Lux Products pspa722 User Manual

PSPA722
LUXPRO®PSPA722
INSTALLATION AND OPERATING INSTRUCTIONS
52071
1
COMPATIBILITY
2
FEATURES
3
ELECTRICAL RATINGS
4
INSTALLATION
4.1
TOOLS REQUIRED
4.2
LOCATION
4.3
REMOVAL OF OLD UNIT
4.4
MOUNTING
4.5
WIRING
4.5.1 TERMINAL DESCRIPTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
4.5.2 CONNECTING THE WIRES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
4.6
COMPLETING YOUR INSTALLATION
5
OPERATING BASICS
5.1
UP/DOWN CHANGE KEYS
5.2
SET DAY AND TIME
5.3
TEMPERATURE CONTROL MODES
5.3.1 HEAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
5.3.2 COOL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
5.3.3 AUTO CHANGE (AUTO) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
5.3.4 OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
5.4
DEFAULT PROGRAM
5.5
HOLD
5.6
OVERRIDE
5.7
FAN MODES
5.7.1 AUTO. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
5.7.2 ON. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
5.7.3 CLEAN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
5.8
DISPLAY ILLUMINATION
5.9
AUDIBLE BEEP
6
PROGRAMMING
6.1
DEFAULT TEMPERATURE PROGRAM
6.2
EDITING HEAT OR COOL PROGRAMS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
. . . . . . . . . . . . . . . . . . . . . . . 3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
. . . . . . . . . . . . . . . . . . . . . . . . . 4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
WARNING: Use Energizer®or DURACELL®Alkaline Batteries Only.
. . . . . . . . . . . . . . . . . . . . . . . 5
. . . . . . . . . . . . . . . . . . . . . . 5
Energizer®is a registered trademark of Eveready Battery Company, Inc.
DURACELL
®
is a registered trademark of The Gillette Company, Inc.
6.2.1 WEEKDAY PROGRAMMING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
6.2.2 WEEKEND PROGRAMMING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
6.3
FAN PROGRAMMING
6.4
COPY
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
7
ADVANCED FEATURES
7.1
KEYBOARD LOCK
7.2
FILTER MONITOR
7.2.1 FILTER USAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
7.2.2 FILTER LIMIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
7.3
ENERGY USAGE
7.4
CALIBRATION OFFSET
7.5
RESET
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
7.5.1 HARDWARE RESET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
7.5.2 SOFTWARE RESET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
7.6
TEMPERATURE VARIATION / SWING
7.6.1 SWING 1 - 1st STAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
7.6.2 SWING 2 - 2nd STAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
7.7
DEAD BAND
8
8.1
8.2
8.3
8.4
8.5
8.6 9
9.1 10 11 12 13 14
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
SETUP OPTIONS
MINIMUM RUN TIME J3 CLOCK FORMAT J4 TEMPERATURE DISPLAY FORMAT (F/C DISPLAY) J5 SMART RECOVERY J6 GAS/ELECTRIC MODE J7 REPOSITIONING JUMPERS
BATTERIES/MAINTENANCE
BATTERY INSTALLATION
TECHNICAL ASSISTANCE WARRANTY
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
WIRING DIAGRAMS USER PROGRAM TABLE JUMPER TABLE
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
. . . . . . . . . . . . . . . . . . . . . . . 8
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
. . . . . . . . . . . . . . . . . . . . . . . . . . . 9
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-11
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
. . . . . . 9
Mt. Laurel, New Jersey 08054, USA ●www.luxproproducts.com
UP DOWN
PSPA722
LUXPRO
PSPA722
1 COMPATIBILITY
Your
PSPA722
or Electric Heating and/or Cooling systems. It cannot be used with 120 volt heating systems, 3 wire zone valves, or Heat Pump Systems. Ask your dealer for other LUXPRO
2 FEATURES
PSPA722
of Cooling. Terminals: RH, RC, W1, W2, Y1, Y2, G, B, O, C
Large Display
Electro-luminescent Display Backlight
Clean Cycle®(Patent No. 6,988,671) IAQ Independently Programmable Fan
7 Day Programming
4 Periods Per Day
Temporary Override 1-4hr (CAT24 Residential Compliant)
Hold
Optional Smart Recovery
F/C Temperature Display
12/24 Hour Clock
Easy Programming with LUX Speed Dial
Energy Usage Monitor
Battery Free Nonvolatile Memory For All Programs And Settings
Auto-Changeover
Keyboard Lockout
Temperature Offset (User Calibration)
is compatible with most 24 volt: Gas, Oil,
®
thermostats to control those systems.
controls up to 2 stages of Heat and 2 stages
®
System or Battery Powered (or Both)
Multi-Stage Adjustable Temperature Differential / Cycle Rate
Programmable Auto-Changeover Dead-Band
3 ELECTRICAL RATINGS
30V maximum (24VAC nominal)
1.5A maximum per terminal
2.0A terminal sum
C A U T I O N: Your thermostat is protected against normal static electric discharges. To minimize the risk of damaging the unit in extremely dry weather, touch a grounded metal object before touching your thermostat.
4 INSTALLATION
4.1 TOOLS REQUIRED
#1 Phillips screwdriver (small)
Drill with 3/16-in. (4.8mm) bit
Wire stripper/cutter
4.2 LOCATION
On replacement installations, mount the new thermostat in place of the old one, unless the conditions listed below suggest otherwise. On new installations, follow the guidelines listed below.
Locate the thermostat on an inside wall, about 5 ft.
(1.5m) above the floor, in a room that is used often.
Do not locate where air circulation is poor, such as in a
corner or an alcove; or behind an open door.
2
Do not install it where there are unusual heating conditions, such as: in direct sunlight; near a lamp, television, radiator, register, or fireplace; near hot water pipes in a wall; near a stove on the other side of a wall.
Do not locate in unusual cooling conditions, such as: on a wall separating an unheated room; or in a draft from a stairwell, door, or window.
Do not locate in a damp area. This can lead to corrosion that will shorten thermostat life.
Do not install the unit until all construction work and painting has been completed.
W A R N I N G:
Read instructions carefully before removing any wiring
from an existing thermostat.
Label wires before they are removed.
When removing wires from their terminals, ignore the
color of the wires since they may not comply with any
standard.
4.3 REMOVAL OF OLD UNIT
1. Switch electricity to the furnace and air conditioner OFF; then proceed with the following steps.
2. Remove cover from old thermostat. Most are snap-on types and simply pull off. Some have locking screws on the side. These must be loosened.
3. Note the letters printed near the terminals. Attach labels (enclosed) to each wire for identification. Label and remove wires one at a time. Make sure the wires do not fall back inside the wall.
4. Loosen all screws on the old thermostat and remove it from the wall.
4.4 MOUNTING
5. Strip insulation 3/8 in. (9.5mm) from wire ends and clean off any corrosion.
6. Fill wall opening with non-combustible insulation to prevent drafts from affecting the thermostat.
7. With each thumb on a release tab at the bottom of the body, and fingers over the top of the unit. Release the unit from its base plate by squeezing the tabs into the body.
8. Separate the unit from its base plate by pulling the body outward at its bottom.
C A U T I O N:
Be careful not to drop the unit or disturb electronic parts.
Leave the door closed while the body is being removed
from the base.
9. Route the wires through the open areas in the base plate above the terminals. Hold the base against the wall, with the wires coming through. Position the base for the best appearance (to hide any marks from an old thermostat). Attach the base to the wall with the two screws provided.
3
N O T E : If you are mounting the base to a soft material like plasterboard or if you are using the old mounting holes, the screws may not hold. Drill a 3/16-in. (4.8mm) hole at each screw location, and insert the plastic anchors provided. Then mount the base as described below.
4.5 WIRING
10. Using the terminal descriptions below, wiring diagrams on pages 10-11, and your labels, determine appropriate wiring for you system.
11. If you are unsure or need assistance, call the LUX Technical Assistance Dept. (see
TECHNICAL ASSISTANCE
4.5.1 TERMINAL DESCRIPTIONS
Provides power for heating terminals.
RH: RC:
Provides power for cooling and fan terminals.
B:
Energized at any time the unit is in Heat mode.
O:
Energized at any time the unit is in Cool mode.
W1:
Energized while the thermostat is calling for a first stage of heat.
W2:
Energized when the thermostat is calling for a second stage of heat.
Y1:
Energized while the thermostat is calling for a first stage of cooling.
Y2:
Energized when the thermostat is calling for a second stage of cooling.
G:
The fan terminal is energized at any time the thermostat attempts to turn the blower on.
C:
Usage of this terminal permits the thermostat to be powered by the system, instead of (or in addition to) batteries alone.
4.5.2 CONNECTING THE WIRES
12. Loosen wire clamp screws just enough to slide wire under the black top part of the clamp.
13. Connect stripped wire ends, by trapping it between its black clamp and brass terminal. Then tighten its terminal screw.
14. Tape the ends of any unused wires.
4.6 COMPLETING YOUR INSTALLATION
15. Install two new Energizer®or DURACELL®"AA" size alkaline batteries at this time. For instructions, refer to BATTERIES/MAINTENANCE.
16. Configure your thermostat at this time. Refer to SETUP OPTIONS.
17. Install your thermostat on its base. To do this hang the top of the unit by the tabs on the base, then snap the bottom of the unit into place. Do not use unnecessary force. If the body does not snap into place easily, remove the body, re-hang it from the tabs and try again.
18. Turn the power back on to your heating and/or air conditioning system.
.)
19. Verify that the system and its fan are operating properly. When set to a high temperature, the heating system should provide warm air after a short time. Likewise a cooling system should provide cool air after a short time. Usually sound from the furnace and air conditioning units can be heard while they are running. The rush of moving air should be heard within a short time after either has been started.
20. Your installation is now complete.
5 OPERATING BASICS
5.1 UP/DOWN CHANGE KEYS
These are the two upper keys just right of the units display. They are used to adjust set temperatures, and make other setting changes.
Pressing these keys once will adjust a setting one step in the associated direction.
If there are many choices for a value, usually that setting will advance while holding one of these keys. Some settings though, must be changed one press at a time.
5.2 SET DAY AND TIME
To set the correct time after the unit has been unpowered or after reset:
Open the door on the front of the thermostat.
Rotate the dial to the day of week will flash.
Use the UP key to advance to the current day.
Press
Use the
Pressing Day, or vice versa.
Return the dial to its
5.3 TEMPERATURE CONTROL MODES
When a unit has first been powered up with the dial in the
RUN
your heating and/or air conditioning system according to it's default program. There is a 4-position slide switch to change temperature control modes. Slide the switch to the mode you would like to use.
5.3.1 HEAT
Use HEAT mode to control your furnace and warm your home.
In HEAT mode, temperature.
While heating is active,
If a second stage of heat is called for the flashing rate increases.
SET DAY/TIME
NEXT
to adjust the time. Time will flash.
UP/DOWN
keys to set the time.
NEXT
again will toggle from Set Time to Set
RUN
position.
. The abbreviation for
position, your thermostat will begin to control
HEAT
is displayed right of the set
HEAT
will flash
4
5.3.2 COOL
Use COOL mode to control your air conditioner,
cooling your home.
In COOL mode, COOL is displayed right of the set
temperature.
While cooling is active, COOL will flash
If a second stage of cooling is called for the flashing
rate increases.
5.3.3 AUTO CHANGE (AUTO)
Use AUTO CHANGE mode to allow your thermostat to switch between HEAT and COOL modes automatically. Slide the mode switch to be displayed above the set temperature. You can determine whether your thermostat is in HEAT or COOL mode by whether HEAT or COOL is visible in the set temperature area of the units display. Initially HEAT or COOL may not be active until a determination is made that HEAT or COOL is necessary.
The programmed temperature for a given mode will be used as the set temperature for that mode.
Pressing the force the unit to change modes and make the programmed set temperature the new set temperature.
5.3.4 OFF
Slide the MODE switch to cooling is desired. Heating and cooling will be disabled, and the set temperature side of the display will be empty.
5.4 DEFAULT PROGRAM
As supplied from the factory, your thermostat will use its default program for temperature control. This program and all other settings maybe restored to their default values via a SOFTWARE RESET. Please refer to DEFAULT TEMPERATURE PROGRAM for program times and temperatures.
5.5 HOLD
Hold is the simplest method to maintain fixed set temperatures.
Press
HOLD
HOLD while in RUN or OVERRIDE. displayed above the set temperature in the display.
Pressing this button again will toggle HOLD off and return to RUN and the programmed set temperature.
Changing system mode or rotating the SPEED DIAL will also cancel a HOLD.
5.6 OVERRIDE
During RUN, set temperatures may be temporarily altered from their programmed values. Immediately after a set temperature has been altered, the 2-hour default duration may be adjusted within the range from 1 to 4 hours. The temporary set temperature(s) will be used for the duration of the OVERRIDE.
AUTO
and
AUTO CHANGE
UP/DOWN
keys at the same time will
OFF
when no heating or
once to enter permanent temperature
HOLD
will
will be
®
Press either the UPor
set temperature will begin to flash.
Adjust the set temperature as desired.
After a few seconds the default 2-hour duration will
flash in the time area of the display.
Adjust the duration in 15-minute increments, from
between 1 to 4 hours.
When the duration stops flashing, the OVERRIDE has been initiated and the Set Temperature side of the display will show
OVERRIDE
The adjusted temperature will remain the set temperature in the current mode for the duration of the OVERRIDE. Then temperature settings return to their program values.
OVERRIDE may be cancelled by initiating a HOLD and then canceling it, changing the position of the mode switch, or rotating the SPEED DIAL
5.7 FAN MODES
The FAN switch controls which of three fan modes your thermostat is to use. These modes are AUTO, CLEAN, and ON.
5.7.1 AUTO
AUTO mode runs the fan only to fulfill your heating and cooling requirements.
DOWN
key. The current modes
®
5.7.2 ON
ON mode runs your system fan continuously.
5.7.3 CLEAN CYCLE
LUX’s Clean Cycle®allows you to program a forced air system to flow air through your system’s filter, cleaning the air in your home, even when heating or cooling is not being utilized. In CLEAN mode the fan maintains the programmed minimum run time; it may run additional time as required to maintain temperature control. The algorithm used avoids additional fan time when the minimum run time has been met over the last hour through temperature control. Minimum fan run times are met by running one third the hourly requirement at twenty minute intervals. The default minimum fan run time is 15 minutes per hour.
5.8 DISPLAY ILLUMINATION
For visibility in the dark, your LUX thermostat incorporates an attractive electro-luminescent display backlight.
Press the light bulb button right of the display to illuminate.
Pressing this or other buttons will keep the display illuminated.
®
5.9 AUDIBLE BEEP
When a key is pressed, the thermostat will emit an audible beep. The beep will terminate within 1/2 second while a button is held.
6 PROGRAMMING
6.1 DEFAULT TEMPERATURE PROGRAM
As supplied from the factory, the following program will be used for temperature control in RUN MODE. This program and all other software settings maybe restored to their default values via a SOFTWARE RESET.
Period Heat Mode Cool Mode Morning 6:00 AM 70°F (21°C) 6:00 AM 78°F (26°C) Day 8:00 AM 62°F (17°C) 8:00 AM 85°F (29°C) Evening 6:00 PM 70°F (21°C) 6:00 PM 78°F (26°C) Night 10:00 PM 62°F (17°C) 10:00 PM 82°F (29°C)
6.2 EDITING HEAT OR COOL PROGRAMS
You can change any preset times and/or temperatures to suit your schedule for each day of the week. The four periods each day are named Morning (MORN), Day, Evening (EVE), and Night (NITE).
6.2.1 WEEKDAY PROGRAMMING
To change the HEAT or COOL program:
Set
HEAT,COOL
, or
AUTO
Rotate dial to
PROGRAM,Mo,MORN
displayed, with the SET TIME flashing.
SET WEEKDAY PROGRAMS
with the mode switch
and
START AT
will be
.
Programming is performed in the following order. 1 Mo Morn Start Time
2 Mo Morn Heat Set Temperature 3 Mo Morn Cool Set Temperature 4 Mo Day Start Time 5 Mo Day Heat Set Temperature 6 …and so on until Fri Nite is fully programmed at which point pressing NEXT again will begin the list at Mo Morn Start Time.
Use the
UP/DOWN
this period. Press in 15 minute increments. Hold change the time at rate of 60 minutes/second.
One period ends at the start time of the next period. The end of one period may not be any closer to the beginning of the next period than one 15 minute increment. Moving a start time too close to the next start time results in the latter time being pushed ahead too. Press
NEXT
advance to the HEAT SET TEMPERATURE, it will flash to show that it may be edited.
keys to change the start time for
UP/DOWN
buttons to change the time
UP/DOWN
button to
to accept the displayed start time and
5
The HEAT SET TEMPERATURE will be displayed on the
right side of the display with the
Edit the HEAT SET TEMPERATURE, then press to accept and advance to the COOL SET TEMPERATURE, it will flash to show that it may be edited.
There is a minimum value that must be maintained between the HEAT SET TEMPERATURE and COOL SET TEMPERATURE. That value is called the Dead band. Its default is 3°F. It is programmable and may be changed See ADVANCED FEATURES. If you move the heat set temperature to close to the cool set temperature the cool set temperature will move away from the heat set temperature to maintain the dead band. Conversely the heat set temperature will move if you adjust the cool set temperature too close.
Edit the COOL SET TEMPERATURE, then press to accept and advance to the next period
When you have changed the Cool set temperature to your desired the temperature, press the next period. Its start time will be flashing indicating that it is under edit.
When all the periods for a day have been set, the start time for the next weekday Morning period will be displayed to begin editing the settings for that day.
Complete programming for all weekdays and rotate the dial back to RUN to accept all current values and end the programming session.
6.2.2 WEEKEND PROGRAMMING
Weekend programming is identical to weekday programming except that you must rotate the dial to SET WEEKEND PROGRAMS and the sequence of days that you may program is Sa and Su, then repeating this two day sequence.
6.3 CLEAN CYCLE®(IAQ FAN PROGRAMMING)
Clean Cycle®programming is similar to temperature programming. It has four consecutive periods, which are independent of the four temperature periods. The default setting for your systems fans CLEAN CYCLE requires it to run at least 15 minutes per hour. Default Program periods are:
HEAT
indicator visible.
NEXT
NEXT
NEXT
to advance to
®
program
Default Periods Time MORN 6:00 AM (6:00) DAY 8:00 AM (8:00) EVE 6:00 PM (18:00) NIGHT 10:00 PM (22:00)
To edit the CLEAN CYCLE®program:
Move Fan switch to
Rotate the dial to
Press
HOLD
PROGRAM,FAN,START AT,MO
CLEAN
AIR FILTER
for 2 seconds.
.
(day) and
MORN
6
(period) will all be visible. Current start time will flash in time area.
Programming is performed in the following order.
1. Mo Morn Start Time
2. Mo Morn Minimum ON Time
3. Mo Day Start Time
4. Mo Day Minimum ON Time
5. …and so on until Sun Night is fully programmed at which point pressing Morn Start Time.
Press 15 minute increments. Hold the time at rate of 60 minutes/second
Press the to set minimum fan on time per hour. Current minimum fan run time will flash with
Press setting by 3 minutes. Time can be adjusted from 0 to minutes to 60 minutes in increments of 3 minutes. Set 0
MIN/HR
while
CLEAN
MIN/HR
Press four program periods of day have been programmed,, pressing period.
One period ends at the start time of the next period. The end of one period may not be any closer to the beginning of the next period than one 15 minute increment. Moving a start time to close to the next start time results in the latter time being pushed ahead too.
Rotate the dial away from the
PROGRAMS/AIR FILTER
programming.
6.4 COPY
Pressing or fan program into the current day and advance the thermostat to the beginning of next day.
NEXT
again will begin the list at Mo
UP/DOWN
to change start time for this period in
UP/DOWN
button to change
NEXT
to accept the start time, and advance
MIN/HR
UP/DOWN
to alter the minimum ON Time
to allow
AUTO
is used in others. Set the fan duration to 60
to run the fan continuously for this period.
NEXT
to advance to the next period. After the
NEXT
will advance to the following days
COPY
will copy the previous days temperature
.
control for particular periods
MORN
SET FAN
position to exit fan
7 ADVANCED FEATURES
7.1 KEYBOARD LOCK
To prevent tampering Press
NEXT, HOLD
unlock all settings and programs. When locked, a padlock icon will be visible above the time / temperature area of the display.
This sequence of keys will lock and
NEXT, NEXT
,
7.2 FILTER MONITOR
Your thermostat can alert you that your system’s air filter should be changed, by displaying temperature display area once the system’s fan has run the number of hours specified by this setting’s limit. The presence of the word the operation of the thermostat. If equipped, the filter is located in your heating/cooling equipment.
7.2.1 FILTER USAGE
To view the number of hours the thermostat has activated the fan since the last timer reset:
Rotate the dial to the
filter usage will be shown with
To reset the timer to 0. press UPor
Pressing
UP
or the current value. The value in display when you exit this mode will be the value retained in memory. Leave the value at 0 to reset the timer.
To exit the
position.
7.2.2 FILTER LIMIT
This general rule will provide you with a good estimate of your filter’s life in hours. Assume that the fan will run at 1/3 duty cycle or 8 hours per day. Common 90 day filters are then good for 90*24/3=720 hours of use. This is the default limit value. Setting the filter counter limit to 0000 will disable the change filter indicator. Valid entries are from 0 to 2000hrs.
To set the number of hours of filter use before replacement is indicated:
Rotate the dial to the
filter usage will be shown with
Hold
displayed.
Refer to your Air Filter package to determine your filters recommended life. If given in days, multiply by 8 to find the recommended setting in hours of filter usage.
Use increments to the recommended value.
Rotate the dial to
7.3 ENERGY USAGE
Your thermostat records the total number of hours the
DOWN
AIR FILTER
NEXT
for 2 seconds. The Filter limit will be
UP/DOWN
keys to adjust the filter limit in 10 hour
RUN
FILTER
in the time
FILTER
on the screen will not effect
AIR FILTER
position. The current
HRS FILTER
DOWN
again will toggle between 0 and
once.
mode, rotate the dial to another
AIR FILTER
position. The current
HRS FILTER
finish this setting.
7
thermostat has activated heating and cooling with six separate timers. They measure:
Today's cumulative heating time
Yesterdays cumulative heating time
Total cumulative heating time
Today's cumulative cooling time
Yesterdays cumulative cooling time
Total cumulative cooling time
To view
HEAT
or
COOL
Slide the mode switch to
Rotate the dial to the
review today's usage.
Day
are all shown along with the usage value.
Press
NEXT
Press
NEXT
timer may be changed to zero by pressing while Total time is displayed. To restore count, press or
DOWN
again.
To finish review and/or reset of this modes energy monitor, rotate the dial to another mode, the current values will be the values retained in memory. Leave the value at 0 to reset the cumulative timer.
7.4 CALIBRATION OFFSET
Your thermostat is accurately calibrated at the factory to within ±1°F An offset value up to ±5°F may be added to the temperature value that the thermostat measures. This may allow you to match this thermostat to another. To change this offset from its default value of 0:
Open the door on the front of the thermostat.
Rotate the dial to
Simultaneously press Temperature Offset value will flash.
Use the
Return the dial to its value.
7.5 RESET
Your thermostat has two RESET buttons. The Software RESET is on the front of the thermostat behind the door. It is labeled the circuit board.
7.5.1 HARDWARE RESET
Use this small white button labeled changing Setup Option Jumper positions to effect the changes. The Hardware RESET turns Heat, Air and Fan off, resets the units' clock, and reads the Setup Option jumper positions, before initiating normal operation.
7.5.2 SOFTWARE RESET
Use this feature to make all settings and programs their default values The Software RESET button turns Heat, Air and Fan off, resets the units' clock, and reads the Setup
energy usage:
HEAT
or
ENERGY USAGE
HRS USAGE, Mode
to review yesterday's usage.
again to review Total usage. The Total
SET DAY/TIME
UP/DOWN
keys to adjust the offset value.
RUN
RESET
. HARDWARE RESET is on the rear of
COOL
.
NEXT
and
HOLD
position to accept the new
H_RST
.
position, to
and
Current
UP
or
DOWN
. The
after
UP
Option jumper positions. It then makes all settings and programs their default values before initiating normal operation.
N O T E: Pressing this button will overwrite your program and install the default values of all temperature programs and setup values into the unit’s nonvolatile memory. To ease reprogramming later, record your thermostat’s programs and settings in the table provided before using this button. (See Page 12.)
7.6 TEMPERATURE VARIATION / SWING
Your thermostat works by turning your heating or cooling system on and off whenever the room temperature varies a certain number of degrees from the set-point temperature. This variation is the "swing." Your system should cycle on about 3 to 6 times per hour. A smaller swing number increases the number of cycles, so room temperature is more constant. A larger swing number decreases the number of cycles, saving energy in most cases.
7.6.1 SWING 1 - 1st STAGE
This setting controls when the heating or cooling turns on and off.
Swing 1 sets the temperature variation that the system allows above and below the set temperature before switching the heating or cooling unit on and off. To change this value:
Rotate the
Temperature section of the display shows
SWING
The Time section flashes the current setting.
UP/DOWN
the most accurate temperature control, and the system will cycle on/off the most frequently. The largest setting of 225 provides the widest temperature differential, and the system will cycle on/off less frequently.
7.6.2 SWING 2 - 2nd STAGE
This setting controls when the second stage of heating or cooling turns on and off. It controls the temperature variation the system allows above and below Swing 1's limit before calling for a second stage. Once a second stage is activated, it will remain on until the set temperature has been reached.
SPEED DIAL®to
Press
NEXT
and
and 1denoting that you are setting
Select one of the 9 values from 025 to 225 with the
buttons. The smallest setting of 025 provides
Return the
SPEED DIAL®to
HOLD
simultaneously. The
ENERGY USAGE
SET TEMP
SWING 1
RUN
To change this value:
Rotate the
Temperature section of the display shows
SWING
The Time section flashes the current setting.
SPEED DIAL®to ENERGY USAGE
Press
NEXT
and
COPY
simultaneously. The
and 2 denoting that you are setting
SET TEMP
SWING 2
Select one of the 9 values from 025 to 225 with the
UP/DOWN
the most accurate temperature control, and the system will cycle on/off the most frequently. The largest setting of 225 provides the widest temperature differential, and the system will cycle on/off less frequently.
Return the
7.7 DEAD BAND
When using Auto-Changeover, dead band provides a disallowed temperature range between the maximum heat set temperature and minimum cool set temperature. dead band may be set from 1 to 6 degrees. With auto­changeover active, dead band set to 3°F and heat set to 70°F the minimum allowed cool set temperature will be 73°F. If the cool set temperature is lowered, then the heat set temperature will be lowered by the same amount maintaining the 3°F dead band.
To change this setting:
Set
Set MODE to
Press The display shows Time/Temperature section flashes the current setting.
Use degree increments.
Press and release seconds the unit will automatically revert to
8 SETUP OPTIONS
There are five jumpers; each controls a setting depending
.
on its position. Jumpers are located on the rear of the thermostats circuit board. For reference there a table of settings and jumper positions printed there as well. They are described here from J3, the rightmost jumper, to J7, the leftmost jumper.
8.1 MINIMUM RUN TIME J3
The position of J3 sets the minimum length of time that the thermostat must remain with HEAT or COOL either On or Off, before it will automatically switch to the alternate On or Off state. This Delay prevents rapid cycling of your system and provides equipment protection for cooling units. Switch position OFF is a 5 minute delay, and ON is a 2 minute delay. 5 minutes is the default setting, and is good for most applications. If you feel that your system is trying to cycle more rapidly than every 5 minutes, you may try the 2 minute setting.
8.2 CLOCK FORMAT J4
The time shown on the thermostats clock may be displayed in 12 or 24-hour format. Set this option to your preference.
.
8
buttons. The smallest setting of 025 provides
SPEED DIAL®to
SPEED DIAL®to
AUTO
NEXT
and
UP/DOWN
RUN
RUN
COPY
simultaneously for 2 seconds.
SET DEAD BAND
, while the
keys to adjust the DEAD BAND in 1
NEXT
to return to
RUN
. Or, after 30
RUN
mode.
8.3 TEMPERATURE DISPLAY FORMAT (F/C DISPLAY) J5
Temperature may be displayed in Fahrenheit or Celsius with this option.
8.4 SMART RECOVERY J6
Smart Recovery allows your HVAC system to attempt to recover from a setback period and reach your desired comfort temperature by the beginning of your programmed comfort period. This jumper allows you to choose whether to use Smart Recovery.
An initial Smart Recovery will start 1/2 hour before the
programmed comfort temperature.
Maximum Smart recovery time is one hour.
If enabled, Smart Recovery will initiate if:
Recovery is valid, from an evening setback to morning
comfort or day setback to evening comfort period
In Heat mode the set temperature of the comfort
period must be higher than the setback period
In Cool mode the set temperature of the comfort
period must be lower than the setback period
8.5 GAS/ELECTRIC MODE J7
This setting changes how the system’s blower fan (if applicable) is controlled while in HEAT mode, and with the Fan switch in the AUTO position. This setting does not affect fan operation while in COOL mode. When set to “Gas”, the fan is controlled solely by the heating system itself. When set to “Electric”, the fan is controlled directly by the thermostat. NOTE: If your blower fan does not operate properly after installation, move the Gas / Electric option to the “Electric” setting.
8.6 REPOSITIONING JUMPERS
Use the table on Page 12 to determine the jumper position corresponding to the option you desire. The table is also printed on the circuit board. If necessary change the jumper position by pulling it straight off the pins it covers. Replace the jumper over one pin for OPEN, or both pins for CLOSED. When all changes have been made, press the HARDWARE RESET.
These jumpers are located inside the thermostat on the rear of its circuit board. To access them remove the unit from the wall by pressing up on the thumb latch at the bottom of thermostat, and swinging the body up and away to separate them.
To change a setting, the jumper must be repositioned and a Hardware reset must be performed. See HARDWARE RESET.
Hardware Reset Button
. See
9 BATTERIES/MAINTENANCE
Depending on your installation, your unit may require batteries to control your HVAC system. Replace your thermostats batteries at least once a year or when the
9
battery symbol appears in the display
9.1 BATTERY INSTALLATION
1. Remove fresh batteries from their carton.
2. Remove body of thermostat from the wall as described in installation.
3. Remove the used batteries if present and replace them within 90 seconds to avoid having to reset the day and time.
4. Install two new "AA" size Energizer®or Duracell alkaline batteries. Observe the polarity marking shown in the battery compartment.
W A R N I N G: Replace your thermostat’s batteries with new Energizer or Duracell alkaline batteries at least once a year or when the battery symbol appears in the display. Use of high quality alkaline batteries is absolutely required for your thermostat to operate properly.
®
5. Re-hang on it's base plate as described in installation.
10 TECHNICAL ASSISTANCE
If you have any problems installing or using this thermostat, please carefully and thoroughly review the instruction manual. If you require assistance, please contact our Technical Assistance Department at 856-234-8803 during regular business hours between 8:00AM and 4:30PM Eastern Standard Time, Monday through Friday. You can also receive technical assistance online anytime day or night at http://www.luxproproducts.com. Our web site offers you answers to the most common technical questions, and also permits you to email your questions to our technical support staff at your convenience.
11 WARRANTY
Limited Warranty: If this unit fails because of defects in materials or workmanship within three years of the date of original purchase, LUX will, at its option, repair or replace it. This warranty does not cover damage by accident, misuse, or failure to follow installation instructions. Implied warranties are limited in duration to three years from the date of original purchase. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. Please return malfunctioning or defective units to the location from which the purchase was made, along with proof of purchase. Please refer to “TECHNICAL ASSISTANCE” before returning thermostat. Purchaser assumes all risks and liability for incidental and consequential damage resulting from installation and use of this unit. Some states do not allow the exclusion of incidental or consequential damages, so the above exclusion may not apply to you. This warranty gives you specific legal rights and you may also have other rights which vary from state to state. Applicable in the U.S.A. and Canada only.
12 WIRING DIAGRAMS
TYPICAL 2 OR 3 WIRE HEAT ONLY HOOKUP
24V AC AND MILIVOLT SYSTEMS
GBW2 Y2 O Y1W1 RC RH C
Omit fan connections for two wire systems.
FAN
SYSTEM
COMMON
GAS
VALVE
TYPICAL SINGLE STAGE
COOL ONLY HOOKUP
JUMPER
PROVIDED
XFMR
AC LINE
GBW2 Y2 O Y1W1 RC RH C
JUMPER
PROVIDED
SYSTEM
FAN
COMMON
TYPICAL 24V AC 4 WIRE HOOKUP
SINGLE STAGE HEAT AND COOL
COMPRESSOR
XFMR
AC LINE
GBW2 Y2 O Y1W1 RC RH C
SYSTEM COMMON
FAN
GAS
VALVE
JUMPER
PROVIDED
COMPRESSOR
10
XFMR 1
AC LINE
WIRING DIAGRAM NOTES
1. Dashed lines are optional.
2. Optional common wire allows system to power thermostat.
3. Use “B” or “O” wire - but not both in heat pump systems. Generally neither are required in a conventional system.
4. If “Y” and “C” wires are both present, then “C” is a common wire.
5. If a “B” wire in your system is a common wire then connecting it to the B terminal may cause damage to your system.
6. The PSPA722 is not compatible with Heat Pump Systems.
WARNING: THIS IS A LOW VOLTAGE THERMOSTAT (24 volts). A SERIOUS RISK OF FIRE EXISTS IF YOU CONNECT THIS THERMOSTAT TO A LINE VOLTAGE APPLICATION (typically 115 or 230 volts). IF UNCERTAIN ABOUT THE VOLTAGE CONSULT A PROFESSIONAL ELECTRICIAN.
TYPICAL 24V AC 5 WIRE HOOKUP
SINGLE STAGE HEAT AND COOL
2 TRANSFORMER
GBW2 Y2 O Y1W1 RC RH C
JUMPER
COOL
COMMON
FAN
GAS
COMPRESSOR
VALVE
TYPICAL 24V MULTI-STAGE
HOOKUP
REMOVED
COOL
HEAT
XFMR
XFMR
AC LINE AC LINE
G B W2 Y2 O Y1W1 RC RH C
JUMPER
PROVIDED
SYSTEM
COMMON
HEAT
COMMON
WIRING DIAGRAM NOTES
1. Dashed lines are optional.
2. Optional common wire allows system to power thermostat.
3. Use “B” or “O” wire - but not both in heat pump systems. Generally neither are required in a conventional system.
4. If “Y” and “C” wires are both present, then “C” is a common wire.
5. If a “B” wire in your system is a common wire then connecting it to the B terminal may cause damage to your system.
6. The PSPA722 is not compatible with Heat Pump Systems.
FAN
COMPRESSOR
STAGE 2 STAGE 1
HEAT
STAGE 2 STAGE 1
XFMR
AC LINE
WARNING: THIS IS A LOW
VOLTAGE THERMOSTAT (24 volts). A SERIOUS RISK OF FIRE EXISTS IF YOU CONNECT THIS THERMOSTAT TO A LINE VOLTAGE APPLICATION (typically 115 or 230 volts). IF UNCERTAIN ABOUT THE VOLTAGE CONSULT A PROFESSIONAL ELECTRICIAN.
11
13 USER PROGRAM TABLE
J7 J6 J5 J4 J3
JUMPERS
MOUNTED ON
CIRCUIT BOARD
H_RST
BATTERY COMPARTMENT
BATTERY COMPARTMENTBATTERY COMPARTMENT
BACK OF THERMOSTAT BODY
WITH COVER REMOVED
2 MIN 24 HR
C
S/R ON
ELECT
5 MIN 12 HR
F
S/R OFF
GAS
J3 J4 J5 J6 J7
OPEN CLOSE
To ease reprogramming later, record your thermostat’s programs and settings in the table provided below.
DAY
MON
TUES
WED
PERIOD
MORN
NIGHT
MORN
NIGHT
MORN
NIGHT
HEAT
TIME TEMP. TIME TEMP.
DAY
EVE
DAY
EVE
DAY
EVE
COOL
14 JUMPER TABLE
DAY
THURS
FRI
SAT
SUN
PERIOD
MORN
NIGHT
MORN
NIGHT
MORN
NIGHT
MORN
NIGHT
HEAT
TIME TEMP. TIME TEMP.
DAY
EVE
DAY
EVE
DAY
EVE
DAY
EVE
COOL
MERCURY WARNING AND RECYCLING NOTICE:
Mercury is considered to be a hazardous material. If this product is replacing a thermostat that contains mercury in a sealed tube, contact your local waste management authority for instructions regarding recycling and proper disposal. It may be unlawful in your state to place it in the trash.
12
Loading...