
Backup battery: Six 1.2V
rechargeable nickel-metal hydride batteries.
COMMUNICATION
Ademco Low Speed
Sescoa/Radionics
Ademco Express
Ademco Contact ID
Paging feature
PROGRAMMING
Options stored in EEROM
Can be uploaded, downloaded or
controlled via IBM-compatible computer using Compass downloader software and specified HAYES modem
OFF
AWAY
STAY
AUX
®
OTHER FEATURES
Exit error feature (detects difference between
an actual alarm and exit alarm caused by leaving a door open after the exit delay expires)
Event log stores up to 84 events
Macro/ 1-button paging
RF Jam Detection
Remote phone control
ALARM OUTPUT
Built-in sounder
Piezo output
(30mA max.)
Bell output
(120mA max.)
Steady output for
burglary/panic
Temporal pulse
output for fire alarms
Long Range
Radio/Alarm audio Verification
SPECIAL FEATURES
LYNXR24
24-hour backup
LYNXR-EN
Two-way voice
communication
Speaker phone
operation
–4–
Mounting the Control
Wall Mounting
The illustration below shows the front asse mbly separated from the back plate.
DO NOT disconnect the ribbon cable from the terminal strip board. Disconnect the cable only from the front assembly board.
Certain features differ between the LYNXR/LYNXR24 and the LYNXR-EN models. Verify the specific model being installed prior to programming the system.
LOCKING TABS
1.
Separate the front assembly from the
back plate by pressing on the two locking tabs at the top of the unit.
2
. Carefully disconnect the ribbon cable
from the front assembly,
ribbon cable connected to the terminal block PC board
plate contains the terminal block for
leaving the
. The back
PC BOARD
PART NUMBER
LOCATION
1
16
MXXXX
K5108
making wiring connections.
3.
Mount the back plate to a sturdy wall,
feeding the field wiring through the appropriate openings in the back plate.
4.
After wiring connections are made,
carefully reconnect the ribbon cable to
RED WIRE MARKING
the front assembly PC board connector (properly aligning the red wire).
5.
Before closing the assembly, verify
which LYNXR model is being installed
DISCONNECT
THIS END ONLY!
by checking the model number printed on the PC Boards. (Example: SALYNXREN indicates the unit being installed is a LYNXR-EN.)
6.
Snap the front assembly to the back
plate so it is held by the locking tabs.
PC BOARD PART NUMBER LOCATION
01009-003-V0
Desktop Mounting
If desired, an optional mounting base (model LYNX-DM, purchased separately) allows the LYNXR-Series controls to be used on a desktop.
1.
2.
3.
Use the two supplied screws to secure
Slide the control panel onto the
mounting base locking tabs
Bring all wiring through the bottom of
the mounting base, using one of the three wire entry locations, before making connections to the control panel.
Use tie-wraps to secure the wiring to
the built-in wire loops as needed. the control panel to the mountin
.
g base.
OFF
AWAY
STAY
AUX
®
WIRE ENTRY
KNOCKOUT
(1 of 3)
01000-004-V0
–5–
Wiring Connections
Wiring Overview
The following summarizes the connections required. Refer to the Wiring Connections paragraph and the Summary of Connections diagram on the inside back cover when making connections.
Use either the plug-in jacks or the screw terminals.
Supports 1 EOLR supervised zone using either closed circuit or open circuit sensors.
HARDWIRE ZONE
PHONE LINES
Compatible with ALARMNET 7845C and 7720
LONG RANGE RADIO
Devices. LYNXR and LYNXR24 are compat ible with the LYNXAVM.
POWERLINE CARRIER DEVICES
Supports up to 8 Powerline Carrier Devices for turning on/off lights and appliances. Requires the use of an ADEMCO 1332X10 transformer.
MXXXX
K5108
AC TRANSFORMER
Use the supplied ADEMCO 1332X10 9VAC, 15VA Plug-in Transformer (1332CN in Canada).
01009-005-V0
EARTH GROUND
See Earth Ground paragraph.
LOCAL SOUNDER DISABLE JUMPER
Remove the shorting jumper (shunt) to disable local sounder, leaving only the external sounder active.
UL NOTE:
Do not remove the shorting jumper (the shunt) for
UL installations.
The system includes a built-in sounder in the master keypad. If
desired, an external bell or piezo sounder can be connected.
Bell:
Use a 6-14V bell with maximum current drain of 120mA.
Piezo:
Use a 6-14V piezo sounder with maximum current drain of 30mA. This control complies with NFPA requirements for temporal pulse sounding of fire notification appliances. Temporal pulse sounding for a fire alarm consists of the following: 3 pulses – pause – 3 pulses – pause – 3 pulses. . .
SOUNDERS
Wiring Connections
1. Make Earth Ground Connection
for the lightning transient protective devices in this product to be effective. The following are examples of good earth grounds available at most installations: Metal Cold Water Pipe - Secure a noncorrosive metal strap (copper is recommended) to the pipe that is electrically connected and secured to which the ground lead. AC Power Outlet Ground - Available from 3-prong, 120VAC power outlets only. To test the integrity of the ground terminal, use a three-wire circuit tester with neon lamp indicators, such as the UL Listed Ideal Model 61–035, or equivalent, available at most electr ica l supp ly stores.
a. Connect terminal 1 to a good earth ground.
-
The designated earth ground terminal (1) must be terminated in a good earth ground
–6–
Wiring Connections
Wiring Connections
2. Make Phone Line Connections
seizure proceed to the appropriate steps below.
Local Seizure
a. Connect the incoming phone line to either the
8-position jack or terminals 2 (TIP) and 3 (RING).
b. Connect the handset phone lines to either the RJ11
jack or terminals 4 (TIP) and 5 (RING).
Full Line Seizure
with the incoming phone line. Plugging the Direct Connect Cord directly into the RJ31X jack, allows the control to seize the phone line when an alarm occurs and normal phone line usage by the premises phones if the plug needs to be removed.
a. Cut the incoming RING and TIP phone lines
(typically red and green, respectively) and connect them to RJ31X terminals 4 (red) and 5 (green).
b. Connect the premises end of the cut RING and TIP
wires to RJ31X terminals 1 (grey) and 8 (brown) respectively.
c. Wire the flying leads of a Direct Connect Cord to the
control’s phone terminals as shown in the diagram or plug into the 8-position jack.
d. Plug the Direct Connect Cord into the RJ31X jack.
HARDWIRED ZONE: If the EOLR is not at the end of the loop, the zone will not be properly supervised, and the system may not respond to an open circuit on the zone.
3. Make Hardwired Zone Connections -
circuit devices and has a response time of 350msec. Maximum zone resistance: 300 ohms, plus EOLR
Note: The hardwire zone cannot be used as a fire zone.
a. Connect sensors/contacts to the hardwired zone terminals 6 (+) and 7 (–). Refer to the Summary of Connections
diagram.
b. Connect closed circuit devices in series in the high (+) side of the loop. The EOL resistor must be connected in
series with the devices, following the
c. Connect open circuit devices in parallel across the loop. The 2000-ohm EOLR must be connected across the loop
at the last device.
4. Make External Sounder Connections -
6-14VDC bell (120mA max.; e.g. ADEMCO WAVE2EX). a. Connect a piezo sounder to terminals 10 (+) and 11 (–); OR a bell to terminals 11 (–) and 12 (+).
LOCAL SOUNDER DISABLE: The Master Keypad’s built-in piezo sounder can be disabled by removing the shorting jumper (shunt) on the terminal board. If disabled, however, no sounding
8/
will occur upon AC loss, since the external sounder does not operate when AC power is lost.
Do not remove shorting jumper (the shunt) for UL installations.
- For local or full line
: The control must be placed in
Zone 1 is an EOLR supervised zone that supports both open circuit and closed
last device.
The control panel supports either a 6-14VDC piezo sounder (30mA max.) or
series
INCOMING
PHONE LINE
RING TIP
6
7 8
DIRECT CONNECT CORD
8-POSITION
JACK
GREENRED
PREMISES PHONES
RING TIP
BROWN
TO
01000-008-V0
45
3
RJ31X
2
GREY
RED
1
BROWN
}
TO
PREMISES
PHONES
OR
OR
GREY
GREEN
TIP RING TIP RING
}
INCOMING
PHONE LINE
Full Line Seizure Connections
5. Disable Local Sounder Option
a. Remove the shorting jumper (shunt) on the terminal board.
6. Make Powerline Carrier Device Connections -
- If required the Master Keypad’s built-in piezo sounder can be disabled.
The control panel supports up to 8 Powerline Carrier Devices. If using these devices, they must be connected to the ADEMCO 1332X10 transformer, as shown in the SUMMARY OF CONNECTIONS diagram. a. Connect the com/data/sync/ lines from the ADEMCO 1332X10 transformer to terminals 9, 13, and 14, respectively.
Note: If not using the supplied Ademco connection cable, you may need to reverse the black and yellow wire connections. Refer
*80 Device Programming Menu Mode
to the
section for details on programming Powerline Carrier Devices.
–7–
Wiring Connections
TO PREVENT RISK OF SHOCK
DISCONNECT TELEPHONE LINE
RJ11
TO
HANDSET
PHONE
LINE
LOCAL SOUNDER
DISABLE SHUNT
REMOVE TO
THE LYNX SERIES CONTROLS ARE EQUIPPED WITH AN INTEGRAL RECHARGEABLE BATTERY PACK. LYNXR: P/N LYNXRCHKIT-SC LYNXR24: P/N LYNXRCHKIT-HC LYNXR-EN: P/N LYNXRCHKIT-SC OR P/N LYNXRCHKIT-HC
REPLACE EVERY FOUR YEARS
WARNING:
AT TELECOM JACK BEFORE
SERVICING THIS UNIT .
EARTH
GROUND
8
POS
JACK
INCOMING
PHONE
LINE
DISABLE
GROUND
1
EARTH
2
TIP
INCOMING
TELEPHONE
LINE
PHONE
3
4
TIP
RING
RING
PREMISES
TELEPHONE
WEEKL Y TESTING IS
REQUIRED TO ENSURE
PROPER OPERATION
OF THIS SYSTEM
ALL OUTPUT CIRCUITS ARE POWER LIMITED.
AAV / LRR
TRIGGER
(LYNXR/LYNR24)
LRR
TRIGGER
EOLR
(LYNXR-EN)
7
TRIGGER
SIGNAL
(NEG)
SOUNDERS
12
865
9
( )
USE ONLY 1332/1332X10 OR 1332CN
11
10
(+)( )
( )
(+)
PIEZO
BELL
6-14VDC 30mA max.
TRANSFORMERS PROVIDED
6-14VDC
120mA max.
(e.g. W AVE2EX)
NOTE
ZONE
(+)
HARD
WIRED
ZONE
2k OHMS
PLCD
14
13
DATA
SYNC
OUT
IN
POWERLINE
CARRIER DEVICES
AC
15
16
1332/
1332X10/
1332CN
PLUG-IN
TRANSFORMER
9VAC, 15VA
AC
AC
SYNC
COM
DATA
1332X10
ONLY
CONNECTIONS
01009-009-V0
–8–
AC Power and Backup Battery
The system is powered by a 9VAC, 15VA Plug-in Transformer, ADEMCO 1332/1332X10 (1332CN in Canada). Refer to the wiring table below for wire gauge and length.
Distance from Transformer
Use only the provided ADEMCO 1332/1332X10 or 1332CN Transformer
to Control
Up to 75 feet #20
75 to 150 feet #18
150 to 300 feet #16
Wire Gauge
Wiring to the AC Transformer must not exceed 300 feet using 16-gauge wire. The voltage reading between terminals 15 and 16 of the control must not fall below 9.00VAC.
Do not plug the transformer into the AC outlet until after all wiring connections have been made.
Backup battery.
In the event of an AC power loss, the system is supported by a long life backup battery that is supervised for connection and for low voltage conditio ns. If the battery is missing, or a low battery condition is detected, a “low battery” message is displayed and a report is sent to the central station. In addition, the system will beep once every 45 seconds to audibly indicate a low battery condition (p ress any key to stop the beeping).
AC Power and Rechargeable Backup Battery
Connecting AC Power and backup battery
1.
Connect wires from the 1332/1332X10 (1332CN in
Canada) AC Transformer to terminals 15 and 16 as shown in the wiring diagram.
2.
Remove battery retainer.
3.
Peel the backing from tape on the back plate.
4.
Insert battery pack into back plate.
5.
Install battery retainer.
6.
Connect battery connector to receptacle on
terminal block PC board.
7.
After all wiring connections have been made, snap
the front assembly to the back plate and plug the transformer into a 24-hour, 110VAC unswitched outlet.
8.
Rechargeable batteries may take up to 48-hours to
fully charge. The “LOW BAT” message should clear within four hours or by entering Test Mode.
BATTERY
PACK
BATTERY
RECEPTACLE
RETAINER
1
TAPE
16
WIRING
TERMINALS
NOTE
LYNXRCHKIT-HC
BATTERY PACK SHOWN
MXXXX
K5108
01009-007-V0
Ensure the cover is snapped closed prior to applying AC power.
–9–
AC Power and Backup Battery
AC Power and Rechargeable Backup Battery
The LYNXR Series is equipped with an integral, replaceable, rechargeable battery pack composed of six (6) rechargeable
1.2-volt nickel-metal hydride batteries. Select the appro priate battery pack, based on the installation’s requirement, and install the battery pack.
Model/Part Number
LYNXRCHKIT-SC 4-hours (minimum) Approximately 1-hour before battery depletion LYNXRCHKIT-HC 24-hours (minimum) At least 1-hour before battery depletion
Battery StandbyTime
Replacing the Rechargeable Battery
1.
When battery replacement is required, unplug
the transformer from the wall outlet, and open the control panel cover.
2.
Remove the battery retainer and disconnect the
battery pack connector from the receptacle on the terminal block PC board.
3.
Remove the battery pack from the back plate.
4.
If required, replace the tape that secures the
battery pack.
5.
Install a replacement battery pack (P/N
LYNXRCHKIT-SC or LYNXRCHKIT-HC) into the back plate.
6.
Install the battery retainer.
7.
Connect the battery connector to the receptacle
on the terminal block PC board.
8.
After the wiring connection has been made, snap
the front assembly to the back plate.
9.
Plug the transformer into a 24-hour, 110VAC
unswitched outlet.
10.
Rechargeable batteries may take up to 48-hours
to fully charge. The “LOW BAT” message should clear within four hours or by entering Test Mode.
Low Battery Notification
LYNXRCHKIT-HC OR LYNXRCHKIT-SC
BATTERY CONNECTOR
TAPE
MXXXX
K5108
01009-006-V0
RETAINER
BATTERY
PACK
BATTERY
RECEPTACLE
Ensure the control panel assembly is snapped closed prior to applying AC power.
–10–
Installing Wireless Zones
General Information
Zones: The control supports up to 24 wireless zones using 5800 Series transmitters, and up to 16 wireless buttons. Range: The built-in RF receiver can detect signals from wireless transmitters within a nominal range of 200 feet. Transmitters: 5800 Series transmitters have built-in serial numbers that must be entered into the system using the
*
56 or *83 interactive mode, or input to the control via the downloader. 5800 Series transmitters (except the 5800RL and 5827, described separately) do not have DIP switches. Each transmitter's zone number is programmed into the system in loops or inputs). On the 5816, for example, the wire connection terminal block is loop 1, the reed contact is loop 2. Each loop must be assigned a different zone number.
8
For button transmitters (RF "keys") such as the 5804 and 5801, you must assign a unique zone number to each individual button used on the transmitter. Each button on the transmitter also has a pre-designated loop or input number, which is automatically displayed.
House Identification
If you are using a 5804BD/5804BDV, 5827, or 5827BD Wireless Keypad with the system, you must program a House ID Code (01–31) in field establish proper communicatio n, and the keypad must be set to the sa me ID. House ID 00 disables all wireless keypads. An RF House ID is not necessary for other 5800 Series transmitters; the entry should be left at “00” (default) in those cases. The 5827 reports low battery status as zone “00”.
Transmitter Supervision
Except for some transmitters/keypads that may be carried off-premises (5804, 5804BD, 5804BDV, 5804E, 5804WATCH, 5827 and 5827BD), each transmitter is supervised by a check-in signal that is sent to the receiver at 70–90 minute intervals. If at least one check-in is not received from each supervised transmitter within a 12-hour period, the "missing" transmitter number(s) and "FAULT" will be displayed. The supervision for a particular transmitter in the system that may also be carried off the premises (5801, 5802MN) may be turned off by entering it as a "UR" (unsupervised RF) type, as described in the 5800 Series transmitters have built-in tamper protection and will annunciate as a fault condition if covers are removed.
Note: The 5804E and 5804WATCH transmitters are only supported by the
Transmitter Input Types
All of the transmitters described have one or more unique factory-assigned input (loop) ID codes. Each of the inputs requires its own programming zone (e.g., a 5804's four inputs require four button zones). Transmitters can be entered as one of the following types (see transmitter’s instructions for approp riate input type):
Type Description "RF" (Supervised RF)
"UR" (Unsupervised RF)
"BR" (Unsupervised Button RF)
*
56 mode. Some transmitters, such as the 5816 and 5817, can support more than one "zone" (referred to as
The 5816 and 5817 Transmitters do not have EOL supervision of their loop wiring. Therefore, for UL Household Burglary installations, the loop wiring may not exceed 3 feet.
/
The 5800RL, 5802MN, 5802MN2, 5804, 5804BD, 5804BDV, 5804E, 5804WATCH, 5814, 5816TEMP, 5819, 5819S(WHS & BRS), 5827BD, and 5850(GBD) transmitters are not intended for any UL installations.
*
24 to
1
2
4
3
5
7
6
8
*
9
0
#
5827 5827BD5804BD/5804BDV
*56 Enhanced Zone Programming Mode
section.
5806/5807/5808 5890 / 5890PI5816
LYNXR-EN.
Sends periodic check-in signals, as well as fault, restore, and low battery signals. The transmitter must remain within the receiver's range.
Sends all the signals that the "RF" type does, b ut the control does no t supervise the check-in signals. The transmitter may therefore be carried off-premises.
These only send fault signals. They do not send lo w ba ttery signals until they are activated. The transmitter may be carried off-premises.
1
2
3
4
5
6
7
8
9
*
0
#
01009-010-V0
–11–
Installing Wireless Zones
Transmitter Battery Life
• Batteries in the wireless transmitters may last from 4–7 years, depending on the environment, usage, and the specific wireless device being used. Factors such as humid ity, high or low te mperatures, as well as large swings in te mperature may all reduce the actual batter y life in a given installation. T he wireless s ystem ca n identi fy a true lo w battery situation, thus allowing the dealer or user of the system time to arrange a change of battery and maintain protection for that point within the system.
• Button-type transmitters should be periodically tested for battery life. The 5801, 5802MN, 5802MN2, 5804, 5804BD, 5804BDV, 5804E, and 5804WATCH button transmitters have replaceable batteries.
Note: The 5804E and 5804WATCH transmitters are only supported by the
LYNXR-EN.
Using the Transmitter Sniffer Mode
Use this mode after all transmitters have been entered to check that all transmitters have been properly progra mmed.
1. Enter Installer code (4112) + [#] + 3.
Note: If the communicator is in the process of sending a report to the ce ntral statio n, the syste m w ill not go i nto the Sniffer
mode. If so, wait a few minutes and try again.
2. The keypad will display all zone nu mbers of wireless u nits pr ogrammed into the syste m. Fault each tra nsmitter in turn, causing each one to send a signal. As the system receives a signal from each of the transmitters, the zone number of that transmitter will disappear from the display. The transmitters may be chec ked up on installatio n, or in an installed system.
3. When all transmitters have been checked, exit the Sniffer mode b y keying Installer Code (4112) + OFF.
Notes:
• Sniffer mode does not automatically ex pire. You must manual ly exit (Instal ler Code + OFF) Sniffer mode to return to
normal operation.
• All BR-type units must physically be activated to clear the display, since they do not automatically send check-in
signals.
• When one button of a transmitter (RF, UR, or BR) is activated, all zones assigned to other buttons on that transmitter
are cleared. This also applies to 5816 and 5817 transmitters that have multiple loops (zones).
• Any transmitter that is not “entered” will not turn off its zone number.
Go/No Go Test Mode
The Go/No Go tests will verify adequate RF signal strength from the proposed transmitter location, and allow you to reorient or relocate transmitters if necessary, before mounting the transmitters permanently. This mode is similar to the transmitter Test mode, except that the wireless receiver gain is reduced. This will enable you to make sure that the RF signal from each transmitter is received with sufficient signal amplitude when the system is in the normal operating mode.
1. Enter Installer Code (4112) + [#] + 8.
2. Once you have placed transmitters in their desired locations and the approximate length of wire to be run to sensors is connected to the transmitter's screw terminals (if used), fault eac h transmitter. Do not conduct this test with your hand wrapped around the transmitter, as this will cause inaccurate results
Note: On button type transmitters whose buttons have been set to Arm AWAY, Arm STAY, or Disarm, pressing a
button will take the system out of the Go/No Go Test mode and cause that action.
a. The keypad will beep three times to indicate signal reception and display the appropriate zone number. b. If the keypad does not b eep, reorient o r move the trans mitter to ano ther location. Usual ly a few inches i n
either direction is all that is required.
4. If each transmitter produces the proper keypad response when it is faulted, you can then permanently mount each of the transmitters according to the instructions provided with them.
5. Exit the Go/No Go Test mode by entering: Installer Code (4112) + OFF.
5801
ON
OFF
5804 /5804E
5802MN
01009-011-V0
–12–
Installing Wireless Zones
5806/5807/5808/5808LST
ENROLL AS
LOOP 2
(REED)
LOOP 3
(TERMINALS)
5819S (WHS & BRS)
ENROLL AS
5800 Series Transmitter Loop Numbers
The following illustration shows the compatible transmitters, their associated input types and loop designations.
5800RL
SET
HOUSE ID
LOOP 1
"RF"
LOOP 1 (INTERNAL SHOCK SENSOR
"RF"
LOOP 4
YOU MUST
ENROLL
THIS
BUTTON
"UR" OR "RF"
ENROLL AS
5801
ENROLL AS
5814
1
2
4
5
7
8
*
0
5827
PROGRAM
HOUSE ID
LOOP 3
LOOP 2 LOOP 1
LOOP 1
"RF"
3 6 9 #
5802 MN
ENROLL AS
"UR" OR "RF"
5816
ENROLL AS
1
2
3
4
5
6
7
8
9
*
0
#
5827BD
PROGRAM
HOUSE ID
LOOP
1
LOOP 2 (REED)
LOOP 1 (TERMINALS)
"RF"
LOOP
1
ALTERNATE
POSITION
FOR LOOP 2
5802 MN2
ENROLL AS
"UR" OR "RF"
5816MN
ENROLL AS
5849
ENROLL AS
LOOP 2 (REED)
LOOP 1 (TERMINALS)
"RF"
LOOP 1 (SOUND)
"RF"
(Refer to this information when programming transmitters)
LOOP 4
LOOP 4
YOU MUST
ENROLL
THIS
BUTTON
ON
OFF
5804/5804E
ENROLL AS "BR"
5816TEMP
ENROLL AS
"RF"
LOOP 3
LOOP 2 LOOP 1
LOOP 1 (TEMP SENSOR)
5850 (GBD)
ENROLL AS
LOOP 3
5804BD/5804BDV
PROGRAM HOUSE ID
5817
ENROLL AS
(Green) (Red) (Yellow)
"RF"
ENROLL AS
LOOP 1 (PRIMARY)
LOOP 2 (AUX. CENTER)
LOOP 3 (AUX. RIGHT)
"RF"
LOOP 2
"BR"
LOOP 4 YOU MUST ENROLL THIS BUTTON
LOOP 1
5818
ENROLL AS
5890/5890PI
ENROLL AS
LOOP 1
"RF"
YOU MUST
ENROLL BUTTON
LOOP 3
LOOP 1 (MOTION)
"RF"
THIS
5804WATCH
(TERMINALS)
LOOP 2
(REED)
LOOP 3
1:15:00 1:13:16
ENROLL AS
5819
LOOP 1
LOOP 2
ENROLL AS
LOOP 1 (TERMINALS)
"RF"
Notes: (1 ) You must enroll loop 4 on the 5801, 5804, 5804BD, 5804B DV, 5804E and 5804WATCH transmitter s, regardless of whether or not the
loop is used.
(2) The 5804E and 5804WATCH tra nsmitter s are only supported by the LYNXR-EN.
The 5800RL, 5802MN, 5802MN2, 5804, 5804BD, 5804BDV, 5804E, 5804WATCH, 5814, 5816TEMP, 5819, 5819S(W HS &
8
/
BRS), 5827BD, and 5850(GBD) wireless transmitters are not intended for any UL installations.
Setting DIP Switches on the 5800RL and 5827 Transmitter(s)
Set the 5800RL and 5827 Transmitters to the programmed House ID, using its DIP switches. (OFF position is indicated by ---)
Notes: (1) The 5827 transmitter can not be used in conjunction with the *58 RF Jam Detection feature. (2) The 5800RL cannot be used in conjunction with the Auto Arm (scheduled arming) feature.
234561
SW-1 ACTIVATES
SW-6 SETS
MODE SETTING
2-6 SETS HOUSE ID
SHOWN SET FOR HOUSE ID# 12
SWITCH UP FOR "ON"
1
5
2 3 4 HOUSE ID
SHOWN SET FOR HOUSE ID# 30
SWITCH UP FOR "ON"
MODE
SWITCH DOWN
FOR "OFF"
01000-014-V1
Setting 5800RL DIP Switches
SWITCH DOWN FOR "OFF"
01000-013-VO
Setting 5827 DIP Switches
ID
0 --- --- --- --- --- 16 ON --- --- --- --­1 --- --- --- --- ON 17 ON --- --- --- ON 2 --- --- --- ON --- 18 ON --- --- ON --­3 --- --- --- ON ON 19 ON --- --- ON ON 4 --- --- ON --- --- 20 ON --- ON --- --­5 --- --- ON --- ON 21 ON --- ON --- ON 6 --- --- ON ON --- 22 ON --- ON ON --­7 --- --- ON ON ON 23 ON --- ON ON ON 8 --- ON --- --- --- 24 ON ON --- --- ---
9 --- ON --- --- ON 25 ON ON --- --- ON 10 --- ON --- ON --- 26 ON ON --- ON --­11 --- ON --- ON ON 27 ON ON --- ON ON 12 --- ON ON --- --- 28 ON ON ON --- --­13 --- ON ON --- ON 29 ON ON ON --- ON 14 --- ON ON ON --- 30 ON ON ON ON --­15 --- ON ON ON ON 31 ON ON ON ON ON
DIP SWITCH POSITIONS DIP SWITCH POSITIONS House
2 3 4 5 6
5800RL DIP SWITCH TABLE
5827 WIRELESS KEYPAD DIP SWITCH TABLE
DIP SWITCH POSITIONS DIP SWITCH POSITIONS House
1 2 3 4 5 1 --- --- --- --- ON 17 ON --- --- --- ON 2 --- --- --- ON --- 18 ON --- --- ON --­3 --- --- --- ON ON 19 ON --- --- ON ON 4 --- --- ON --- --- 20 ON --- ON --- --­5 --- --- ON --- ON 21 ON --- ON --- ON 6 --- --- ON ON --- 22 ON --- ON ON --­7 --- --- ON ON ON 23 ON --- ON ON ON 8 --- ON --- --- --- 24 ON ON --- --- --­9 --- ON --- --- ON 25 ON ON --- --- ON
10 --- ON --- ON --- 26 ON ON --- ON --­11 --- ON --- ON ON 27 ON ON --- ON ON 12 --- ON ON --- --- 28 ON ON ON --- --­13 --- ON ON --- ON 29 ON ON ON --- ON 14 --- ON ON ON --- 30 ON ON ON ON --­15 --- ON ON ON ON 31 ON ON ON ON ON 16 ON --- --- --- ---
House
ID
2 3 4 5 6
House
1 2 3 4 5
–13–
5809
"RF"
01009-012-V0
LOOP 1
Mechanics of Programming
General Programming Information
Programming options are stored in nonremovable, electrical ly erasable, nonvolatile EEROM memory. You can program the system at any time, even at the installer's premises p rior to the actual installation. Simply apply power temporarily to the Control and then program the unit as desired. There are two programming modes:
Data field programming (used for setting various syste m options)
Interactive menu mode programming (used for programming zone information, programming Powerline Carrier Devices,
and for entering transmitter serial numbers) You can also program this system remotely, using an IBM Personal Computer, a modem, and Compass Downloader for Windows. See the Remote Programming/Control (Downloading) section.
Note:
You may find it convenient to adjust the volume setting before entering the Program Mode. This will allow you to clearly hear the
feedback announcements or system beeps in the Programming Mode, of the system’s built-in speaker. To adjust the volume, press FUNCTION + VOLUME+ [3] or [6]. Upon exiting the Program Mode, the system will reset the volume to the default value (mid level).
!
Entering Program Mode - Use one of the following methods:
a) Press both the [] and [#] keys at the same time, within 50 seconds after power is applied to the Control or from exitin g
Programming mode, OR
b) After power-up, enter the Installer Code (4 1 1 2) + 8 0 0.
Note:
If a different Installer Code is subsequently programmed, use it instead of 4112 to enter the Programming mode.
Once you have entered the Program mode, data field *20 will be displayed (this is the first data field in the system) and bo th keypad LEDs will flash.
Programming a Data Field
1. Press [*] + Field No. (for example, *21), then make the required entry.
2. When you have completely programmed a data field, the ke ypad will “beep” three times and then automatically display
the next data field in sequence. To go to a different field, press [*] plus the desired field number.
3. If the number of dig its that you need to enter in a data field is less than the ma ximum number of digits available (eg.
phone number field), enter the desired data, then press [*
4. If you enter a nonexistent field, the keypad will display “EE”. Simply re-enter [*] plus a valid field number.
To view a data field without making changes, press [#] + Field No. Data will be displayed for that field.
To delete an entry in a field, press [*] + Field No. + [*]. (Applies only to fields
Interactive Mode Programming (*56, *80, *81, *83, *84, *85)
Press [*] + interactive mode No. (for example, A detailed procedure (with displays of prompts) is provided in later sections of this manual.
*56 Enhanced Zone Programming Mode *
80 Device Programming Menu Mode
*
81 Zone List Menu Mode *83 Enhanced Sequential Mode *84 Assign Zone Voice Descriptors Voice descriptors for each zone *85 Record Custom Voice Descriptors Up to 5 custom voice descriptors for zones
Loading Factory Defaults
To load the factory defaults, enter the Programming mode, press tables 1-4 at the back of this manual, or press “0” if you are not selecting a default table.
If loading a default table, any data that has already been programmed into the system will be changed according to
!
the default table selected!
*
96 resets all the subscriber account numbers and CSID in preparation for an initial download. Exiting Program Mode
*
99 allows re-entry into the Program mode using Installer Code + 8 0 0.
*
98 inhibits re-entry into the Programming mode using the Installer Code.
Note:
After exiting program mode (or upon power-up), the system takes up to a minute to reset. To bypass the reset delay, press [#] + [0].
Certain features differ between the LYNXR/LYNXR24 and the LYNXR-EN models. Verify the specific model being installed prior to the system programming.
(This method disabled if exit Program mode using *98.)
]
to program the next data field.
*
40–*44, *88 and *94).
*
56). The keypad will display the first of a series of prompts.
Interactive Mode Used to Program
Zone characteristics, report codes, and serial numbers
5800 Series transmitter serial numbers
Powerline Carrier Devices Zone Lists for powerline carrier activation
*
97, then press number 1, 2, 3, or 4 to select from default
–14–
Zone Response Type Definitions
General Information
During programming, you must assign a zone type to each zone, which defines the way in which the system responds to faults in that zone. Zone types are defined below.
Type 00
Zone Not Used
Type 01
Entry/Exit Burglary #1
01000-017-V0
Type 02
Entry/Exit Burglary #2
01000-017-V0
Zone type 00 is used to program a zone that is not used.
Zone type 01 is usually assigned to sensors or contacts on primary entry and exit doors.
Zone Characteristics:
Entry delay #1 is programmable from 0-99 seconds (field *35).
Exit delay is independently programmable from 0-99 seconds (field *34).
Exit and entry delays when armed in AWAY or STAY mode.
No entry delay when armed in INSTANT or MAXIMUM mode.
Exit delay regardless of the arming mode selected.
Zone type 02 is usually assigned to sensors or contacts on which secondary entry and exit doors that might be further from the keypad (typically used for a garage, loading dock, or basement door).
Zone Characteristics:
Entry delay #2 is programmable from 0-99 seconds (field *36).
Exit delay is independently programmable from 0-99 seconds (field *34).
Secondary entry delay, if armed in the AWAY or STAY mode.
No entry delay when armed in the STAY NO DELAY or AWAY NO DELAY mode.
Exit delay begins regardless of the arming mode selected.
Type 03
Perimeter Burglary
01000-018-V0
Type 04
Interior, Follower
5890 / 5890PI
01000-019-V1
Type 05
Trouble by Day/
Alarm by Night
Type 06 24-hour
Silent Alarm
Zone type 03 is usually assigned to all sensors or contacts on exterior doors and windows.
Zone Characteristics:
Instant alarm, when armed in AWAY, STAY, STAY NO DELAY, or AWAY NO DELAY
mode.
Zone type 04 is usually assigned to a zone covering an entry area (i.e.: foyer, lobby, or hallway) that one must pass upon entry (after faulting the entry/exit zone) to reach the keypad. It provides an instant alarm if the entry/exit zone is not violated first, and protects an area in the event an intruder has hidden on the premises before the system is armed, or gains access to the premises through an unprotected area.
Zone Characteristics:
Delayed alarm (using the programmed entry/exit time) if entry/exit (types 01 or 02) or
interior-with-delay (type 10) zone is faulted first. Instant alarm in all other situations.
Active when armed in AWAY or AWAY NO DELAY mode.
Bypassed automatically when armed in STAY or STAY NO DELAY mode.
Zone type 05 is usually assigned to a zone, that contains foil-protected doors or windows or covers a sensitive area (i.e.: stock room, drug supply room, etc.) It can also be used on a sensor or contact in an area where immediate notification of an entry is desired.
Zone Characteristics:
Instant alarm, when armed in AWAY, STAY, STAY NO DELAY, or AWAY NO DELAY
(night) mode. Provides a latched trouble sounding from the keypad and, if desired, a central station report
during the disarmed state (day).
Zone type 0 6 is usually assigned to a zone conta ining an E mergency but ton (silent emergency).
Zone Characteristics:
Sends a report to the central station but provides no keypad display or sounding.
–15–
Zone Response Type Definitions
Zone type 07 is usually assigned to a zone containing an Emergency button (audible emergency).
Zone Characteristics:
Sends a report to the central station, and provides alarm sounds externally and
at the keypad.
Zone type 08 is u sually assig ned to a zone c ontaining a b utton for us e in personal emergencies or to a zone containing monitoring devices (i.e.: water or temperature sensors, etc.).
Zone Characteristics:
Sends a report to the central station and provides an alarm sound at the keypad.
(No bell output is provided and there is no keypad timeout.)
Zone type 09 can be assigned to any wireless zone used as a fire zone. This zone type is always active and cannot be bypassed.
Zone Characteristics
Bell output will pulse when this zone type is alarmed.
:
Zone type 10 is bypassed when the panel is armed in the STAY or STAY NO DELAY mode.
Zone Characteristics
Entry delay #1 (with programmed entry time) when armed in the AWAY
mode. Entry delay begins whenever sensors in this zone are violated, regardless of
whether an entry/exit delay zone was tripped first. No entry delay when armed in the
Exit delay regardless of the arming mode selected.
:
AWAY NO DELAY
5806/5807/5808
01000-020-V0
Type 07 24-hour
Audible Alarm
Type 08
24-hour
Auxiliary Alarm
Type 09
Supervised
Fire
Type 10
Interior w/Delay
mode.
Type 20
Arm–Stay
Type 21
Arm–Away
Type 22
Disarm
Type 23
No Alarm Response
Type 24
Silent Burglary
Zone type 20 is a special-purpose zone type used with 5800 Series wireless pushbutton units.
Zone Characteristics:
Exit delay regardless of the arming mode selected.
System is armed in the S TAY mode when the zone is activat ed.
Zone number is sent to the central station as a u ser number when arming or
disarming.
Zone type 21 is a special-purpose zone type used with 5800 Series wireless pushbutton units.
Zone Characteristics
System is armed in the AWAY mode when the zone is activated.
Zone number is sent to the central station as a u ser number when arming or
disarming.
:
Zone type 22 is a special-purpose zone type used with 5800 series wireless pushbutton.
Zone Characteristics
Disarms the system when the zone is activated.
:
Zone type 23 can be used on a zone when a Powerline Carrier Device (e.g., X-10) action is desired, but with no accompanying alarm (e.g., front door light).
Zone type 24 is usually assigned sensors or contacts on exterior doors and windows where bells and/or sirens are NOT desired.
Zone Characteristics
Instant alarm, with NO audible indication when is armed in the AWAY, STAY,
STAY NO DELAY, or AWAY NO DELAY mode. Report sent to the central station.
Note:
Keypa d beeps if the zone i s faulted when system i s disarmed and Chim e mode is
on.
:
–16–
Data Field Descriptions
Defaults (where applicable) are Indicated in Text.
The following pages list all data fields in this Control (in numerical order). Use the blank programming form to record the data for this installation. Note that both ke ypad LEDs flash while in Programming mode.
Note: Entry of a number other than the one specified will give unpredictable results.
* *
*
*
*24
*
*
*
*
*
*
*
*
*
20 21
22
23
25
26
27
29
30
31
32
33
34
Installer Code
Enter 4 digits, 0-9
Quick Arm Enable
0 = do not allow quick arm 1 = allow quick arm
Keypad Backlight Timeout
0 = no timeout; always backlight keys 1 = turn backlighting off after inactivity
Forced Bypass
0 = no forced bypass 1 = provide automatic bypass of all open (faulted) zones
RF House ID Code
00 = disable all wireless keypad usage 01-31 = House ID
Powerline Carrier Device
0 = A 4 = E 8 = I # + 12 = M 1 = B 5 = F 9 = J # + 13 = N 2 = C 6 = G # + 10 = K # + 14 = O 3 = D 7 = H # + 11 = L # + 15 = P
Chime by Zone
0 = no (chimes on fault of any entry/exit or perimeter
zone when Chime mode is activated
1 = yes (chimes on fault of those zones assigned to
Zone List 3 when Chime mode on)
Real Time Clock Display
0 = do not display the time 1 = display the time
Daylight Savings Time Sta r t/End Month
0, 0 = no daylight saving time used 1-12 = start month and end month
Daylight Savings Time Start/End Week
0 = disable 4 = fourth weekend 1 = first weekend of month 5 = last weekend 2 = second weekend 6 = next to last 3 = third weekend 7 = 3
Single Alarm Sounding Per Zone
(per armed period)
0 = no limit on alarm sounding per zone 1 = limit alarm sounding to once per arming period for a
given zone
LYNXR/LYNXR24
selected in field *91
LYNXR-EN
Range Radio is connected to the Trigger Single (Neg.) terminal #8.
Fire Sounder Timeout
0 = yes, fire sounder timeout after time programmed in
field *33
1 = no fire sounder timeout; continue sounding until
manually turned off
Alarm Bell Timeout
0 = No timeout 2 = 8 min 4 = 16 min 1 = 4 min 3 = 12 min
Exit Delay
00-99 = exit delay time in seconds
- Applies to Long Range Radio Output if “0” is
- Applies to Long Range Radio Output if a Long
(X-10)
rd
from last
House ID
The Installer Code is us ed to enter the 4-digit Master Security C o de. See "Master Code" in the
If enabled, security code is not required to arm the system. The user simply presses and holds down the AWAY or STAY key to arm.
This option allows the choice of either always backlighting the keypad or turning the backlighting off after 10 seco nds of keypad inactivity.
All zones bypassed by this function will be displayed after the bypass is initiated.
Note:
UL installations: must be 0 (no forced bypass)
The House ID identifies receivers and wireless keypads. If a 5827/5827BD Wireless Keypad or 5804BD/580 4BDV Transmitter is
to be used, a House ID Code MUST be entered, and the keypad should be set to the same ID.
Powerline Carrier Devices require a House ID. This field identifies this House ID to the Control. The Powerline Carrier Devices are programmed in field * 80.
This option allows the installer to define the specific zones intended to chime when faulted while the s ystem is in Chime m o de. If enabled, these zones are defined in zone list 3 (see
Refer to the User’s Manual for setting the clock time and date.
Enter # + 10 for 10, # + 11 for 11, and # + 12 for 12.
Enter the appropr iate start and end weekend of the month.
UL installations: must be 0 (no li mit) This field applies only to burglary zones (zone response types 1-5, 10), and affects long range radio reporting but does not affect central station reporting.
Note:
This field applies only to the bell and does not affect keypad
sounds.
This Control complies with NFPA requirements for temporal pulse sounding of fire notification appliances. Temporal pulse sounding for a fire alarm consists of the following: 3 pulses – pause – 3 pulses – pause – 3 pulses. . .
This field determines whether the external sounder will shut off after time allowed, or continue until manually turned off. UL installations: must be set for a minimum of 4 min (option 1)
The system will wait the time entered before sounding an alarm if the exit door is left open af ter the system has been armed. UL installations: must be set for a maximum of 60 seconds
System Operation
section for proce dur e .
*81 Zone List Menu Mode
–17–
).
Data Field Descriptions
*
35
*
36
*
37
*
38
*
39
DIALER PROGRAMMING (*40–*50)
Fields *40, *41, *42:
a pause
*
40
*
41
Entry Delay 01
00-99 = entry delay time in seconds.
Entry Delay 02
00-99 = entry delay time in seconds.
Audible Exit Warning/Quick Exit
Exit Warning Quick Exit
0 = no exit warning sound 1 = provide exit warning sound
when armed AWAY
Confirmation of Arming Ding
0 = no ding 1 = confirmation ding after arming system 2 = confirmation ding after arming from RF button or
RF keypad only
Power Up In Previous State
0 = always power up in a disarmed state 1 = assume the system status prior to power-down
Enter up to the number of digits shown. Do not fill unused spaces. Enter 0–9, # + 11 for ‘*’; # + 12 for ‘#’; # + 13 for
(2 seconds)
PABX Access Code
Enter up to 6 digits if PABX is needed to access an outside line.
Primary Phone No.
Enter up to 20 digits.
0 = no quick exit 1 = allow quick
exit
*
42
Secondary Phone No.
Enter up to 24 digits.
Fields *43 and *44:
Enter [*] as the fourth digit if a 3-digit account number (for 3+1 dialer reporting format) is used. Enter 0 as the first digit of a 4-digit account number for Nos. 0000–0999. Exit field by pressing [*] if only 3 digits are u sed. To clear entries fro m field, press *43
See blank Programming Form for examples of account number entries. If using the paging feature, do not enter a leading 0 in the subscriber account number, and do not use digits A-F anywhere in the number. Some paging systems provide voice mail capability, which is activated by a leading 0 in the message. Enter digits 0–9; # +11=B; # +12=C; # +13=D; # +14=E; or # +15=F.
*
43
*
44
*
47
Primary Subs Account No.
Enter four digits .
Secondary Subs Account No.
Enter four digits.
Phone System Select
Note:
For LYNXR/LYNXR24 only options 0, 1, 2, and
3 are applicable. For LYNXR-EN all options apply.
Central Station Pulse Tone Pulse Tone
No WATS
WATS
0 = No Speaker Phone
2 = No Speaker Phone
1 = No Speaker Phone
3 = No Speaker Phone
Dialing Mode
4 = With
Speaker
Phone
6 = With Speaker
Phone
5 = With Speaker Phone
7 = With Speaker Phone
The system will wait the time entered before sounding alarm upon entering if system is not disarmed. UL installations: must be set for a maximum of 45 seconds
The system will wait the time entered before sounding alarm upon entering. UL installations: must be set for a maximum of 45 seconds
Exit Warning: Soun d consists of slow continuous beeps until last 5 seconds, when it chan ges to fast beeps. The warning sound will end at the termination of exit delay.
Quick Exit: If enabled, user can restart the exit delay time after arming in STAY mode by entering the user code and pressing the pressing the user disarm then re-arm the system a f ter allowing someon e to enter or exit
Confirmation of arming is provided by a 1/2 second external sounder “ding” that sounds when closing report is s ent, or at the end of exit delay.
If Option 2 is selected the external s o under “ding” occurs immediately aft er the system receives the RF transmission.
When the system powers up armed, an alarm will occur 1 minute after arming if a zone is faulted, and any bypassed zones will be unbypassed. Note: If the previous state was armed respond to sensor changes for 1 minute, which allows time for sensors such as PIRs to stabilize. UL installations: must be 1 (power up in previous state)
If fewer than 6 digits need to be entered, exit by pres sing [*]. To clear entries from field, press *40*.
If fewer than 20 digits entered, exit by pressing [ *]. To clear entries from field, press *41*.
Note:
Backup reporting (8 attempts are made to the secondary phone number if
no kissoff is received after 8 attempts to the primary number) is automatic only if there is a secondary phone number (field *42).
If fewer than 24 digits entered, exit by pressing [ *]. To clear entries from field, press *42*. See backup reportin g note for field *41. If using the paging feature, enter the pager phone number here.
Enter the primary subscriber account number. To clear entries from field, press *43*.
Enter the secondary subscriber account number. To clear entries from field, press *44*.
This option is used to enter the correct type of phone dialing (pulse or tone), and to select the correct WATS line option for the Central Station. For LYNXR-EN only this option is used to activate the speaker phone option.
Note:
If using pulse dialing, you must enter the numbers slowly in ord er to allow the pulse dialer time to operate.
key if Quick Arm is enabled. This avoids having the
STAY
or
AWAY
STAY
, the system will not
STAY
–18–
key, or by
* or *44*
.
Data Field Descriptions
*
48
*
49
*
50
*
51
*
52
*
53
*
58
Report Format for Primary/Secondary
Primary Secondary
See choices below See choices below 0 = 3+1; 4+1 ADEMCO Low Speed Standard
1 = 3+1; 4+1 Radionics Standard 2 = 4+2 ADEMCO Low Speed Standard 3 = 4+2 Radionics Standard 6 = 4+2 ADEMCO Express 7 = ADEMCO Contact ID Reporting 8 = 3+1; 4+1 ADEMCO Low Speed Expanded 9 = 3+1; 4+1 Radionics Expanded
Split/Dual Reporting
To Primary To Secondary
0 = All reports None, unless primary fails, then all 1 = Alarms, Restore, Cancel Others 2 = All except Open/Close, Test Open/Close, Test 3 = Alarms, Restore, Cancel All 4 = All except Open/Close, Test All 5 = All reports All
To Primary To Paging Number
6 = All reports except Open/Close Alarms, Open/Close ‡, Troubles 7 = All reports Alarms, Troubles
8 = All reports Alarms, Open/Close ‡, Troubles
9 = All reports except Open/Close Open/Close
Will report Users 0, 5-8, and, if using wireless button-type devices, will report the zone number of the arm or disa rm button 26-33. All other zones and users are not reported.
15-Second Dialer Delay (Burglary)
0 = no dialer delay 1 = provide 15-second delay of burg. alarm report
Periodic Test Report
0 = no test report 2 = weekly 1 = once every 24 hrs 3 = once every 30 days
First test Report Offset
0 = 24 hrs after exit program mode or download 1 = 6 hours after exit program mode or download 2 = 12 hrs after exit program mode or download 3 = 18 hrs after exit program mode or download
Sescoa/Radionics Select
0 = Radionics (0–9, B–F reporting) 1 = SESCOA (0–9 only reporting)
RFJam Detection
0 = no jam detection 1 = RF jam detection with event logging, but no
central station report
2 = RF jam detection with event logging and with
central station report (if trouble/restore report is enabled in fields *60, *71)
Enter * as the 4th digit of *43 through *44, if 3+1 dia ler reporting is to be used. (For an explanation of these form ats, see the System C o m munication section of this manual.)
Notes:
(1) The maximum number of alarm and alarm restore reports during
(2) Op tion 7 (ADEMCO Contact ID Report ing) must be selected for
Use options 0 - 5 when reporting to telephone receivers. Use options 6 - 9 when reporting to a pager is des ired.
Pager Report Format
Options 6-9 send reports to the primary phone number and send reports to a pager, which has its phone number entered as the secondary phone number in field *42. The pager report is a 7-digit code, with optional 16-digit prefix, in the following format:
AAAAAAAAAAAAAAAA-EEE–00NN
AAA = Optional 16 digits for PIN number, etc. See field *88 for full
EEE = 3-digit Event Code as follows:
00 = Always displayed before 2-digit user/zone no. NN = 2-digit user number or zone number, depending on the type of
If enabled, provides communication delay to the central station and allows the subscriber time to avoid a fa lse alarm transmission. Delay does n ot apply to zone type 6, 7, 8, and 24 alarms, wh ich are always sent as soon as they occur. UL installations: must be 0 (no delay)
Test report code entered in field *64 is sent.
This is the time to first report from programming or downloading.
Select 0 for all other formats.
For Event Logging, Opti on 2 must be selected.
If the control detects an RF jam condition, a “FAULT” message appears for zone 90. The Contact ID code for RF Jam is 344.
Note:
one armed per iod is determined by field *92.
AVM.
where:
description of these characters.
911 = Alarm (NN = zone number) 101 = Open, system disarmed (NN = user no.) 102 = Close, system armed (NN = user no.) 811 = Trouble (NN = zone no.)
event (EEE) th at occurred. NN=00 indicates AC loss, system low battery, or low battery in 5827/5827BD.
This feature cann ot be used in conjunction with the 5827 wireless keypad .
–19–
Data Field Descriptions
*
SYSTEM STATUS AND RESTORE REPORT CODES PROGRAMMING (* 59 –* 76, &
Program Report Codes using the interactive *56 Enhanced Zone Programming Mode, or codes can be entered in data fields *59-*76, *89. The following is a set of guidelines when programming report codes. The actual report code digits that you enter depend upon the particular installation, and should be in agreement with you and the central station office receiving the si gnals.
With a 3+1 or 4+1 S tandar d For mat:
receivers), "#+11" for B, "#+1 2" for C, "#+13" for D, "#+14" for E, "#+15" for F. Entering "0" in the first box will disable a report. Entering "0" in the second box results in automatic advance to the next field.
With an Expanded or 4+2 Format:
the first box will disable a report. Entering "0" in the second box will eliminate the expanded message for that report.
With ADEMCO Contact ID® Reporting:
until you have used up available digits. If the number of zones exceeds the number of avail able digits, begin with digit 1 again. This is an "enabling" code only and is not the actual code sent to the central station office. Entries in the second boxes will be ignored. For system status (non-alarm) codes, enter a “1” in the first box for all the system conditions you want to send to the central station. A "0" in the first box disables the report.
SYSTEM STATUS REPORT CODES
*
59
Exit Error Report Code
See notes above
*60 *61 *62
*
63
*
64
*
65
*
66
*
67
*
68
Trouble Report Code Bypass Report Code AC Loss Report Code
Low Battery Report Code
Test Report Code
Open Report Code
Arm AWAY/STAY Report Code
above
)
RF transmitter Low Batt. Report Code
notes above
Cancel Report Code
)
Enter a code in the first box: 1–9, A, B, C, D, E, or F. Enter "#+10" for A (reports a “0” on some
Enter codes in
Enter a digit in the first box to enable the zone to report. Use a different digit for each zone
*
(
59–*68)
(See notes above
(See notes above
(See notes above
(See notes above
(See notes above
(See notes above
(See notes above
boxes (1st and 2nd digits) for 1–9, or A–F, as described above. Entering "0" in
both
If the system is armed and an entry/exit or interior zone is still open after the exit delay time has expired, an alarm will sound at the keypad and external sounder. If the system is disarmed before the end of the entry delay that immediatel y f ollows, the alar m s ounding will stop and no message will be sent to the central station. The keypad will display “CA (CANCELED A LARM).” If the system is not disar med before the end of the entry delay mentioned above, and an entry/exit or interior zone is still open, an “exit alarm” message will be sent to the central station if an Exit Error report code is selected in this field. The keypad will display “EA (EXIT ALARM),” and the alarm sounding will continue until the system is disarmed (or timeout occurs). An Exit Alarm condition will also result if a fault occurs in an exit or interior zone within 2 minutes following the end of the exit delay, and an “Exit Alarm” message will be sent to the central station. If Contact ID format has been programmed, the message will contain the zone number and error code 374 (Trouble–Exit Error). If 4+2 format is used, the digit entered in this field will be sent followed by the second digit of the programmed alarm code for that zone. If 3+1 or 4+1 format is used, only the digit entered in this field will be sent. This message wi ll go to the pri mary phone no. Under any of these conditions, no restore message will be sent. If “0” is entered in this field, no special message will be sent, only the regular alarm and alarm restore code for the zone.
)
)
)
)
)
)
(See notes
(See
)
This will be sent if a zone goes into trouble.
This will be sent when a zone is manually bypassed. Timing of this report is random with up to a 4-hour delay. If AC
restores before the report goes out, there is no AC restore r ep ort. This will be sent when a low battery condition exists in the system’s
standby battery. This is sent periodically to test that the communicator and phone
lines are operational (frequency of report is selected in field *51). This is sent upon disarming of the system. 2nd di git = user number, if
expanded or 4+2 reporting is selected. This option allows for independent programming of AWAY and
STAY reports. 2nd di git of report is user number if expanded or 4+2 reporting is selected. NOTE: OPEN reports are not sent if the associated closing report is not enabled.
This is sent in the event that a wireless transmitter low battery condition exists.
This is sent upon disarming of the system after an a larm condition was reported.
89)
–20–
Loading...
+ 44 hidden pages