Connection of sensor and power supply by means of
telephone plug RJ11
Power supply: 230V~ ±10 %
Power consumption: < 1W
Ambient temperature: -25°C – +50°C
Degree of protection/class: Detector: IP65 / II / CE
Supply: IP20 / II / CE
Settings: manually or by remote
control
Light values: 10 - 2000 Lux
(remote control)
Extension of the detection area: with PD9-S-SDB
Area of coverage: circular 360°
Range Ø H 2.5m / T= 18°C:
PD9-M-1C-IP65 seated 4 m / tangential
10m / radial 6 m
PD9-M-1C-IP65-GH max. Ø 5.4m
Recommended height for mounting
PD9-M-1C-IP65 2 - 3 m
PD9-M-1C-IP65-GH 5 - 10m
Light measurement: daylight and artificial light
One channel to switch the lighting
Type of contact: NOC/with pretravel
tungsten contact
Contact load: 2300 W, 230 V~,
1150VA cos ϕ= 0.5
Time-settings: 15sec. - 30 min. / Test
(remote control)
Dimensions H x Ø [mm]
Detector Ø 45 x H 40 mm
Visible part Ø 45 x H 12 mm
Power supply L 165 x W 24 x H 24 mm
Technical data PD9-Slave
Electrical data same as above, but just one channel for
signaling motion detection.
Declaration of Conformity: The product complies
with the low voltage recommendation 2006/95/EC
and the EMV recommendation 2004/108/EC.
18. Technical data
14. Wiring diagram
15. Connections
Typ RAL9010 RAL9006
PD9-M-1C-SDB-IP65-FC 92912 92913
PD9-S-SDB-IP65-FC
(only sensor part)
92915
PD9-M-1C-SDB-IP65-GH-FC 92931 92932
PD9-S-SDB-GH-FC
(only sensor part)
92933
LUXOMAT® Remote control:
IR-PD9 (incl. wall bracket) 92201
IR-PD-Mini 92159
Accessory:
Wire basket BSK 92199
Wall bracket for remote control as replacement 92100
Coverring for PD9 white 92238
Coverring for PD9 silver 92237
Coverring for PD9 anthracite 92235
Blind PD9-GH for detection 180° white 33207
13. Article / Part-Nr. / Accessory
11. Manual Switching
You can switch the lighting on and off manually by
pressing the pushbutton for a short time. It will stay on or
off as long as people are detected plus the congured
follow up time.
17. LED-functional indicators, fault-finding
The functional indicators in the case of the LUXOMAT
®
PD9-M-1C-SDB-IP65(-GH) (red and green LED‘s)
Red LED indicating self-checking mode (over a period
of 60 seconds following mains‘-supply lock-on)
Flashing at intervals of 1 second
EEPROM/ memory empty
Flashing rapidly
EEPROM/ memory contains information
Red LED as an indicator of status
Flashing irregularly
Movements are detected within the area of coverage
Flashing regularly
Detector identifies bright, light off
(dependent upon operating mode)
Not illuminated
Detector identifies dark, light on
(dependent upon operating mode)
Flashing extremely rapidly
Too bright / Too dark / Undefined
Red LED as an acknowledgement of receipt for
commands from the remote control
Illuminated for 2 seconds
Signal validly received
Illuminated for 0.5 seconds
Not-accepted command, detector blocked
Flashing extremely rapidly
Not-accepted command, occurs, for example, when an
attempt is made to input twilight-value are too bright or
too dark
Lights up for 3 seconds
Display automatic: Lights up for 3 seconds
Flashing for 3 seconds
Display
semi automatic
Green LED as an indicator of status for
“Permanent protection against sabotage”
Flashing irregularly
Movement are detected within the area of coverage
Flashing regularly
Detector identifies bright, light off
(dependent upon operating mode)
Not illuminated
Detector identifies dark, light on
(dependent upon operating mode)
lluminated for 2 seconds
Signal validly received
(only possible for status “Light on/Light off”)
10. Fully/Semi automatic mode
(for IR-PD9
functions see page 1
)
Fully automatic operation (presence)
In this operating mode, the lighting switches automatically on and off for increased comfort, depending on
presence and brightness.
Semiautomatic operation (absence)
(Semiautomatic can only be activated via the remote
control!)
In this operating condition, in order to gain increased
savings, the lighting is energized only after being manually
switched on.
Switch-off takes place automatically.
The semiautomatic mode basically behaves like the fully
automatic one. However, the difference is that switching-on
must always be carried out manually!
12. Determination of the switch on threshold
to attain a calculatory target value
(for IR-PD9 functions see page 1)
Example:
To do this, rst: open, then select the channel.
Using remote control, you then enter a low Lux value, e.g.
100Lux. The red channel LED ashes quickly and looks “bright”.
You can now approach the switch-on threshold in steps of
20 Lux by repeatedly pressing the step button.
(This only applies to a preselected value of less than 200 Lux.
If the preselected value is above 200 Lux, the threshold is
approached in steps of 50Lux.)
Always take into account the response time of the LUXOMAT®;
each time you press the button, you must wait for 4sec.
Once the correct value is reached, the LED stops ashing.
In this example, 100 Lux is entered and the button is pressed
twice. If the LED goes out, the value seen by the PD9-M-1CSDB-IP65(-GH) is approximately 140Lux.
If the light value actually measured on the working surface is
280Lux, for example, then: 140 : 280 = 0.5 (light distribution
in the room).
If the specied value on the working surface is now to be
500Lux, the LUXOMAT® PD9-M-1C-SDB-IP65(-GH) must be
programmed with a value of 500 Lux * 0.5 = 250 Lux.
In the example, enter 200Lux and then press the button
again.
Steps:
Range 20 - 200 Lux ........ 20Lux/step
Range 200 - 1000Lux ........ 50 Lux/step
If the current luminosity is sufcient,
the button can be used to simply read in the light value
as a brightness switching value (switch-on value).
16. Putting into operation / Settings
Follow-up time for light control
The time can be set infinitely variably at
between 1 and 30min.
Symbol TEST: test mode (every movement
switches on the light for a period of 1 second,
switching it off for a period of 2 seconds after
that regardless of the level of brightness
Twilight-switch for light control (relay 1)
The switch-on value for the light can be set at
between 100 and 1500 Lux. Using the rotary
control, the luminance set points can be set as
desired.
Symbol :
Night-time operation
Symbol :
Daytime/ Night-time operation
Standard mode with master 1-channel occupancy detectors
(NO)