INSTALLATION AND
OPERATING INSTRUCTIONS
EcoStat®PSM011 Heating & Cooling
Mercury FREE Manual Thermostat
LUX PRODUCTS CORPORATION
Mt. Laurel, New Jersey 08054, USA
http://www.luxproproducts.com
IMPORTANT!
Please read all instructions carefully before beginning installation and save for future
reference. Before removing any wiring from your existing thermostat, the wires must
be labeled with their terminal designations. Ignore the color of the wires since they
may not comply with any standard.
Thank you for your confidence in our product. To obtain the best results from your investment,
please read these instructions thoroughly. You should become fully acquainted with this thermostat
before installing it for usage. Follow the installation procedures carefully, and one step at a time.
This will save you time and minimize the chance of damaging either the thermostat or the systems
that it controls. These instructions may contain information beyond that required for your particular
installation. Please save these instructions for future reference.
COMPATIBILITY
52093
Wall / Trim Plate Sub-Base
UP
UP
Orientation
Marks (3)
T
A
E
H
F
F
O
•
L
O
O
C
F
A
N
O
N
•
A
U
T
O
Mounting Holes
9. Insert the two longer mounting screws provided through the right and left Trim Plate screw holes
and thread each screw into the mounting holes into the wall or the plastic screw anchors.
10. Carefully push all excess wire back into the wall. Align the thermostat sub-base with the
decorative wall plate by using the 3 alignment pins and holes molded into the back of the
subbase and Trim Plate. Attach the Sub-Base to the Trim Plate using the two smaller mounting
screws provided. Thread these two small screws into the single inner holes in the Trim Plate.
11. Now that the Sub-Base is mounted, align the front portion of the thermostat with the Sub-Base
using the Light Button and the cutout for it in the Sub-Base. While holding the thermostat in
place against the Sub-Base, carefully and evenly tighten the 3 silver captive screws that are held
in place inside the front of the thermostat assembly.
WIRING INFORMATION
** Complete heating and/or cooling system wiring can be found in the WIRE IDENTIFICATION AND
WIRING SCHEMATICS section of this instruction sheet. The schematics shown provide component
information for brand new installations or for unreferenced wires.
This mechanical thermostat can be used with most single-stage 24 volt gas or oil heating and air
conditioning systems. It cannot be used with heat pumps, 3 wire zone valves, line voltage (120/240
volt) heating systems, or Millivolt systems. Ask your dealer for other LUXPRO thermostats to
control those systems.
FEATURES
• Push Button Back Light
• Glow-In-The-Dark Dial Numbers
Light Button
Temperature
Mode
Switch
Ambient
Room
Temperature
US Patent USP D471,572
F
F
O
•
L
O
O
C
• Soft Rubber Set Temperature Ring
• Large Easy To Use Mode Switches
55
65
65
75
75
85
85
F
A
N
O
N
•
A
U
T
O
T
A
E
H
55
Temperature
Temperature
Selector Ring
SELECTING A LOCATION
On replacement installations, mount the new thermostat in place of the old one unless the conditions
listed below suggest otherwise. On new installations, follow the guidelines listed below.
1. Locate the thermostat on an inside wall, about 5 ft. (1.5m) above the floor, and in a room that is
used often.
2. Do not locate where air circulation is poor, such as in a corner or an alcove, or behind an open
door.
3. Do not install it where there are unusual heating conditions, such as: in direct sunlight; near a
lamp, television, radiator, register, or fireplace; near hot water pipes in a wall; near a stove on the
other side of a wall.
4. Do not locate in unusual cooling conditions, such as: on a wall separating an unheated room; or in
a draft from a stairwell, door, or window.
5. Do not locate in a damp area. This can lead to corrosion that may shorten thermostat life.
6. If painting or construction work has yet to be completed, cover the unit completely or do not
install it.
TOOLS REQUIRED
• #1 Phillips screwdriver • #1 Slotted screwdriver
• Drill with 3/16 in. (4.8mm) bit • Wire Stripper / Cutter
NOTE: Review the type of wiring configuration that your system requires, prior to removing your old
thermostat or its wiring connections.
REMOVAL OF OLD UNIT
1. Turn OFF the electricity to all heating and cooling components. Do not turn the
electricity back on until all work is completed.
2. Remove the cover and front portion of your old thermostat to expose the wiring
connections.
3. Write down the letters printed near each wire terminal that is used, and the color of
the wire that is connected to it. Using the enclosed labels, attach a label to each of
your wires so that the letter matches the marking on your existing thermostat.
4. When they are all labeled, carefully remove the wires one at a time, making sure that they do not
fall back inside the wall. Do not allow any of the bare wire ends to touch each other, or any parts
on the thermostat.
5. Loosen all of the screws on the old thermostat and remove it from the wall.
INSTALLATION
MOUNTING
1. Strip insulation leaving 3/8 in. (9.5mm) bare wire ends and clean off any corrosion.
2. Fill wall opening with non-combustible insulation to prevent drafts from affecting the thermostat.
3. The Wall/Trim Plate is optional, however its usage is recommended.
4. Remove the front trim ring from the thermostat by pulling it straight outwards.
5. If there are no existing mounting holes that are able to be reused, hold the Trim Plate level against
the wall with the “UP” markings up, and mark the “outer” two oval mounting holes on the right
and left. NOTE: if you are not using the Trim Plate, you can still mark the holes for the thermostat
using the two small inner holes on the right and left of the Trim Plate, which line up with the
thermostat mounting holes.
6. If you are mounting the base to a soft material like plasterboard, the screws alone may not hold.
Drill a 3/16 in. (4.8mm) hole at each screw location, and insert the plastic anchors provided into
the wall. If you are mounting to wood or similar substance, the screws may be used alone without
the plastic anchors.
7. First, feed the wires through the large middle hole in decorative wall plate (if used) and then
through the square lower hole near the bottom of the thermostat’s Sub-Base.
8. Referring to your earlier notes from removing your old thermostat, and the electrical diagrams in
this manual, attach the wires to the terminal screws. Make sure bare metal wires do not touch
each other. The wire connector screws on the Sub-Base may need to be loosened prior to
inserting any wires. When all wiring is complete, ensure that every screw is securely tightened.
© 2010 LUX PRODUCTS CORPORATION. ALL RIGHTS RESERVED
Fan
Mode
Switch
Set
Set
SETUP
The only item that will need to be tailored to your
system is the Heat Anticipator. This setting is for
heating systems only. If you are using this
thermostat on a “cooling only” system with no
heater, the Anticipator does not need to be set and
Heat
Anticipator
Adjustment
can be left as is.
If you are replacing an old mechanical thermostat,
find the Anticipator setting on the old thermostat,
and set the new thermostat to the same value. Do this by carefully sliding the silver metal pointer,
shown here, over desired number printed on the Anticipator scale. If an old Anticipator setting
cannot be determined, look on the gas control valve on your furnace, and find either the Anticipator
Value or a Current Rating. This will be the value to use for the Anticipator setting. If you cannot find
either of these numbers, set it to .6 initially to start with. During heating season, your furnace
should operate about five times an hour. If adjustments are necessary, move heat anticipator pointer
slightly and recheck. A lesser value will cause your heater to cycle more frequently, and a larger
value will cause it to cycle less frequently.
OPERATION
There are two mode switches on the front, a Temperature mode switch and a Fan mode switch. The
Temperature mode switch has three positions: HEAT, OFF, and COOL. In the winter, set the system
switch to HEAT to control your heating system. In the summer, set the switch to COOL to control
your air conditioner. In the spring and fall or when the windows are open, you can set the switch
OFF. The Fan mode switch has two positions, AUTO and ON. Setting the Fan mode switch to AUTO,
automatically runs your system's blower fan as required only during heating and cooling activation.
Setting the Fan mode switch to ON, runs your system’s fan continuously, even if heating or cooling is
not needed, including when the Temperature mode switch is in the OFF position to provide air
circulation only. In either HEAT or COOL mode, turn the front thermostat dial to the desired
temperature setting.
BACKLIGHT
This thermostat has an illuminated panel to assist in reading the temperature while in low light
conditions. While in HEAT or COOL mode, press and hold the button on the top of the thermostat.
The backlight will not operate while the thermostat is in OFF mode.
TECHNICAL ASSISTANCE
If you have any problems installing or using this thermostat, please carefully and thoroughly review
the instruction manual. If you require assistance, please contact our Technical Assistance Department
at 856-234-8803 during regular business hours between 8:00AM and 4:30PM Eastern Standard Time,
Monday through Friday. You can also receive technical assistance online anytime day or night at
http://www.luxproproducts.com. Our web site offers you answers to the most common technical
questions, and also permits you to email your questions to our technical support staff at your
convenience.
WARRANTY
Limited Warranty: If this unit fails because of defects in materials or workmanship within three years
of the date of original purchase, LUX will, at its option, repair or replace it. This warranty does not
cover damage by accident, misuse, or failure to follow installation instructions. Implied warranties
are limited in duration to three years from the date of original purchase. Some states do not allow
limitations on how long an implied warranty lasts, so the above limitation may not apply to you.
Please return malfunctioning or defective units to the location from which the purchase was made,
along with proof of purchase. Please refer to
“TECHNICAL ASSISTANCE” before returning
COMPATIBILITY
For Use On:
• Most 24V Systems
• 1 Heat/1 Cool: Gas or Oil
• 2 Wire Hydronic (Hot Water)
Not For Use On:
• Heat Pumps
• Electric Furnaces
• 3 Wire Hydronic (Hot Water)
• Line Voltage (120/240V)
• Millivolt Systems
Systems
À ne pas utiliser pour :
• Thermopompes
• Fournaises électriques
• Systèmes électromécaniques
• Tension de ligne (120/240 V)
• Systèmes Millivolt
(d'eau chaude) à 3 fils
No usar en:
• Bombas de calor
• Hornos eléctricos
• Sistemas hidrónicos (de
• Voltaje de línea
• Sistemas de Milivoltios
agua caliente) de 3 cables
(120/240 voltios)
(d'eau chaude) à 2 fils
Systems
Systems
COMPATIBILITÉ
À utiliser pour :
• La plupart des systèmes 24
• 1 chauffage / 1
• Systèmes électromécaniques
agua caliente) de 2 cables
V
refroidissement : systèmes à
l'huile ou au gaz
COMPATIBILIDAD
Para su uso con:
• La mayoría de los sistemas
• 1 Calefacción / 1 Aire acondi-
• Sistemas hidrónicos (de
de 24 voltios
cionado: a gas o petróleo
thermostat. Purchaser assumes all risks and
liability for incidental and consequential damage
resulting from installation and use of this unit.
Some states do not allow the exclusion of
incidental or consequential damages, so the
above exclusion may not apply to you. This
warranty gives you specific legal rights and you
may also have other rights which vary from state
to state. Applicable in the U.S.A. and Canada
only.
**MERCURY WARNING
AND RECYCLING NOTICE:
Mercury is considered to be a
hazardous material. If this product is
replacing a thermostat that contains mercury
in a sealed tube, contact your local waste
management authority for instructions
regarding recycling and proper disposal. It
may be unlawful in your state to place it in
the trash.
52093
G
Y
(PSM011) ENGLISH - WIRE IDENTIFICATION AND WIRING SCHEMATICS
RC
RH
W
ECOSTAT PSM011
HEATING ONLY SYSTEM WIRING
ECOSTAT PSM011
COOLING ONLY SYSTEM WIRING
PROVIDED
RC-RH
JUMPER WIRE
WIRING DIAGRAM NOTES:
• The dashed wires ar e optional, and usage depends upon your specific
system t ype.
• If replacing a Honeywell TM-11, t ape off the “R” wir e. Connect t he
“B” wire t o t he “RH” terminal.
• If replacing a t hermost at that has a clock wire labeled as “C,” t ape off
this wir e and do not connect it to t his t hermost at .
• If “Y” and “C” wires ar e both pr esent , t hen “C” is a common wire,
tape off t his wire and do not connect it t o this ther mostat.
If a “B” wire in your system is a common wir e, tape off t his wire and
•
do not connect it to t his t hermost at .
**Factory RH-RC Jumper Wire Installed
GAS
VALV E
OR
HEATER
-
SYSTEM
XFMR
ECOSTAT PSM011
HEAT AND COOL SYSTEM WIRING
WITH ONE TRANSFORMER
**Factory RH-RC Jumper Wire Installed
GAS
VALV E
OR
HEATER
-
SYSTEM
XFMR
**Factory RH-RC Jumper Wire Installed
YRH GRCW
(”G” wire is optional
depending upon
+
FAN
system type)
-
SYSTEM
XFMR
+
FAN
YRH GRCW
A/C
COMPRESSOR
ECOSTAT PSM011
HEAT AND COOL SYSTEM WIRING
WITH TWO TRANSFORMERS
**Factory RC-RH Jumper Wire REMOVED
YRH GRCW
YRH GRCW
+
+
-
+
FAN
A/C
COMPRESSOR
GAS
VALV E
OR
HEATER
-
COOL
XFMR
HEAT
XFMR
Chassis Ground
FAN
A/C
COMPRESSOR
(PSM011) FRANÇAIS
Y
RC
RH
G
CAVALIER
RC-RH
FOURNI
NOTES DU DIAGRAMME DE CÂBLAGE :
• Les fils en traits t ir és sont opt ionnels et leur utilisation dépend de
votre système pr écis.
• Si vous remplacez un modèle Honeywell TM-11, couvr ez le fil « R ».
Br anchez le fil « B » à la bor ne « RH ».
• Si vous remplacez un t hermost at à fil d'horloge portant la mention
« C », couvr ez ce fil et ne le br anchez pas à ce ther mostat.
• Si vous avez les fils « Y » et « C » , alors le « C » est un fil commun,
couvrez-le et ne le branchez pas à ce t hermost at .
Si un fil « B » de votre syst ème est un fil commun, couvr ez ce fil et ne
•
le branchez pas à ce t hermost at .
W
- SCHÉMAS D'IDENTIFICATION DES FILS ET DU CÂBLAGE
CÂBLAGE DU SYSTÈME DE CHAUFFAGE
SEULEMENT ECOSTAT PSM011
**Cavalier RC-RH d'usine installé
+
-
VALVE À
GAZ OU
CHAUDIÈRE
SYSTÈME
XFMR
VENTILATEUR
CÂBLAGE DU SYSTÈME DE CHAUFFAGE ET
DE REFROIDISSEMENT AVEC UN SEUL
TRANSFORMATEUR ECOSTAT PSM011
**Cavalier RC-RH d'usine installé
+
VALVE À
GAZ OU
CHAUDIÈRE
-
SYSTÈME
XFMR
VENTILATEUR
YRH GRCW
(Le fil « G » est
optionnel selon
le type de
système)
YRH GRCW
COMPRESSEUR DE
CLIMATISATION
CÂBLAGE DU SYSTÈME DE REFROIDISSEMENT
SEULEMENT ECOSTAT PSM011
**Cavalier RC-RH d'usine installé
+
-
SYSTÈME
XFMR
VENTILATEUR
CÂBLAGE DU SYSTÈME DE CHAUFFAGE
ET DE REFROIDISSEMENT AVEC DEUX
TRANSFORMATEURS ECOSTAT PSM011
** Cavalier RC-RH d'usine RETIRÉ
+
+
VALVE À
GAZ OU
CHAUDIÈRE
-
REFROIDISSEMENT
XFMR
-
CHAUFFAGE
XFMR
Châssis mis à la terre
COMPRESSEUR DE
CLIMATISATION
YRH GRCW
VENTILATEUR
YRH GRCW
COMPRESSEUR DE
CLIMATISATION
(PSM011) ESPAÑOL – IDENTIFICACION DE CABLES Y DIAGRAMAS DE CABLEADO
Y
RC
RH
G
CABLE DE PUENTE
RC-RH
INCLUIDO
NOTAS DEL DIAGRAMA DEL CABLEADO:
• Los cables marcados por líneas punt eadas son cables opcionales y su
uso dependerá del t ipo de sistema específico.
• Si reemplaza un Honeywell TM-11 despr enda el cable "R". Conecte el
cable “B” a la terminal “RH”.
• Si reemplaza el t er mostato que t iene un cable de reloj mar cado como
tipo “C”, despr enda este cable y no lo conect e a este t er mostato.
• Si los cables “Y” y “C” están present es, entonces “C” es un cable
normal, despr éndalo y no lo conecte a est e termost at o.
• Si un cable “B” en su sistema es un cable normal, despr éndalo y no lo
conecte a est e termost at o.
W
CABLEADO DEL SISTEMA SÓLO
PARA CALEFACCIÓN ECOSTAT PSM011
**Cable de puente RC-RH instalado de fábrica
+
-
VÁLVULA
DE GAS O
CALENTADOR
SISTEMA
XFMR
VENTILADOR
CABLEADO DEL SISTEMA DE CALEFACCIÓN Y
ENFRIAMIENTO ECOSTAT PSM011
CON UN TRANSFORMADOR
**Cable de puente RC-RH instalado de fábrica
+
VÁLVULA
DE GAS O
CALENTADOR
-
SISTEMA
XFMR
VENTILADOR
YRH GRCW
(El cable ”G” es opcional
dependiendo del
tipo de sistema)
YRH GRCW
COMPRESOR DE
AIRE
ACONDICIONADO
CABLEADO DEL SISTEMA SÓLO PARA
ENFRIAMIENTO ECOSTAT PSM011
**Cable de puente RC-RH instalado de fábrica
+
-
SISTEMA
XFMR
VENTILADOR
CABLEADO DEL SISTEMA DE CALEFACCIÓN Y
ENFRIAMIENTO ECOSTAT PSM011
CON DOS TRANSFORMADORES
**Cable de puente RC-RH de fábrica ELIMINADO
+
+
VÁLVULA
DE GAS O
CALENTADOR
-
ENFRIAMIENTO
XFMR
-
CALEFACCIÓN
XFMR
Tierra del chasis
YRH GRCW
YRH GRCW
VENTILADOR
COMPRESOR DE
AIRE
ACONDICIONADO
COMPRESOR
DE AIRE
ACONDICIONADO