Lux Products PSD022W, PSD011WA User Manual

Complete, Easy To Read
JP3
B
O
INSTALLATION AND OPERATING INSTRUCTIONS
PSD011Wa and PSD022W
SYSTEM POWERED, NON-PROGRAMMABLE
DIGITAL HEAT & COOL THERMOSTATS
LUX PRODUCTS CORPORATION
Mt. Laurel, New Jersey 08054, USA
Please read all instructions carefully before beginning installation
and save for future reference. Before removing any wiring from
your existing thermostat, the wires must be labeled with their
terminal designations. Ignore the color of the wires since they
Thank you for your confidence in our product. You should become fully acquainted with this thermostat before installing it for usage. Follow the installation procedures carefully, and one step at a time. This will save you time and minimize the chance of damaging either the thermostat or the systems that it controls. These instructions may contain information beyond that required for your particular installation. Please save these instructions for future reference.
COMPATIBILITY
• The multi-stage PSD022W thermostat can be used with most 24 volt, 2 stage heat and/or 2 stage cool: gas, oil, or electric heating and air conditioning systems, or single-stage heat pumps.
• These thermostats cannot be used to control 3-wire zone valves, gas Millivolt heating systems, multi-stage heat pumps, or 120/240 volt (line voltage) heating or cooling systems. Ask your dealer for other LUXPRO thermostats to control those systems.
FEATURES
Large Easy to Read Backlit Display
• Digital, Non-Programmable
• Gas / Electric Blower Fan Option
• System Powered Only
• Set Temperature Range 45°F to 90°F
• Clean, Attractive Design
• Large, Easy To Read Display with LED Backlight
INSTALLATION
PLEASE READ ALL INSTRUCTIONS CAREFULLY BEFORE BEGINNING INSTALLATION.
This thermostat is protected against normal static electric
discharges. However, in extremely dry weather you should touch
a grounded metal object before touching the thermostat to
minimize the risk of causing damage to the unit.
TOOLS REQUIRED:
• #1 Phillips screwdriver (small - medium)
• Drill with 3/16-in. (4.8mm) drill bit
• Wire stripper/cutter
• Your thermostat is a precision instrument. Please handle it with care.
• Do not short (jumper) across the electric terminals on either the
furnace or air conditioner to test the system. This may damage the thermostat and void your warranty.
• All wiring must conform to all applicable local codes and ordinances.
• This thermostat should be limited to a maximum of 1.5 amps; higher
current may cause damage to the thermostat.
THERMOSTAT LOCATION:
On replacement installations, mount the new thermostat in place of the old one unless the conditions listed below suggest otherwise. On new instal­lations, follow the guidelines listed below.
1. Locate the thermostat on an inside wall, at about 5 ft. (1.5m) above the floor, and in a room that is used often.
2. Do not install it where there are unusual heating conditions, such as: direct sunlight, near a lamp, television, radiator, register, fireplace, on a wall opposite a stove, or that carries hot water pipes.
3. Do not locate in unusual cooling conditions, such as: on a wall separating an unheated room, or in a draft from a stairwell, door, or window.
4. Do not locate where air circulation is poor, such as: in a corner or alcove, or behind an open door.
5. Do not locate in a damp area. This can lead to corrosion that may shorten thermostat life.
6. Do not install the unit until all construction work and painting has been completed.
REMOVING THE OLD THERMOSTAT:
1. Switch OFF the electricity to both the furnace and air conditioner; then proceed with the following:
2. Remove cover from old thermostat. Most are snap-on types and simply pull off, some have screws on the sides, and these must be loosened first.
IMPORTANT!
may not comply with any standard.
Quick & Easy Temperature Change Buttons
Fan Slide Switch
Mode Slide Switch
7
2
˚
FAN
AUTO
ON
HEAT
OFF
COOL
LUXPRO
• Easy To Install
• F / C Selectable Temperature Display
• Fixed 5 Minute Minimum Run / Off Time For Compressor Protection
• User Adjustable Set Temperature Limit Stops (PSD011Wa Only)
CAUTION:
Turn off electricity to the appliance before
installing or servicing the thermostat or any part
of the system. Do not turn the electricity back on
CAUTION:
until the work is completed.
52051
3. Take note the letters printed near the wire terminals. Attach labels (enclosed) to each wire for identification by terminal letter, not color.
4. Make sure the wires do not fall back inside the wall, and remove and label one wire at a time. Do not allow wires to touch each other or any parts of the thermostat.
5. Loosen all screws on the old thermostat and/or base, and remove it from the wall.
CAUTION:
Be careful not to drop the body or disturb any
MOUNTING THE NEW THERMOSTAT:
1. Strip insulation leaving 3/8 in. (9.5mm) of bare wire on the ends and clean off any corrosion present.
2. Fill the wall opening with non-combustible insulation to prevent drafts from affecting the thermostat while in use.
3. Pull your new thermostat apart by applying pressure to the thumb tab on the bottom edge of the unit. While pressure is being applied to this release latch, pull the two halves of the thermostat apart near the bottom edge.
4. Hold the base against the wall. Route the wires through the larger hole adjacent to the terminal block. Position the base for best appearance (to hide any marks from an old thermostat). Attach the base to the wall with the two screws provided.
NOTE: If you are mounting the base to a soft material like plasterboard, or if you are using the old mounting holes, the screws may not hold. Drill a 3/16-in (4.8mm) hole at each screw location, and insert the plastic anchors provided. Then mount the base as described below.
CONNECTING THE WIRES:
5. Clean bare wire ends must be inserted between the black clamp plate and the brass terminal as shown here.
6. Securely tighten all electrical terminal screws (even unused ones).
of the electronic parts.
WIRING INFORMATION
** Complete heating or cooling system wiring can be found in the WIRE IDENTIFICATION AND WIRING SCHEMATICS section of this instruction sheet. The schematics shown provide component information for brand new installations or for un-referenced wires.
SETUP OPTIONS
A table similar to this one shown below is printed on the thermostat's circuit board. There may be minor differences present in some of the wording of your specific model, but the function of each option will be the same.
UP
DOWN
JP1 (SCALE)
JP2 (FAN)
JP3 (B / O)
JUMPER SETTINGS:
There are three (3) headers (or jumpers) located inside the thermostat at the rear of the circuit board. These settings can be changed from their default values by removing its corresponding black jumper cap and reinstalling the cap so that it is positioned on the adjacent pair of metal pins. A change to ANY of the jumper settings will not be recognized until power to the thermostat is removed for at least 2 minutes, and then power is restored again. This can simply be accomplished by removing the thermostat from the wired back plate. Each of these jumpers changes a different setup option. The choices for these options are listed in a table printed on the circuit board, and are also printed adjacent to each individual setting jumper.
F
ELECT
B
C
GAS
O
F
JP1 - FAHRENHEIT OR CELSIUS DISPLAY FORMAT:
This setting controls whether the temperature is shown in degrees °F or °C on the LCD display screen.
JP1
C
JP2 - GAS / ELECTRIC FAN OPERATION:
This setting changes whether the system's blower fan (if applicable) is controlled by the thermostat in HEAT mode. Choose ELECTRIC if you have electric heating, and require the thermostat to control the fan. Choose GAS if you have a gas heating system, this will allow the furnace itself to control the operation of the blower fan.
NOTE: If you have an Electric Heat system and the blower does not operate after installation, locate the "Gas/Electric" option jumper and ensure that it is in the "Electric" position.
JP3 - [B] OR [O] TERMINAL USAGE OPTION:
This setting determines how the thermostat will use the shared B/O terminal connection on the back plate. Choose the UP (B) position to have the B/O terminal powered while in heat mode, and un-powered while in cool and off modes. Choose the DOWN (O) position to have the B/O terminal powered while in cool mode, and un-powered while in heat and off modes.
ELECT
GAS
JP2
COMPLETING THE INSTALLATION
Once any optional jumper settings have been performed as described in the previous section, ensure that at least 2 minutes have passed since the thermostat has been last powered. Install your new thermostat onto its base. To do this, start with the bottom tilted out towards you at first, and line up the two holes in the top of the thermostat with the two hooks on the top of the back plate. Slowly pivot the bottom of the thermostat towards the back plate and push firmly on the bottom half of the thermostat until it is securely latched to the back plate. If the two thermostat halves do not latch easily, remove and try again. Do not attempt to force them together.
NOTE: Before use, remove the plastic film (if present) that is protecting the LCD display screen.
Turn the electrical power back ON to both your heating and/or air conditioning systems. Verify that both systems (and the blower fan if used) are operating properly. When set to a high temperature, the heating system should provide warm air after a short time in Heat Mode. Likewise, a cooling system should provide cool air after a short time when set to a low temperature in Cool Mode. Usually, sound from the furnace and/or air conditioning units can be heard while either is running. If your system uses a blower fan, the rush of moving air should be heard within a short time after either has been started. Your installation is now complete.
© 2007 LUX PRODUCTS CORPORATION. ALL RIGHTS RESERVED
FRONT PANEL ITEMS
SYSTEM MODE SWITCH:
The MODE switch has three positions: HEAT, OFF, and COOL. In the winter, set the mode switch to HEAT to control your heating system; in the summer, set the switch to COOL to control your air conditioning. In the spring and fall, or when the windows are open, you can set the switch OFF.
NOTE: When the system mode switch is in the OFF position, it is normal for the system's blower fan ("G" terminal if used) to still become activated depending upon the position of the FAN mode switch (see below).
FAN MODE SWITCH:
The FAN switch has two positions: AUTO and ON.
• In the AUTO position, the operation of the blower fan is determined only by the on/off cycling of the heating and cooling systems.
• When the FAN switch is in the ON position, the system's blower fan will be commanded ON, and remain ON while the FAN switch is in the ON position (this also includes when the System Mode Switch is in the OFF position).
NOTE: The FAN switch only works if your system provides a wire for the thermostat’s "G" terminal.
PUSH BUTTONS:
There are two push buttons to the right of the unit's display screen. These are used to adjust the set point temperature.
OPERATING INSTRUCTIONS
TEMPERATURE ADJUSTMENT:
While in HEAT or COOL mode, a single press on either the UP or DOWN button causes the word “SET” to appear on the screen. Once “SET” is present, the set temperature value starts flashing and the set point temperature can be altered by pressing either the UP or DOWN button once per degree of change, or by holding either button for at least two seconds to automatically increment the set point quickly in the associated direction.
Based upon the relationship of the set temperature to the displayed ambient room temperature, the thermostat will engage either the W1 terminal in heat mode or the Y1 terminal in cool mode, if a temperature demand is present.
(For the PSD022W model only): If there is a large thermal demand present which is greater than the first stage of heating (W1) or cooling (Y1) can accommodate for, then a second stage of heating (W2) or cooling (Y2) will be activated. When the second stage of either heating or cooling becomes active, the word “AUX” will be shown on the display screen. There is approximately a 4 minute delay that is enforced between the activation of the first stage and the second stage of heating or cooling.
DISPLAY ILLUMINATION:
Pressing either set temperature button will illuminate the display for easier viewing in dim light conditions. The light will remain on for approximately 12 seconds. While the light is illuminated, pressing any of the three push buttons will continue the lighting and remain on for approximately 12 more seconds.
MINIMUM RUN/OFF TIME:
This is determined by the thermostat, and controls the minimum length of time that the thermostat must remain with Heat or Cool either On or Off, before it will automatically switch to the alternate On or Off state. This feature prevents rapid or short cycling, and provides compressor protection for cooling equipment. The time amount for this delay is fixed at 5 minutes between on or off load changes.
TEMPERATURE LIMIT STOPS (PSD011Ba ONLY):
There are two independent set temperature stops: a Maximum Heat Set Temperature, and a Minimum Cool Set Temperature. Each of these temperature stops is user adjustable in one-degree increments. The heat limit stop prevents the set temperature from being adjusted higher than the heat limit setting. The cool limit stop prevents the set temperature from being adjusted lower than the cool limit setting.
To set the heat and cool set temperature limit stops, always start with the system mode switch in the OFF position. Press and hold the UP key while sliding the mode switch from either OFF to HEAT (to adjust the maximum heat set temperature), or from OFF to COOL (to adjust the minimum cool set temperature). “Ht Lim” or “Cl Lim” will be displayed on the LCD screen while you are setting the heat or cool limits respectively. While in the adjustment mode for each of the temperature stops, use the UP and DOWN buttons to adjust the limit value, just as you would for adjusting the set temperature under normal operation. NOTE: If no buttons are pressed for 4 seconds, the thermostat will accept the limit value that was on the screen, and return to normal operating mode, for the current mode switch position. Once, complete, you should return to the adjustment mode again for both heat and cool to confirm your desired settings for both temperature modes.
TECHNICAL ASSISTANCE
If you have any problems installing or using this thermostat, please carefully and thoroughly review the instruction manual. If you require assistance, please contact our Technical Assistance Department at 856-234-8803 during regular business hours between 8:00AM and 4:30PM Eastern Standard Time, Monday through Friday. You can also receive technical assistance online anytime day or night at http://www.luxproproducts.com. Our web site offers you answers to the most common technical questions, and also permits you to email your questions to our technical support staff at your convenience.
WARRANTY
Limited Warranty: If this unit fails because of defects in materials or workmanship within three years of the date of original purchase, LUX will, at its option, repair or replace it. This warranty does not cover damage by accident, misuse, or failure to follow installation instructions. Implied warranties are limited in duration to three years from the date of original purchase. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. Please return malfunctioning or defective units to the location from which the purchase was made, along with proof of purchase. Please refer to "Technical ASSISTANCE" before returning thermostat. Purchaser assumes all risks and liability for incidental and consequential damage resulting from instal­lation and use of this unit. Some states do not allow the exclusion of incidental or consequential damages, so the above exclusion may not apply to you. This warranty gives you specific legal rights and you may also have other rights which vary from state to state. Applicable in the U.S.A. and Canada only.
(PSD011W, PSD011Wa, PSD022W) ENGLISH - WIRE IDENTIFICATION AND WIRING SCHEMATICS
W2
Y2
V
RH R
5
4
W1
W
H
G
F
C B*
TC
RRC
V 5
G F
C B*
TC
Y1
C*
6
RRHRC
R
V 5
6
4
W1
W
H
W2
G F
C B* TC
Y1
Y
C*
Y2
V
R RCRH
5
4
6
W1
W
H
W2
G F
C B*
TC
Y1
Y
C*
Y2
V
R RHRC
5
G
O
B
F
C B* TC
Y
C*
6
SISTEMAS EXCLUSIVOS
DE CALEFACCIÓN
SISTEMAS EXCLUSIVOS
DE ENFRIAMIENTO
CON UN TRANSFORMADOR CON DOS TRANSFORMADORES
SISTEMAS DE CALEFACCIÓN/ENFRIAMIENTO SISTEMAS DE CALEFACCIÓN/ENFRIAMIENTO
Y2 Y1
W1 W2
B/O
RH
RC
G
C
OPCIONAL
PUENTE
INSTALADO
CABLES DE UNA BOMBA DE CALOR DE UNA SOLA FASE TÍPICA
Y2 Y1
W1 W2
B/O
RH
RC
G
C
PUENTE
INSTALADO
Y2 Y1
W1 W2
B/O
RH
RC
G
C
PUENTE
INSTALADO
Y2 Y1
W1 W2
B/O
RH
RC
G
C
PUENTE
PROPORCIONADO
RETIRADO
Y2 Y1
W1 W2
B/O
RH
RC
G
C
OPCIONAL
PUENTE
INSTALADO
PUENTE
"PROVISTO POR EL CLIENTE"
INCLUIDO
OPCIONAL
OPCIONAL
OPCIONAL
OPCIONAL
OPCIONAL
OPCIONAL
022
*
022
*
022
*
022
*
022
*
HEATING ONLY SYSTEMS
C B*
C
G W1 W2
022
*
Y2 Y1
JUMPER
RH
INSTALLED
RC
B/O
HEATING / COOLING SYSTEMS HEATING / COOLING SYSTEMS
WITH ONE TRANSFORMER WITH TWO TRANSFORMERS
C
G W1 W2
022
*
Y2
Y1
JUMPER
RH
INSTALLED
RC
B/O
G
W1
W2
RH R
C B*
G F
W1
W2
Y2
Y1
R RCRH
TC
OPTIONAL
F
W
H
4
OPTIONAL
V
5
TC
W
H
4
OPTIONAL
OPTIONAL
Y
6
C*
V
5
TYPICAL SINGLE STAGE HEAT PUMP WIRING
C B* TC
G
Y
R RHRC
O
“CUSTOMER SUPPLIED”
JUMPER
ADDED
022
JUMPER
INSTALLED
C
G W1 W2
*
Y2 Y1
RH
RC
B/O
COOLING ONLY SYSTEMS
022
*
JUMPER
INSTALLED
022
*
PROVIDED
JUMPER
REMOVED
F
C*
6
V
5
OPTIONAL
B
TYPICAL 24 VOLT
C B*
C
G W1 W2
Y2 Y1
RH
RC B/O
C
G W1 W2
Y2 Y1
RH
RC
B/O
G F
Y2
C*
Y1
RRC V 5
C B* TC
G F
W
W1
W2
Y2
Y
Y1
R
RRHRC
TC
C*
6
H
V 5
OPTIONAL
4
OPTIONAL
OPTIONAL
6
Jumper INSTALLED
+
SYSTEM
Jumper INSTALLED
+
SYSTEM
XFMR
TYPICAL 24 VOLT, HEATING & COOLING SYSTEMS
Jumper INSTALLED
HEATING ONLY SYSTEMS
022
*
RC RHB/O Y1 Y2 W2 W1 G C
System Common
-
XFMR
COOLING ONLY SYSTEMS
TYPICAL 24 VOLT
STAGE-2 STAGE-1
022
022
*
*
HEATER
RC RHB/O Y1 Y2 W2 W1 G C
System Common
-
STAGE-1 STAGE-2
022
*
A/C COMPRESSOR
WITH ONE TRANSFORMER
022
*
BLOWER
FAN
BLOWER
FAN
RC RHB/O Y1 Y2 W2 W1 G C
022*
(PSD022W)
ONLY
System Common
+
SYSTEM
XFMR
-
STAGE-1 STAGE-2
022*022
A/C COMPRESSOR
STAGE-2 STAGE-1
*
HEATER
BLOWER
FAN
022*
(PSD022W)
ONLY
022*
(PSD022W)
ONLY
022*
(PSD022W)
ONLY
Chassis Ground
WIRING DIAGRAM NOTES:
1. The BOLD lines are what you should be connecting to the terminals on this new thermostat.
2. The DASHED lines are optional depending upon your system type.
3. In many cases, the thin lines shown as “SYSTEM COMMON” will not be visible at the thermostat location, they are located with your heating and cooling equipment.
4. For Heat Pumps, use the “B” or “O” wire, NOT BOTH. Typically neither are used in a conventional system.
5. If “Y” and “C” wires are both present, then “C” is a common wire.
6. If you have a “B” wire in your system which is used as a common wire, connecting it to the “B/O” terminal on this thermostat may damage your system and/or the thermostat.
TYPICAL 24 VOLT, HEATING & COOLING SYSTEMS
Provided Jumper REMOVED
WITH TWO TRANSFORMERS
022
*
RC RHB/O Y1 Y2 W2 W1 G C
Common #1
+
COOL XFMR
Common #2
+
-
HEAT XFMR
Jumper INSTALLED
-
STAGE-1 STAGE-2
A/C COMPRESSOR
TYPICAL 24 VOLT, SINGLE-STAGE
HEAT PUMP SYSTEMS
STAGE-2 STAGE-1
022*022
022
RC RHB/O Y1 Y2 W2 W1 G C
System Common
+
-
SYSTEM
XFMR
SINGLE STAGE
HEAT PUMP
COMPRESSOR
REVERSING
VALVE
*
HEATER
“Customer Supplied”
Jumper ADDED
*
BLOWER
FAN
BLOWER
FAN
022*
(PSD022W)
ONLY
022*
(PSD022W)
ONLY
(PSD011W, PSD011Wa, PSD022W) FRANÇAIS – IDENTIFICATION DES FILS ET SCHÉMAS DE CÂBLAGE
SYSTÈMES DE
CHAUFFAGE SEULEMENT
C B*
C
G W1 W2
022
*
Y2 Y1
CAVALIER
RH
INSTALLÉ
RC
B/O
SYSTÈME DE CHAUFFAGE /
REFROIDISSEMENT
AVEC UN SEUL TRANSFORMATEUR AVEC DEUX TRANSFORMATEURS
C
G W1 W2
022
*
Y2 Y1
CAVALIER
RH
INSTALLÉ
RC
B/O
FILS DE POMPE À CHALEUR À UN ÉTAGE TYPIQUE
CAVALIER AJOUTÉ
« FOURNI PAR LE CLIENT »
022
*
CAVALIER INSTALLÉ
G
W1
W2
RH R
C B*
G F
W1
W2
Y2
Y1
R RCRH
C
G W1 W2 Y2 Y1
RH
RC
B/O
TC
OPTIONNEL
F
W
H
4
OPTIONNEL
V
5
TC
W
H
4
OPTIONNEL
OPTIONNEL
Y
6
C*
V
5
C B* TC
G
Y
R RHRC
O
SYSTÈMES DE
REFROIDISSEMENT SEULEMENT
C
G W1 W2
022
*
Y2 Y1
CAVALIER
RH
INSTALLÉ
RC B/O
SYSTÈME DE CHAUFFAGE /
REFROIDISSEMENT
C
G W1 W2
022
*
Y2
CAVALIER
Y1
FOURNI
RETIRÉ
RH
RC
B/O
F
C*
6
V
5
OPTIONNEL
B
C B*
G F
Y2
C*
Y1
RRC V 5
C B* TC
G F
W
W1
W2
Y2
Y
Y1
R
RRHRC
(PSD022W)
SEULEMENT
TC
OPTIONNEL
6
H
4
OPTIONNEL
OPTIONNEL
C*
6
V 5
022*
SYSTÈMES DE CHAUFFAGE
TYPIQUE DE 24 VOLTS SEULEMENT
Cavalier INSTALLÉ
022
*
RC RHB/O Y1 Y2 W2 W1 G C
Système commun
+
-
SYSTÈME
XFMR
SYSTÈMES DE REFROIDISSEMENT
TYPIQUE DE 24 VOLTS SEULEMENT
Cavalier INSTALLÉ
ÉTAGE-2 ÉTAGE-1
022
*
RADIATEUR
022
*
RC RHB/O Y1 Y2 W2 W1 G C
Système commun
+
-
SYSTÈME
XFMR
SYSTÈMES DE CHAUFFAGE ET DE REFROIDISSEMENT TYPIQUES DE 24 VOLTS AVEC UN TRANSFORMATEUR
Cavalier INSTALLÉ
ÉTAGE-1 ÉTAGE-2
022
COMPRESSEUR
DE CLIMATISATION
022
*
*
VENTILATEUR
SOUFFLANT
RC RHB/O Y1 Y2 W2 W1 G C
Système commun
+
-
SYSTÈME
XFMR
ÉTAGE-1 ÉTAGE-2
COMPRESSEUR
DE CLIMATISATION
022
*
ÉTAGE-2 ÉTAGE-1
022
*
RADIATEUR
VENTILATEUR
SOUFFLANT
VENTILATEUR
SOUFFLANT
022*
(PSD022W)
SEULEMENT
022*
(PSD022W)
SEULEMENT
022*
(PSD022W)
SEULEMENT
SYSTÈMES DE CHAUFFAGE ET DE REFROIDISSEMENT
TYPIQUES DE 24 VOLTS AVEC DEUX TRANSFORMATEURS
Cavalier fourni RETIRÉ
022
*
022*
(PSD022W)
SEULEMENT
RC RHB/O Y1 Y2 W2 W1 G C
Commun n° 1
+
-
REFROIDISSEMENT
XFMR
Châssis mis à la terre
Commun n° 2
+
-
CHAUFFAGE
Cavalier INSTALLÉ
ÉTAGE-1 ÉTAGE-2
XFMR
COMPRESSEUR
DE CLIMATISATION
SYSTÈMES DE POMPE À CHALEUR
TYPIQUES À UN ÉTAGE, 24 VOLTS
022*022
022
*
ÉTAGE-2 ÉTAGE-1
*
RADIATEUR
VENTILATEUR
SOUFFLANT
022*
(PSD022W)
SEULEMENT
RC RHB/O Y1 Y2 W2 W1 G C
Système commun
+
-
SYSTÈME
XFMR
COMPRESSEUR
DE POMPE À CHALEUR
À UN ÉTAGE
VENTILATEUR
SOUFFLANT
ROBINET
INVERSEUR
REMARQUES AU SUJET DES SCHÉMAS DE BRANCHEMENT :
1. Les lignes en GRAS représentent les fils que vous devriez connecter aux bornes de ce nouveau thermostat.
2. Les traits TIRÉS sont optionnels d’après le type de votre système.
3. Dans de nombreux cas, les lignes minces marquées « SYSTÈME COMMUN » ne seront pas visibles où le thermostat se trouve, car elles se trouvent avec les appareils de chauffage et de climatisation.
4. Pour les pompes à chaleur, utilisez le fil « B » ou le fil « O », MAIS PAS LES DEUX. Ceux-ci ne sont habituellement pas utilisés pour les systèmes traditionnels.
5. Si « Y » et « C » sont tous les deux présents, alors « C » est un fil commun.
6. Si un fil « B » de votre système est un fil commun, le connecter à la borne « B/O » du thermostat pourrait endommager votre système et/ou le thermostat.
(PSD011W, PSD011Wa, PSD022W) ESPAÑOL – IDENTIFICACION DE CABLES Y DIAGRAMAS DE CABLEADO
022*
SÓLO
(PSD022W)
SISTEMAS TÍPICOS EXCLUSIVOS DE CALEFACCIÓN DE 24 VOLTIOS
Puente INSTALADO
022
*
RC RHB/O Y1 Y2 W2 W1 G C
Sistema Común
+
-
SISTEMA
XFMR
SISTEMAS TÍPICOS EXCLUSIVOS
DE ENFRIAMIENTO DE 24 VOLTIOS
Puente INSTALADO
DOS FASES UNA FASE
022
*
CALENTADOR
022
*
VENTILADOR
RC RHB/O Y1 Y2 W2 W1 G C
Sistema Común
+
-
SISTEMA
XFMR
SISTEMAS TÍPICOS DE CALEFACCIÓN Y ENFRIAMIENTO
Puente INSTALADO
UNA FASE DOS FASES
022
*
COMPRESOR DE
AIRE ACONDICIONADO
DE 24 VOLTIOS CON UN TRANSFORMADOR
022
*
VENTILADOR
RC RHB/O Y1 Y2 W2 W1 G C
Sistema Común
+
-
SISTEMA
XFMR
UNA FASE DOS FASES
COMPRESOR DE
AIRE ACONDICIONADO
DOS FASES UNA FASE
022*022
*
CALENTADOR
VENTILADOR
022*
SÓLO
(PSD022W)
022*
SÓLO
(PSD022W)
022*
SÓLO
(PSD022W)
SISTEMAS TÍPICOS DE CALEFACCIÓN Y ENFRIAMIENTO
DE 24 VOLTIOS CON DOS TRANSFORMADORES
Puente Proporcionado RETIRADO
022
*
022*
SÓLO
(PSD022W)
RC RHB/O Y1 Y2 W2 W1 G C
Común #1
+
ENFRIAMIENTO
XFMR
-
Tierra del chasis
+
CALEFACCIÓN
XFMR
Común #2
-
UNA FASE DOS FASES
AIRE ACONDICIONADO
022*022
COMPRESOR DE
DOS FASES UNA FASE
*
CALENTADOR
VENTILADOR
022*
SISTEMAS TÍPICOS DE BOMBAS DE CALOR
DE UNA SOLA FASE DE 24 VOLTIOS
Puente INSTALADO
022
*
SÓLO
(PSD022W)
RC RHB/O Y1 Y2 W2 W1 G C
Sistema Común
+
-
SISTEMA
XFMR
COMPRESOR DE
BOMBA DE CALOR
DE UNA SOLA FASE
VENTILADOR
VÁLVULA
DE INVERSIÓN
COMENTARIOS SOBRE LOS DIAGRAMAS DE CABLEADO:
1. Las líneas RESALTADAS son las que debe conectar a los terminales de este nuevo termostato.
2. Las líneas ENTRECORTADAS son opcionales de acuerdo con su tipo de sistema.
3. En muchos casos, las líneas delgadas, que se indican como “SISTEMA COMUN”, no se pueden ver en el termostato porque se encuentran en su equipo de calefacción y refrigeración.
4. Para las bombas de calor, use el alambre “B” u “O”, NO AMBOS. Generalmente no se utiliza ninguno en un sistema convencional.
5. Si hay un alambre “Y” y un alambre “C”, el común será el alambre “C”.
6. Si un alambre “B” en su sistema se utiliza como alambre común, entonces conectarlo al terminal "B/O" del terminal del termostato puede causar daños a su sistema y/o al termostato.
Loading...