![](/html/42/42e9/42e98e9b91d47c6e4dc8e166d7b5c61968fe48c2fbe55f6cca4ac6333a099060/bg1.png)
Installation and Operating Instruction for B.E.G.-Occupancy detectors PD4-Master-TRIO-2DALI/DSI-1C-SM/-FC
A circular opening
of diameter 100mm
must be produced in
the ceiling.
Having connected
up the cables in
accor dance with
regulations, the
detector is inserted
into the opening as
shown and fixed
into position with
the retaining bracket
using screws.
A Light sensor 1 | B Light sensor 2
1 LED red OFF function
2 LED green too bright/too dark CDS 1
3 LED white semi-automatic DA 1/2
4 LED white semi-automatic Channel 3
5 LED green too bright/too dark CDS 2
6 LED red motion indicator/walking test
2a. Installation of the LUXOMAT®
PD4-M-TRIO-2DALI/DSI-1C-SM
2b. Installation of the LUXOMAT®
PD4-M-TRIO-2DALI/DSI-1C-FC
3. Hardware configuration
Position of light sensors and LEDs
The detector must be in stalled on a solid and
level surface. The circular cover ring must be removed
prior to assembly. To do this, twist the lens (C) anticlockwise through approximately 5° and lift off.
Having connected up the wires in accordance with
regulations, secure the detector with 2 screws.
After installation replace the lens and lock (turn
clockwise). Mains to be connected.
4. Putting into operation
of the remote control
(optional)
Remote control
LUXOMAT® IR-PD4-TRIO-DALI
1. Check Battery:
open battery compartment by pressing
the plastic springs together and removing the battery-holder.
Caution:
Settings with remote control supersede
the settings by courtesy of potentiometers.
LUXOMAT
®
PD4-M-TRIO-2DALI/DSI-1C
1. Mounting preparations
Work on the 230V mains supply
may only be carried out by qualified professionals or by instructed
persons under the direction and
supervision of qualified skilled electrical personnel in accordance with
electrotechnical regulations.
Disconnect supply before installing!
When in Master/ Slave mode of
operation, the Master-appliance
must always be installed at the
location where there is least
daylight.
Option:
Wall bracket for remote
control
IR-PD4-TRIO-DALI
A4 5 1 3 2 6
B
GB
6. Putting into operation / Settings
Self test cycle
After an initial 60-second self-test cycle, the LUXOMAT® PD4-M-TRIO-2DALI/DSI-1C is
ready for operation.
Potentiometer 3: Follow-up time for light control
The time can be set infinitely variably at between 1 and 60 minutes. The
time-setting is valid for all three channels of the PD4-M-TRIO-2DALI/DSI-1C.
Symbol TEST: Test mode (Every movement switches on the light for a period
of 2 second, switching it off for a period of 2 seconds after that regardless
of the level of brightness.)
Potentiometer 2: Twilight-switch for light control
The switch-on value for the light can be set at between 40 and 1200Lux.
Using the rotary control, the luminance set points can be set as desired.
Symbol : Night-time operation | Symbol : Daytime/ Night-time operation
Potentiometer 1: Orientation lighting
This rotary controller serves to determine the working time of the orientation
lighting (fixed to 20%).
“ON” for permanent orientation lighting.
“OFF” for deactiviation of orientation lighting.
Pulse spacing PD-Slave
2 or 9 seconds can be set for the pause between 2 pulses sent to the master.
The setting can be made with activated ( ) or deactivated ( ) LED indicator.
For devices with a separate slave input, 2sec. can be set.
100 mm
open
close
C
Explanation of the key functions
6
5
4
A
3
2
1
B
DIP 1 HA / A
DIP 2 Ini OFF/ON
Lamps at start-up OFF/ON
DIP 3 RESET
5. Position of potentiometer and DIP switch
SM
FC
3
1
2
DIP
123
DIP
321
123
SM FC
9s 2s
LED ON
DA 1/2 ON/OFF when locked
(=> see page 2, point 9)
Dimming
when locked
=> (
see page 2, point
8)
Activate test mode – when locked
Deactivate test mode: press Reset
Resetting when locked
The lighting relay is switched off, i.e. opened and the follow-up times
reset.
Permanent protection against sabotage
This function blocks the unit permanently (green LED is illuminated).
This operating mode can only be activated during the period of 5
seconds after pressing the “lock“ button. This status will only permit
actuating the function “Light on/Light off”.
The procedure for leaving this mode is as follows:
reset the hardware
using DIP switch 3 or switch the supply voltage as follows:
Dimming in opened state
The following approach will prove useful when setting a command value
(example workplace): Place a luxmeter flat on the desk, then, using the
remote control IR-PD4-TRIO-DALI, adjust the light up or down by pressing
the keys “max“ or “min“ until the desired command value which best
suits your requirements has been reached.
Saving of the through adjusted luminance set point
100 h function in opened state
to extend the life span – sums up automatically the burning time of
100% luminosity at the beginning up to 100 hours – only then can
lights dim
Orientation lighting and its follow-up time ON/OFF
Note: During the orientation light phase, the constant light regulation is
also active: if there is sufficient brightness, dimming occurs < 2V and,
if applicable, the lighting is switched off.
Orientation lighting – Adjustment ot the light intensity
The orientation lighting is adjustable in a span from 10 to 30% of the
nominal light. Standard adjustment is 20%.
t < 5 sec.
100
h
Settings by remote control
Unlocking device
60
10
to
or
Dimming of the luminance set
point (only for channel 1 and 2)
to
60
min
1
min
Follow-up time light
optionaloptionaloptionaloptional optional
100 h function
=> (see page 2, point 19)
Orientation lighting
ON = all LEDs ashes 2x
OFF = all LEDs ashes 1x
Follow-up time
orientation lighting
Orientation lighting
10 – 30% of nominal light
Luminance set point for
constant light regulation
to
or
Fully automatic/semi automatic mode
(only DA1/2) => (see page 2, point 10)
LED display ON/OFF
Sun button – preselected light
value (Daylight operation)
1000100
or
Saving of the dimmed
luminance set point
Resetting
when open:
All values
which have
been programmed using the remote
control are
deleted, and
those values
which have
been set by
potentiometer
are activated.
Locking device – Exit
programming mode
Permanent protection against sabotage
LED ashes
or
t < 5 sec.
DA 1/2 ON/OFF
optional
Switching between DALI and DSI
(factory settings DALI)
optional
Switching
Channel 1C between HVAC-
and light control (
factory settings
light)
ON
230 V
1sec. 1sec.30 sec. - 60sec.
OFF
![](/html/42/42e9/42e98e9b91d47c6e4dc8e166d7b5c61968fe48c2fbe55f6cca4ac6333a099060/bg2.png)
15.
Technical data
PD4-M-TRIO-2DALI/DSI-1C
Sensor and power supply in one case
Power supply: 230V~ ±10 %
Power consumption: < 1W
Ambient temperature: -25°C to +50°C
Degree of protection/class: IP20 / II
Settings: control dial, DIP switch and
remote control
Light values - Remote control:
100 - 1000Lux
Extension of the detection area: with Slaves
Area of coverage: circular 360°
Range of coverage Ø H 2.50m / T= 18°C:
seated 6.40m / tangential 24m / radial 8m
Recommended height for mounting: 2 - 3 m
Light measurement: mixed light, daylight + artificial
light, suitably for constant light
control
Light values - Potentiometer:
10 - 2000Lux
• Dali output DA 1/2 for light switching, light-controlled
Max. numbers of connected EB‘s: each 25 for DA1 and DA2
•
Channel 1C (-1C)
for light switching (panel lighting
), light- or
motion-controlled or HVAC circuit, only motion-controlled
Type of contact: NOC/with pretravel tungsten contact
Contact load
: 3000 W, 230V~, 16A cos ϕ=1 /
1500VA cos ϕ= 0,5, μ-Contact
Time-settings Channel 1C: 1 - 60 min. / Test
Dimensions H x Ø [mm] SM FC
124 x85 100 x 117
Visible portion when built into ceiling: H 37 x Ø 117mm
Technical data PD4-Slave
Power supply: 230 V~ ±10%
Impulse output: Optocoupler max. 2W
Impulse duration: 2sec. or 9sec.
Dimensions: SM FC
76 x 101 97 x 103
Visible portion when built into ceiling: 34x10mm
Declaration of Conformity: The product complies with
the low voltage recommendation 2006/95/EC and the EMV
recommendation 2004/108/EC.
14. Connections
Type SM FC FM
PD4-M-TRIO-2DALI/DSI-1C
(Master)
92751 92756 –
PD4-S (Slave) 92142 92254 9 2163
LUXOMAT
®
Remote control:
IR-PD4-TRIO-DALI (incl. wall bracket) 92104
Accessory:
SM-Socket IP44 for 92751 92386
Wire basket BSK 92199
Wall bracket for remote control as replacement 92100
12. Article / Part nr. / Accessory
In case the sensing area of the LUXOMAT® PD4-M-TRIO2DALI/DSI-1C is too large or areas are being covered that
should not be monitored, the range can be reduced or
limited through use of the enclosed masking clips (e).
11. Exclude sources of interference
10. Range of Coverage
8. Manual Dimming
(for IR-PD4-TRIO-DALI functions see page 1)
You can dim manually by pressing the pushbutton for a long
time (> 2 sec.). When the button is released, the current dimming value is retained. Upon renewed dimming, the dimming
direction is reversed.
7. Fully/Semi automatic mode
(see DIP switch functions and IR-PD4-TRIO-DALI on page 1)
Automatic operation
In this operating mode, the lighting switches
automatically on and off for increased comfort,
depending on presence and brightness.
Semiautomatic operation
In this operating condition, in order to gain
increased savings, the lighting is energized only after
being manually switched on. Switch-off takes place
automatically.
The semiautomatic mode basically behaves like the fully
automatic one. However, the difference is that switchingon must always be carried out manually!
As many (closer-contact) buttons as desired can be wired
in parallel on the “S” button input (ON/ OFF DIM).
9. Manual Switching
You can switch the lighting on and off manually by
pressing the pushbutton for a short time. It will stay
on or off as long as people are detected plus the
congured follow up time.
16. DIP switch functions
PD4-M-TRIO-2DALI/DSI-1C
1
2
Walking across
Walking towards
Seated
quer zum Melder gehen
frontal zum Melder gehen
sitzende Tätigkeit
DIP
switch
OFF ON
1 (A) Fully automatic channel
DA 1/2 + HVAC/Light
Semi-automatic channel
DA 1/2 + HVAC/Light
2 (B) For mains ON /
light ON
For mains ON /
light OFF
3 (C) Standard operation RESET
17. LED function displays
18. Fault-finding
Permanently flashing
Check whether DIP3 switch (RESET)
is set to “ON”
Reset to “OFF” if necessary
DIP
ON
OFF
1 2 3
LED Colour Function Display
6 red Motion indicator Lights up for motion
detection
5 green Light status indica-
tor DA 1
flashes twice per sec.:
-
bright enough (light
OFF)/ too bright (light
ON)
flashes once per sec.:
- Delay time active
4 white HA/VA Channel
1C
lights when semi-automatic
3 white HA/VA DA 1/2
lights when semi-automatic
2 green Light status indica-
tor DA 2
flashes twice per sec.:
-
bright enough (light
OFF)/ too bright (light
ON)
flashes once per sec.:
- Delay time active
1 red OFF-function lights when the feature
is activated, ie in the
initialization phase the
light is off
all LEDs Acknowledgement flashes once per sec.:
- correct input
flashes twice per sec.:
- incorrect input
flashes three times / once
per sec.:
- Reset when locked
flashes three times / twice
per sec.:
- Double locked
light up for 2sec.:
- HVAC mode Channel
1C active
light up for 0,5sec.:
- Light control mode
Channel 1C active
all LEDs Status flashes shortly once per
sec.:
- Detector is double locked
MAN 7603 – 270213–2
WE RECOMMEND THAT BEFORE DIMMING OF THE CONNECTED LIGHTS A
100 h BURN IN (T5 TUBES OR 80 HOURS FOR T8 TUBES) FUNCTION TAKES
PLACE. THIS CAN BE IGNORED BY USING THE REMOTE CONTROL TO DEACTI
VATE. THE LIFESPAN OF THE LAMPS CAN BE REDUCED IF THE BURN IN DOES
NOT TAKE PLACE.
13. Wiring diagram – Standard mode with Master-TRIO-2DALI/DSI-1C occupancy detectors
optional
T1&2 = NO button for semi-automatic mode
Slave for enlargement of detection area
MASTER SLAVE
E1 DALI
N
E2 DALI
L
N
DA
DA
HVAC/LIGHT
L
N
RNO NO
S
S
+-+
DA1/2
HVAC/
Light
HVAC/
Light
DA1 DA2
NLR
LN
–
DA2+DA1
+
S
LiGht
NONO
PD4-M-TRIO-2DALI/DSI-1C-FC
PD4-M-TRIO-2DALI/DSI-1C-SM
L
N
R
Slave
T1T2
DA –
DA +
DA –
DA +
L
N
R
Slave
T2
DA –
DA +
DA –
DA +
NO
L
NO
L N N S S
R
T1
S
hVAC
R
–
DA1+DA2
+
1
2
12 m
12 m
8 m
6.40 m
24 m
360°
2.50 m
e