A circular opening of diameter 100mm must be produced in the ceiling.
Having connected up the cables in accor dance with regulations, the detector is inserted into the opening as shown and fixed into position with the retaining bracket using screws.
A Light sensor 1 | B Light sensor 2 1 LED red OFF function 2 LED green too bright/too dark CDS 1 3 LED white semi-automatic DA 1/2 4 LED white semi-automatic Channel 3 5 LED green too bright/too dark CDS 2 6 LED red motion indicator/walking test
2a. Installation of the LUXOMAT®
PD4-M-TRIO-2DALI/DSI-1C-SM
2b. Installation of the LUXOMAT®
PD4-M-TRIO-2DALI/DSI-1C-FC
3. Hardware configuration
Position of light sensors and LEDs
The detector must be in stalled on a solid and level surface. The circular cover ring must be removed prior to assembly. To do this, twist the lens (C) anti­clockwise through approximately 5° and lift off.
Having connected up the wires in accordance with regulations, secure the detector with 2 screws. After installation replace the lens and lock (turn clockwise). Mains to be connected.
4. Putting into operation of the remote control (optional)
Remote control LUXOMAT® IR-PD4-TRIO-DALI
1. Check Battery:
open battery compartment by pressing the plastic springs together and remov­ing the battery-holder.
Caution: Settings with remote control supersede the settings by courtesy of potentiom­eters.
LUXOMAT
®
PD4-M-TRIO-2DALI/DSI-1C
1. Mounting preparations
Work on the 230V mains supply may only be carried out by quali­fied professionals or by instructed persons under the direction and supervision of qualified skilled elec­trical personnel in accordance with electrotechnical regulations.
Disconnect supply before installing!
When in Master/ Slave mode of operation, the Master-appliance must always be installed at the location where there is least daylight.
Option:
Wall bracket for remote control
IR-PD4-TRIO-DALI
A4 5 1 3 2 6
B
GB
6. Putting into operation / Settings
Self test cycle
After an initial 60-second self-test cycle, the LUXOMAT® PD4-M-TRIO-2DALI/DSI-1C is ready for operation.
Potentiometer 3: Follow-up time for light control
The time can be set infinitely variably at between 1 and 60 minutes. The time-setting is valid for all three channels of the PD4-M-TRIO-2DALI/DSI-1C.
Symbol TEST: Test mode (Every movement switches on the light for a period of 2 second, switching it off for a period of 2 seconds after that regardless of the level of brightness.)
Potentiometer 2: Twilight-switch for light control
The switch-on value for the light can be set at between 40 and 1200Lux. Using the rotary control, the luminance set points can be set as desired.
Symbol : Night-time operation | Symbol : Daytime/ Night-time operation
Potentiometer 1: Orientation lighting
This rotary controller serves to determine the working time of the orientation lighting (fixed to 20%).
“ON” for permanent orientation lighting. “OFF” for deactiviation of orientation lighting.
Pulse spacing PD-Slave
2 or 9 seconds can be set for the pause between 2 pulses sent to the master. The setting can be made with activated ( ) or deactivated ( ) LED indicator.
For devices with a separate slave input, 2sec. can be set.
45
30
15
5
1
TEST
60
1200
600
200
40
60
5
15
30
45
ON
OFF
80 - 90 mm
100 mm
open
close
C
Explanation of the key functions
6 5
4 A 3 2 1
B
DIP 1 HA / A DIP 2 Ini OFF/ON
Lamps at start-up OFF/ON DIP 3 RESET
5. Position of potentiometer and DIP switch
SM
FC
3
1
2
DIP
123
DIP 321
123
SM FC
9s 2s
LED ON
LED OFF
DA 1/2 ON/OFF when locked (=> see page 2, point 9)
Dimming
when locked
=> (
see page 2, point
8)
Activate test mode – when locked Deactivate test mode: press Reset
Resetting when locked
The lighting relay is switched off, i.e. opened and the follow-up times reset.
Permanent protection against sabotage
This function blocks the unit permanently (green LED is illuminated). This operating mode can only be activated during the period of 5 seconds after pressing the “lock“ button. This status will only permit actuating the function “Light on/Light off”. The procedure for leaving this mode is as follows:
reset the hardware
using DIP switch 3 or switch the supply voltage as follows:
Dimming in opened state The following approach will prove useful when setting a command value (example workplace): Place a luxmeter flat on the desk, then, using the remote control IR-PD4-TRIO-DALI, adjust the light up or down by pressing the keys “max“ or “min“ until the desired command value which best suits your requirements has been reached.
Saving of the through adjusted luminance set point
100 h function in opened state
to extend the life span – sums up automatically the burning time of 100% luminosity at the beginning up to 100 hours – only then can lights dim
Orientation lighting and its follow-up time ON/OFF Note: During the orientation light phase, the constant light regulation is
also active: if there is sufficient brightness, dimming occurs < 2V and, if applicable, the lighting is switched off.
Orientation lighting – Adjustment ot the light intensity
The orientation lighting is adjustable in a span from 10 to 30% of the nominal light. Standard adjustment is 20%.
t < 5 sec.
100
h
Settings by remote control
Unlocking device


60


10
to
or
Dimming of the luminance set point (only for channel 1 and 2)
to
60
min
1
min
Follow-up time light
optionaloptionaloptionaloptional optional
100 h function => (see page 2, point 19)
Orientation lighting
ON = all LEDs ashes 2x OFF = all LEDs ashes 1x
Follow-up time orientation lighting
Orientation lighting 10 – 30% of nominal light
Luminance set point for constant light regulation
to
or
Fully automatic/semi automatic mode
(only DA1/2) => (see page 2, point 10)
LED display ON/OFF
Sun button – preselected light value (Daylight operation)
1000100
or
Saving of the dimmed luminance set point
Resetting when open:
All values which have been pro­grammed us­ing the remote control are deleted, and those values which have been set by potentiometer are activated.
Locking device – Exit programming mode
Permanent protection against sabotage
LED ashes
or
t < 5 sec.
DA 1/2 ON/OFF
optional
Switching between DALI and DSI (factory settings DALI)
optional
Switching
Channel 1C between HVAC-
and light control (
factory settings
light)
ON
230 V
1sec. 1sec.30 sec. - 60sec.
OFF
15.
Technical data
PD4-M-TRIO-2DALI/DSI-1C
Sensor and power supply in one case
Power supply: 230V~ ±10 % Power consumption: < 1W Ambient temperature: -25°C to +50°C Degree of protection/class: IP20 / II Settings: control dial, DIP switch and
remote control
Light values - Remote control:
100 - 1000Lux
Extension of the detection area: with Slaves
Area of coverage: circular 360° Range of coverage Ø H 2.50m / T= 18°C:
seated 6.40m / tangential 24m / radial 8m
Recommended height for mounting: 2 - 3 m Light measurement: mixed light, daylight + artificial
light, suitably for constant light control
Light values - Potentiometer:
10 - 2000Lux
• Dali output DA 1/2 for light switching, light-controlled Max. numbers of connected EB‘s: each 25 for DA1 and DA2
Channel 1C (-1C)
for light switching (panel lighting
), light- or motion-controlled or HVAC circuit, only motion-controlled Type of contact: NOC/with pretravel tungsten contact Contact load
: 3000 W, 230V~, 16A cos ϕ=1 /
1500VA cos ϕ= 0,5, μ-Contact
Time-settings Channel 1C: 1 - 60 min. / Test Dimensions H x Ø [mm] SM FC 124 x85 100 x 117
Visible portion when built into ceiling: H 37 x Ø 117mm
Technical data PD4-Slave
Power supply: 230 V~ ±10% Impulse output: Optocoupler max. 2W Impulse duration: 2sec. or 9sec. Dimensions: SM FC
76 x 101 97 x 103 Visible portion when built into ceiling: 34x10mm
Declaration of Conformity: The product complies with
the low voltage recommendation 2006/95/EC and the EMV recommendation 2004/108/EC.
14. Connections
Type SM FC FM
PD4-M-TRIO-2DALI/DSI-1C (Master)
92751 92756 –
PD4-S (Slave) 92142 92254 9 2163
LUXOMAT
®
Remote control:
IR-PD4-TRIO-DALI (incl. wall bracket) 92104
Accessory:
SM-Socket IP44 for 92751 92386 Wire basket BSK 92199 Wall bracket for remote control as replacement 92100
12. Article / Part nr. / Accessory
In case the sensing area of the LUXOMAT® PD4-M-TRIO­2DALI/DSI-1C is too large or areas are being covered that should not be monitored, the range can be reduced or limited through use of the enclosed masking clips (e).
11. Exclude sources of interference
10. Range of Coverage
8. Manual Dimming
(for IR-PD4-TRIO-DALI functions see page 1)
You can dim manually by pressing the pushbutton for a long time (> 2 sec.). When the button is released, the current dim­ming value is retained. Upon renewed dimming, the dimming direction is reversed.
7. Fully/Semi automatic mode
(see DIP switch functions and IR-PD4-TRIO-DALI on page 1)
Automatic operation
In this operating mode, the lighting switches automatically on and off for increased comfort, depending on presence and brightness.
Semiautomatic operation
In this operating condition, in order to gain increased savings, the lighting is energized only after being manually switched on. Switch-off takes place automatically.
The semiautomatic mode basically behaves like the fully automatic one. However, the difference is that switching­on must always be carried out manually!
As many (closer-contact) buttons as desired can be wired in parallel on the “S” button input (ON/ OFF DIM).
9. Manual Switching
You can switch the lighting on and off manually by pressing the pushbutton for a short time. It will stay on or off as long as people are detected plus the
congured follow up time.
16. DIP switch functions
PD4-M-TRIO-2DALI/DSI-1C
1
2
Walking across Walking towards Seated
quer zum Melder gehen frontal zum Melder gehen sitzende Tätigkeit
DIP switch
OFF ON
1 (A) Fully automatic channel
DA 1/2 + HVAC/Light
Semi-automatic channel DA 1/2 + HVAC/Light
2 (B) For mains ON /
light ON
For mains ON / light OFF
3 (C) Standard operation RESET
17. LED function displays
18. Fault-finding
Permanently flashing
Check whether DIP3 switch (RESET) is set to “ON”
Reset to “OFF” if necessary
DIP
ON
OFF
1 2 3
LED Colour Function Display
6 red Motion indicator Lights up for motion
detection
5 green Light status indica-
tor DA 1
flashes twice per sec.:
-
bright enough (light OFF)/ too bright (light ON)
flashes once per sec.:
- Delay time active
4 white HA/VA Channel
1C
lights when semi-automatic
3 white HA/VA DA 1/2
lights when semi-automatic
2 green Light status indica-
tor DA 2
flashes twice per sec.:
-
bright enough (light OFF)/ too bright (light ON)
flashes once per sec.:
- Delay time active
1 red OFF-function lights when the feature
is activated, ie in the initialization phase the light is off
all LEDs Acknowledgement flashes once per sec.:
- correct input
flashes twice per sec.:
- incorrect input
flashes three times / once per sec.:
- Reset when locked
flashes three times / twice per sec.:
- Double locked
light up for 2sec.:
- HVAC mode Channel 1C active
light up for 0,5sec.:
- Light control mode Channel 1C active
all LEDs Status flashes shortly once per
sec.:
- Detector is double locked
MAN 7603 – 270213–2
WE RECOMMEND THAT BEFORE DIMMING OF THE CONNECTED LIGHTS A 100 h BURN IN (T5 TUBES OR 80 HOURS FOR T8 TUBES) FUNCTION TAKES PLACE. THIS CAN BE IGNORED BY USING THE REMOTE CONTROL TO DEACTI
­VATE. THE LIFESPAN OF THE LAMPS CAN BE REDUCED IF THE BURN IN DOES NOT TAKE PLACE.
13. Wiring diagram – Standard mode with Master-TRIO-2DALI/DSI-1C occupancy detectors
optional
T1&2 = NO button for semi-automatic mode Slave for enlargement of detection area
MASTER SLAVE
E1 DALI
L
N DA DA
L
N
E2 DALI
L
N DA DA
HVAC/LIGHT
L
N
RNO NO
S
S
+-+
DA1/2
HVAC/ Light
HVAC/
Light
DA1 DA2
NLR
T2
T1
LN
DA2+DA1
+
S
LiGht
NONO
PD4-M-TRIO-2DALI/DSI-1C-FC
PD4-M-TRIO-2DALI/DSI-1C-SM
L
N
R
Slave
T1T2
DA – DA +
DA – DA +
L
N
R
Slave
T2
DA – DA +
DA – DA +
NO
L
NO
L N N S S
R
T1
S
hVAC
R
DA1+DA2
+
1
2
12 m
12 m
8 m
6.40 m
24 m
360°
2.50 m
e
Loading...