Luxaire THRD18S41S1, THRD24S41S1, THRD30S41S1, THRD36S41S1, THRD42S41S1 Technical Manual

...
TECHNICAL GUIDE
COMPETITOR SERIES
SPLIT-SYSTEM HEAT PUMPS
13 SEER – R-410A MODELS:
THRD18 THRU 60 (1.5 THRU 5 NOMINAL TONS, 1 PHASE)
Due to continuous product improvement, specif ic a t io ns are subject to change without notice.
Visit us on the web at www.york.com Additional rating information can be found at
www.ahridirectory.org
LISTED
ISO 9001
Certified Quality
Management System
445073-LTG-A-0109
DESCRIPTION
The heat pump condensing unit is the outdoor part of a versatile system of heating and air conditioning. It is designed to be cus­tom-matched with one of UPG’s complete line of evaporator sections, with each serving a specific function. Matching Air Handlers are available for upflow, downflow, or horizontal appli­cations to provide a complete system. Electric Heaters are available, if required. Add-on coils are available for use with upflow, downflow, or horizontal furnaces and air handlers.
WARRANTY
Single Phase Units:
5-year limited parts warranty. 5-year limited compressor warranty.
FEATURES
QUALITY CONDENSER COILS - The coil is constructed of copper tubing and enhanced aluminum fins for increased efficiency and corrosion protection.
PROTECTED COMPRESSOR - The compressor is inter­nally protected against high pressure, temperature, and externally by a factory installed high pressure switch. This is accomplished by the simultaneous operation of high pres­sure relief valve and a temperature sensor which protects the compressor if undesirable operating conditions occur. A liq­uid line filter-drier further protects the compressor.
DURABLE FINISH - The cabinet is made of pre-painted steel. The pre-treated galvanized steel provides a better paint to steel bond, which resists corrosion and rust creep. Special primer formulas and matted-textured finish insure less fading when exposed to sunlight.
LOWER INSTALLED COST - Installation time and costs are reduced by easy power and control wiring connections. Available in sweat connect models only. The unit contains enough refrigerant for matching indoor coils and 15 feet of interconnecting piping. The small base dimension means less space is required on the ground or roof.
TOP DISCHARGE - The warm air from the top mounted fan is blown up away from the structure and any landscaping. This allows compact location on multi-unit applications.
LOW OPERATING SOUND LEVEL - The upward air flow carries the normal operating noise away from the living area. The rigid top panel effectively isolates any motor sound. Iso­lator mounted compressor and the rippled fins of the con­denser coil muffle the normal fan motor and compressor operating sounds.
LOW MAINTENANCE - Long life permanently lubricated motor-bearings need no annual servicing.
EASY SERVICE ACCESS - Fully exposed refrigerant con­nections, and a single panel covering the electrical controls make for easy servicing of the unit.
SECURED SERVICE VALVES - Secured re-usable service valves are provided on both the liquid and vapor sweat con­nections for ease of evacuating and charging.
U.L. and C.U.L. listed - approved for outdoor application.
Agency Listed - U.L. and C.U.L. listed - approved for out­door application. The unit is certified in accordance with the Unitary Small Equipment cerification program, which is based on ARI Standard 210/240.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
445073-LTG-A-0109
B
C
A
Physical and Electrical Data
MODEL
THRD18
S41S1
THRD24
S41S1
THRD30
S41S1
THRD36
S41S1
THRD42
S41S1
THRD48
S41S1
THRD60
S41S1
Unit Supply Voltage 208-230V, 1 60Hz Normal Voltage Range
1
187 to 252
Minimum Circuit Ampacity 11.2 12.4 14.9 19.9 21.1 23.0 35.4 Max. Overcurrent Device Amps Min. Overcurrent Device Amps
2
3
15 20 25 30 35 40 60 15 15 15 20 25 25 40
Compressor Type Recip Recip Recip Recip Recip Recip Scroll Compressor Amps
Rated Load 8.3 9.3 11.3 14.7 15.7 17.2 27.5
Locked Rotor434354748884135 Crankcase Heater Yes Yes Yes Yes Yes Yes No Fan Motor Amps Rated Load 0.8 0.8 0.8 1.5 1.5 1.5 1.5 Fan Diameter Inches 18 18 22 24 24 24 24
Rated HP 1/8 1/8 1/8 1/4 1/4 1/4 1/4 Fan Motor
Nominal RPM 1075 1075 1075 850 850 850 850
Nominal CFM 2000 2000 2500 3500 3500 3900 23.58
Face Area Sq. Ft. 9.3 9.3 12.8 15.7 15.7 23.6 23.6 Coil
Rows Deep 1111112
Fin / Inches 18 18 18 22 22 22 18 Liquid Line Set OD (Field Installed) 3/8 3/8 3/8 3/8 3/8 3/8 3/8 Vapor Line Set OD (Field Installed) 3/4 3/4 3/4 3/4 7/8 7/8 7/8
Unit Charge (Lbs. - Oz.)
4
5 - 6 5 - 8 7 - 8 7 - 8 8 - 8 9 - 1 13 - 1
Charge Per Foot, Oz. 0.62 0.62 0.62 0.62 0.67 0.67 0.67 Operating Weight Lbs. 145 145 176 193 198 248 290
1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
2 Johnson Controls Unitary Products
All dimensions are in inches. They are subject to change with­out notice. Certified dimensions will be provided upon request.
Unit
Model
18 28
Dimensions
(Inches)
1
A
B C Liquid Vapor
23-1/2 23-1/2 24 28 23-1/2 23-1/2 30 28 29 29 36 28 34 34 42 28 34 34
60 40 34 34
1. Including Fan Guard.
Refrigerant Connection
Service Valve Size
3/4”
3/8”
7/8”48 40 34 34
445073-LTG-A-0109
Additional R-410A Charge / Orifice Size for Various Matched Systems
Outdoor Unit THRD18S41S1 THRD24S41S1 THRD30S41S1 THRD36S41S1 THRD42S41S1 THRD48S41S1 THRD60S41S1
1,2
Required Orifice or TXV Factory Charge, lbs-oz 5 - 6 5 - 8 7 - 8 7 - 8 8 - 8 9 - 1 13 - 1
.049/902/4F1 .055/903/4G1 .060/903/4G1 .067/904/4H1 .075/905/4J1 .078,.081/906/4K1 906/4K1
Indoor Coil
3,4
Additional Charge, Oz
FC/MC/PC/UC18A3X .049 + 0 – FC/MC/PC/UC18B3X .049 + 0 – FC/MC/PC/UC24A3X .049 + 5 .055 + 3 – FC/MC/PC/UC24B3X .049 + 5 .055 + 3 – FC/MC/PC/UC30A3X .049 + 5 .055 + 3 – FC/MC/PC/UC30B3X .049 + 5 .055 + 3 – FC/MC/PC/UC32A3X .060 + 0 – FC/MC/PC/UC35B3X .060 + 0 – FC/MC/PC/UC35C3X .060 + 0 – FC/MC/PC/UC37A3X .060 + 4 – FC/MC/PC/UC43B3X .060 + 4 – FC/MC/PC/UC43C3X .060 + 4 .067 + 6 – FC/MC/PC/UC48C3X––––.075 + 0 – FC/MC/PC/UC48D3X––––.075 + 0 – FC/PC/UC60C3X ––––.075 + 2 – FC/MC/PC/UC60D3X––––.075 + 2 .081 + 0 – FC/PC62D3X –––––.078 + 8TXV + 0 HC30A3X .049 + 11 .055 + 9 – HC42C3X .060 + 4 .067 + 6 – HC60D3X ––––.075 + 2 – AV24B2A .049 + 2 .055 + 0 – AV36C2A .060 + 4 .067 + 6 – AV48D2C ––––.075 + 2 .081 + 0 – AV60D2C ––––.075 + 2 .081 + 0 – F6FP018H06 .049 + 0 – F6FP024H06 .049 + 2 .055 + 0 – F6FP030H06 .060 + 0 – F6FP036H06 .060 + 0 .067 + 0 – F6FP042H06 ––––.075 + 0 – F6FP048H06 ––––.075 + 2 .081 + 0 – F6FP060H06 –––––.078 + 8TXV + 0
FOOTNOTES:
1. For applications requiring a TXV use the correct 1TVM* series kit listed above.
2. Approved orifice shipped with outdoor unit.
3. Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.
4. PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.
PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of interconnecting line tubing.
2. Verify the TXV or orifice and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in Physical and Electrical Data Table.
4. For TXV match charge weight needs to be weighed in for specififc coil match and lineset length.
5. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evaporator + adder for line set.
Johnson Controls Unitary Products 3
445073-LTG-A-0109
COOLING CAPACITY - With Air Handler Coils
UNIT
MODEL
AIR HANDLER
MODEL W
COIL
MODEL
1
RATED
CFM
TOTAL SENS.
13 SEER HP WITH MV - VARIABLE SPEED
THRD18S41S1 MV12B 17 FC/MC18B 655 18.0 13.5 13.00 11.20 THRD18S41S1 MV12B 17 FC/MC24B 655 18.0 13.5 13.00 11.45 THRD18S41S1 MV12B 17 FC/MC30B 655 18.0 13.5 13.00 11.45 THRD24S41S1 MV12B 17 FC/MC24B 770 23.0 17.5 13.00 11.20 THRD24S41S1 MV12B 17 FC/MC30B 770 23.0 17.5 13.00 11.20 THRD30S41S1 MV16C 21 FC/MC35C 1095 30.0 21.7 13.00 11.50 THRD30S41S1 MV12B 17 FC/MC43B 1050 30.0 21.7 13.00 11.65 THRD30S41S1 MV16C 21 FC/MC43C 1095 30.0 21.7 13.00 11.70 THRD36S41S1 MV16C 21 FC/MC35C 1215 34.2 25.0 13.00 11.20 THRD36S41S1 MV16C 21 FC/MC43C 1215 35.0 25.6 13.00 11.60 THRD42S41S1 MV16C 21 FC/MC48C 1400 40.5 31.6 13.00 11.75 THRD42S41S1 MV20D 24 FC/MC48D 1430 40.5 31.6 13.00 11.80 THRD42S41S1 MV16C 21 FC/MC60C 1400 40.5 31.1 13.00 11.85 THRD42S41S1 MV20D 24 FC/MC60D 1430 40.5 31.6 13.00 11.90 THRD48S41S1 MV20D 24 FC/MC60D 1595 47.0 35.3 13.00 11.80 THRD48S41S1 MV20D 24 FC/MC62D 1595 47.5 35.5 13.00 11.80 THRD60S41S1 MV20D 24 FC/MC62D 1800 54.5 43.0 13.00 11.20
13 SEER HP WITH AV - VARIABLE SPEED
THRD18S41S1 AV*24 17 595 18.0 13.5 13.00 11.20 THRD24S41S1 AV*24 17 815 23.6 18.0 13.00 11.30 THRD30S41S1 AV*36 21 1005 30.0 21.7 13.00 11.45 THRD36S41S1 AV*36 21 1230 35.0 25.6 13.00 11.60 THRD42S41S1 AV*48 24 1440 40.5 31.6 13.00 11.80 THRD42S41S1 AV*60 24 1400 40.5 31.6 13.00 11.75 THRD48S41S1 AV*48 24 1605 47.0 35.3 13.00 11.70 THRD48S41S1 AV*60 24 1600 47.0 35.3 13.00 11.65
13 SEER HP WITH F6FP
THRD18S41S1 F6FP18 17 600 18.0 13.5 13.00 11.20 THRD18S41S1 F6FP24 17 600 18.0 13.5 13.00 11.20 THRD24S41S1 F6FP24 17 800 23.6 18.0 13.00 11.30 THRD30S41S1 F6FP30 21 990 30.0 21.7 13.00 11.45 THRD30S41S1 F6FP36 21 1000 30.0 21.7 13.00 11.45 THRD36S41S1 F6FP36 21 1190 34.2 25.0 13.00 11.20 THRD42S41S1 F6FP42 24 1430 40.5 31.6 13.00 11.80 THRD42S41S1 F6FP48 24 1400 40.5 31.6 13.00 11.80 THRD48S41S1 F6FP48 24 1600 47.0 35.3 13.00 11.70 THRD48S41S1 F6FP60 24 1600 47.5 35.5 13.00 11.80 THRD60S41S1 F6FP60 24 1800 54.5 43.0 13.00 11.20
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210. Cooling MBH based on 8°F entering air temperature, 50% RH, and rated air flow. EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions. SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period.
1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number. — = Not applicable.
COOLING
NET MBH
SEER EER
COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils
UNIT
MODEL
FURNACE**
CFM RANGE
(Min.-max.)
COIL
W
MODEL
RATED
CFM
TOTAL SENS.
THRD60S41S1 1600 - 2000 21,24 FC/MC62 1850 54.0 42.5 13.00 11.00
1. Requires a 2FD06700224 Blower Time Delay unless a standard furnace is equipped with one. ** Refer to Quick Selection Chart for specific furnace match-up.
COOLING
NET MBH
SEER
1
EER
4 Johnson Controls Unitary Products
COOLING CAPACITY - With Variable Speed Furnaces
UNIT
MODEL
THRD18S41S1
THRD24S41S1
THRD30S41S1
THRD36S41S1
THRD42S41S1
THRD48S41S1
THRD60S41S1
1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.
2. Variable speed furnaces have B.O.D (Blower on Delay) standard.
VARIABLE SPEED FURNACE MODEL
13 SEER HP WITH VARIABLE SPEED FURNACES
L*(8,L)C*A12 FC/MC/PC/UC24A 14 600 18.0 13.5 13.00 11.00 L*(8,L)C*B12 FC/MC/PC/UC24B 17 580 18.0 13.5 13.00 11.00
L*9C*B12 FC/MC/PC/UC24B 17 600 18.0 13.5 13.00 11.00 L*(8,L)C*A12 FC/MC/PC/UC30A 14 600 18.0 13.5 13.00 11.00 L*(8,L)C*B12 FC/MC/PC/UC30B 17 580 18.0 13.5 13.00 11.00
L*9C*B12 FC/MC/PC/UC30B 17 600 18.0 13.5 13.00 11.00 L*(8,L)C*A12 HC30 14 600 18.0 13.5 13.00 11.00 L*(8,L)C*A12 FC/MC/PC/UC24A 14 815 23.6 18.0 13.00 11.00 L*(8,L)C*B12 FC/MC/PC/UC24B 17 775 23.6 18.0 13.00 11.10
L*9C*B12 FC/MC/PC/UC24B 17 760 23.6 18.0 13.00 11.00 L*(8,L)C*A12 FC/MC/PC/UC30A 14 815 23.6 18.0 13.00 11.00 L*(8,L)C*B12 FC/MC/PC/UC30B 17 775 23.6 18.0 13.00 11.10
L*9C*B12 FC/MC/PC/UC30B 17 760 23.6 18.0 13.00 11.00 L*(8,L)C*A12 HC30 14 815 23.6 18.0 13.00 11.00 L*(8,L)C*B12 FC/MC/PC/UC43B 17 960 30.0 21.7 13.00 11.25
L*9C*B12 FC/MC/PC/UC43B 17 1000 30.0 21.7 13.00 11.15 L*(8,L)C*C16 FC/MC/PC/UC43C 21 1000 30.0 21.7 13.00 11.40
L*9C*C16 FC/MC/PC/UC43C 21 995 30.0 21.7 13.00 11.25 L*9V*C16 FC/MC/PC/UC43C 21 995 30.0 21.7 13.00 11.25
L*(8,L)C*C16 HC42 21 1000 30.0 21.7 13.00 11.40
L*9C*C16 HC42 21 995 30.0 21.7 13.00 11.25
L*(8,L)C*C16 FC/MC/PC/UC43C 21 1200 34.2 25.0 13.00 11.00
L*9C*C16 FC/MC/PC/UC43C 21 1175 34.2 25.0 13.00 11.00
L*(8,L)C*C20 FC/MC/PC/UC43C 21 1270 34.2 25.0 13.00 11.00
L*9C*C20 FC/MC/PC/UC43C 21 1270 34.2 25.0 13.00 11.00
L*(8,L)C*C16 HC42 21 1200 34.2 25.0 13.00 11.00
L*9C*C16 HC42 21 1175 34.2 25.0 13.00 11.00
L*(8,L)C*C20 HC42 21 1270 34.2 25.0 13.00 11.00
L*9C*C20 HC42 21 1270 34.2 25.0 13.00 11.00
L*(8,L)C*C16 FC/MC/PC/UC48C 21 1430 40.5 31.6 13.00 11.50
L*9C*C16 FC/MC/PC/UC48C 21 1385 40.5 31.6 13.00 11.30 L*9V*C16 FC/MC/PC/UC48C 21 1385 40.5 31.6 13.00 11.30
L*(8,L)C*C20 FC/MC/PC/UC48C 21 1370 40.5 31.6 13.00 11.60
L*9C*C20 FC/MC/PC/UC48C 21 1445 40.5 31.6 13.00 11.40 L*9C*D20 FC/MC/PC/UC48D 24 1435 40.5 31.6 13.00 11.45
L*(8,L)C*C16 FC/PC/UC60C 21 1430 40.5 31.6 13.00 11.55
L*9C*C16 FC/PC/UC60C 21 1385 40.5 31.6 13.00 11.35
L*(8,L)C*C20 FC/PC/UC60C 21 1370 40.5 31.6 13.00 11.65
L*9C*C20 FC/PC/UC60C 21 1445 40.5 31.6 13.00 11.50 L*9C*D20 FC/MC/PC/UC60D 24 1435 40.5 31.6 13.00 11.60 L*9C*D20 HC60 24 1435 40.5 31.6 13.00 11.60
L*(8,L)C*C20 FC/MC62D 24 1670 47.0 35.3 13.00 11.60
L*9C*C20 FC/MC62D 24 1605 47.0 35.3 13.00 11.50 L*9C*D20 FC/MC62D 24 1595 47.0 35.3 13.00 11.40
L*(8,L)C*C20 FC/MC62D 24 1750 54.0 42.5 13.00 11.00
L*9C*C20 FC/MC62D 24 1650 53.0 41.0 13.00 11.00 L*9C*D20 FC/MC62D 24 1615 53.5 41.5 13.00 11.00
COIL
MODEL
W
1
RATED
CFM
TOTAL SENS.
2
COOLING
Net MBH
445073-LTG-A-0109
SEER EER
Johnson Controls Unitary Products 5
445073-LTG-A-0109
HEATING PERFORMANCE - With Air Handler
UNIT
MODEL
THRD18S41S1 MV12B FC/MC18B 17.6 3.36 1.43 9.6 2.28 1.14 7.70 THRD18S41S1 MV12B FC/MC24B 17.6 3.36 1.43 9.6 2.28 1.14 7.70 THRD18S41S1 MV12B FC/MC30B 17.6 3.36 1.43 9.6 2.28 1.14 7.70 THRD24S41S1 MV12B FC/MC24B 23.0 3.74 1.66 13.4 2.62 1.32 8.20 THRD24S41S1 MV12B FC/MC30B 23.0 3.74 1.66 13.4 2.62 1.32 8.20 THRD30S41S1 MV16C FC/MC35C 27.4 3.58 2.05 14.0 2.46 1.56 8.20 THRD30S41S1 MV12B FC/MC43B 28.0 3.70 2.02 14.0 2.46 1.56 8.20 THRD30S41S1 MV16C FC/MC43C 28.0 3.70 2.02 14.0 2.46 1.56 8.20 THRD36S41S1 MV16C FC/MC43C 33.0 3.70 2.53 17.9 2.38 2.01 8.00 THRD36S41S1 MV16C FC/MC48C 33.0 3.70 2.53 17.9 2.38 2.01 8.00 THRD42S41S1 MV16C FC/MC48C 40.0 3.95 2.64 23.4 2.76 2.17 8.75 THRD42S41S1 MV20D FC/MC48D 40.0 3.95 2.64 23.4 2.76 2.17 8.75 THRD42S41S1 MV16C FC/MC60C 40.5 4.00 2.64 23.4 2.76 2.17 8.75 THRD42S41S1 MV20D FC/MC60D 40.5 4.00 2.64 23.4 2.76 2.17 8.75 THRD48S41S1 MV20D FC/MC60D 46.0 4.00 3.10 27.0 2.78 1.82 8.20 THRD48S41S1 MV20D FC/MC62D 46.0 4.00 3.10 27.0 2.78 1.82 8.20 THRD60S41S1 MV20D FC/MC62D 56.5 3.54 4.04 35.2 2.46 3.55 8.00
THRD18S41S1 AV*24 17.6 3.36 1.43 9.6 2.28 1.14 7.70 THRD24S41S1 AV*24 23.03.741.6613.42.621.328.20 THRD30S41S1 AV*36 27.43.582.0514.02.461.568.20 THRD36S41S1 AV*36 32.03.502.5317.92.382.018.00 THRD42S41S1 AV*48 40.53.952.6423.42.762.178.75 THRD42S41S1 AV*60 40.53.952.6423.42.762.178.75 THRD48S41S1 AV*48 46.04.003.1027.02.781.828.20 THRD48S41S1 AV*60 46.04.003.1027.02.781.828.20
THRD18S41S1 F6FP18 17.6 3.36 1.43 9.6 2.28 1.14 7.70 THRD18S41S1 F6FP24 17.6 3.36 1.43 9.6 2.28 1.14 7.70 THRD24S41S1 F6FP24 23.03.741.6613.42.621.328.20 THRD30S41S1 F6FP30 27.43.582.0514.02.461.568.20 THRD30S41S1 F6FP36 27.43.582.0514.02.461.568.20 THRD36S41S1 F6FP36 32.03.502.5317.92.382.018.00 THRD42S41S1 F6FP42 40.03.952.6423.42.762.178.75 THRD42S41S1 F6FP48 40.03.952.6423.42.762.178.75 THRD48S41S1 F6FP48 46.04.003.1027.02.781.828.20 THRD48S41S1 F6FP60 46.04.003.1027.02.781.828.20 THRD60S41S1 F6FP60 56.53.544.0435.22.463.558.00
1. Rated CFM same as for cooling.
2. Heating MBH based on ARI standards of 70° DB entering indoor air, 72% RH outdoor air with 25 feet of interconnecting piping and no supplemental electric heat operation.
CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by the total electric power input during the same period. — = Not Applicable.
AIR
HANDLER
13 SEER HP WITH MV - VARIABLE SPEED
13 SEER HP WITH AV - VARIABLE SPEED
1
COIL
MODEL
13 SEER HP WITH F6FP
MBH COP KW MBH COP KW STD
47F17FHSPF
ARI HEATING
2
6 Johnson Controls Unitary Products
445073-LTG-A-0109
HEATING PERFORMANCE - Upflow, Downflow, and Horizontal Furnaces and Coils
UNIT
MODEL
COIL
MODEL
1
47F17F HSPF
MBH COP KW MBH COP KW STD
ARI HEATING
60S41S1 FC/MC62 56.5 3.48 4.76 35.4 2.42 4.29 8.00
1. Rated CFM same as for cooling.
2. Heating MBH based on ARI standards of 70° DB entering indoor air, 72% RH outdoor air with 25 feet of interconnecting piping and no supplemental electric heat operation.
CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by the total electric power input during the same period. — = Not Applicable.
2
HEATING CAPACITY - With Variable Speed Furnaces
UNIT
MODEL
THRD18S41S1
THRD24S41S1
THRD30S41S1
THRD36S41S1
For notes See Page 8.
VARIABLE
SPEED
FURNACE
1
COIL
MODEL
MBH COP KW MBH COP KW STD
47F17F HSPF
13 SEER HP WITH VARIABLE SPEED FURNACES
ARI HEATING
3
L*(8,L)C*A12 FC/MC/PC/UC24A 17.6 3.36 1.43 9.6 2.28 1.14 7.70 L*(8,L)C*B12 FC/MC/PC/UC24B 17.6 3.36 1.43 9.6 2.28 1.14 7.70
L*9C*B12 FC/MC/PC/UC24B 17.6 3.36 1.43 9.6 2.28 1.14 7.70 L*(8,L)C*A12 FC/MC/PC/UC30A 17.6 3.36 1.43 9.6 2.28 1.14 7.70 L*(8,L)C*B12 FC/MC/PC/UC30B 17.6 3.36 1.43 9.6 2.28 1.14 7.70
L*9C*B12 FC/MC/PC/UC30B 17.6 3.36 1.43 9.6 2.28 1.14 7.70 L*(8,L)C*A12 HC30 17.6 3.36 1.43 9.6 2.28 1.14 7.70 L*(8,L)C*A12 FC/MC/PC/UC24A 23.0 3.74 1.66 13.4 2.62 1.32 8.20 L*(8,L)C*B12 FC/MC/PC/UC24B 23.0 3.74 1.66 13.4 2.62 1.32 8.20
L*9C*B12 FC/MC/PC/UC24B 23.0 3.74 1.66 13.4 2.62 1.32 8.20 L*(8,L)C*A12 FC/MC/PC/UC30A 23.0 3.74 1.66 13.4 2.62 1.32 8.20 L*(8,L)C*B12 FC/MC/PC/UC30B 23.0 3.74 1.66 13.4 2.62 1.32 8.20
L*9C*B12 FC/MC/PC/UC30B 23.0 3.74 1.66 13.4 2.62 1.32 8.20 L*(8,L)C*A12 HC30 23.0 3.74 1.66 13.4 2.62 1.32 8.20 L*(8,L)C*B12 FC/MC/PC/UC43B 28.0 3.70 2.02 14.0 2.46 1.56 8.20
L*9C*B12 FC/MC/PC/UC43B 28.0 3.70 2.02 14.0 2.46 1.56 8.20 L*(8,L)C*C16 FC/MC/PC/UC43C 28.0 3.70 2.02 14.0 2.46 1.56 8.20
L*9C*C16 FC/MC/PC/UC43C 28.0 3.70 2.02 14.0 2.46 1.56 8.20 L*(8,L)C*C16 HC42 28.0 3.70 2.02 14.0 2.46 1.56 8.20
L*9C*C16 HC42 28.0 3.70 2.02 14.0 2.46 1.56 8.20 L*(8,L)C*C16 FC/MC/PC/UC43C 33.0 3.70 2.53 17.9 2.38 2.01 8.00
L*9C*C16 FC/MC/PC/UC43C 33.0 3.70 2.53 17.9 2.38 2.01 8.00 L*(8,L)C*C20 FC/MC/PC/UC43C 33.0 3.70 2.53 17.9 2.38 2.01 8.00
L*9C*C20 FC/MC/PC/UC43C 33.0 3.70 2.53 17.9 2.38 2.01 8.00 L*(8,L)C*C16 HC42 33.0 3.70 2.53 17.9 2.38 2.01 8.00
L*9C*C16 HC42 33.0 3.70 2.53 17.9 2.38 2.01 8.00 L*(8,L)C*C20 HC42 33.0 3.70 2.53 17.9 2.38 2.01 8.00
L*9C*C20 HC42 33.0 3.70 2.53 17.9 2.38 2.01 8.00
2
Johnson Controls Unitary Products 7
445073-LTG-A-0109
HEATING CAPACITY - With Variable Speed Furnaces (Continued)
UNIT
MODEL
THRD42S41S1
THRD48S41S1
THRD60S41S1
1. Rated CFM same as for cooling.
2. Heating MBH based on ARI standards of 70° DB entering indoor air, 72% RH outdoor air with 25 feet of interconnecting piping and no supplemental electric heat operation.
3. Variable speed furnaces have B.O.D (Blower on Delay) standard.
CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by the total electric power input during the same period. — = Not Applicable.
VARIABLE
SPEED
FURNACE
13 SEER HP WITH VARIABLE SPEED FURNACES
L*(8,L)C*C16 FC/MC/PC/UC48C 40.0 3.95 2.64 23.4 2.76 2.17 8.75
L*9C*C16 FC/MC/PC/UC48C 40.0 3.95 2.64 23.4 2.76 2.17 8.75
L*(8,L)C*C20 FC/MC/PC/UC48C 40.0 3.95 2.64 23.4 2.76 2.17 8.75
L*9C*C20 FC/MC/PC/UC48C 40.0 3.95 2.64 23.4 2.76 2.17 8.75 L*9C*D20 FC/MC/PC/UC48D 40.0 3.95 2.64 23.4 2.76 2.17 8.75
L*(8,L)C*C16 FC/PC/UC60C 40.54.002.6423.42.762.178.75
L*9C*C16 FC/PC/UC60C 40.54.002.6423.42.762.178.75
L*(8,L)C*C20 FC/PC/UC60C 40.54.002.6423.42.762.178.75
L*9C*C20 FC/PC/UC60C 40.54.002.6423.42.762.178.75 L*9C*D20 FC/MC/PC/UC60D 40.5 4.00 2.64 23.4 2.76 2.17 8.75 L*9C*D20 HC60 40.54.002.6423.42.762.178.75
L*(8,L)C*C20 FC/MC62D 46.04.003.1027.02.781.828.20
L*9C*C20 FC/MC62D 46.0 4.00 3.10 27.0 2.78 1.82 8.20 L*9C*D20 FC/MC62D 46.0 4.00 3.10 27.0 2.78 1.82 8.20
L*(8,L)C*C20 FC/MC62D 55.5 3.42 4.11 34.6 2.44 3.51 8.00
L*9C*C20 FC/MC62D 56.0 3.36 4.24 35.0 2.40 3.63 8.00 L*9C*D20 FC/MC62D 56.0 3.46 4.10 35.0 2.42 3.59 8.00
COIL
MODEL
1
47F17FHSPF
MBH COP KW MBH COP KW STD
ARI HEATING
3
2
ACCESSORIES
Refer to Price Manual for specific model numbers. Start Assist Kit (2SA067*) - May be required on 42, 48, 60
models. Models 18, 24, 30, 36 have been factory installed. Blower Time Delay - Available to increase efficiency when
installed. Installs on indoor section and maintains blower for approximately one minute after cooling thermostat has been satisfied.
Hard Start Kits - Provides required starting torque for use with Thermal Expansion Valve Kit.
Low Temperature Cutout (2LT06700224) - Prevents heat pump operation below -1°F ambient temperature.
Compressor Blanket - Designed to further reduce the normal operating sound.
Add-on Fossil Fuel Control - Interface controls for use with gas, oil furnaces and the heat pump system are available.
Thermal Expansion Valve Kit - 1TVM900 Series TXV kit used to improve system performance.
Outdoor Thermostat (2TD06700124) - Provides additional staging of supplemental electric heat.
Room Thermost ats - A wide selection of matching thermostats is available to provide features required for any installation.
2H/1C, manual changeover electronic non-programmable ther­mostat.
3H/2C, non-programmable digital thermostat. 3H/2C, auto/manual changeover, electronic programmable, 7-
day, hardwire thermostat. * For the most current accessory information, refer to the price
book or consult factory.
SOUND POWER RATINGS
UNIT MODEL
018 73.1 80.4 024 72.9 75.0 030 76.8 80.4 036 76.5 78.2 042 72.7 75.2 048 76.7 78.1 060 77.2 78.9
* Rated in accordance with ARI 270-95 Standards.
Cooling Heating
(dBA)*
8 Johnson Controls Unitary Products
TYPICAL INSTALLATION
THERMOSTAT
SEAL OPENING(S) WITH PERMAGUM OR EQUIVALENT
TO INDOOR COIL
TO FURNACE OR AIR HANDLER TERMINAL BLOCK
NEC CLASS 2 WIRING
NEC CLASS 1 WIRING
ALL OUTDOOR WIRING MUST BE WEATHERPROOF.
CONTROL ACCESS PANEL
WEATHERPROOF DISCONNECT SWITCH
MINIMUM 24” SERVICE ACCESS CLEARANCE ON ONE SIDE
48” OVERHEAD CLEARANCE
10” CLEARANCE AROUND PERIMETER
NOTE:
THERMOSTAT
INDOOR UNIT
OUTDOOR UNIT
LOW VOLTAGE TERMINAL BLOCK IN AIR HANDLER WITH ELECTRIC HEAT
DEFROST CONTROL
FIELD INSTALLED JUMPER
DEHUMIDIFICATION CONTROL CONNECTION (Humidistat* Jumper must be removed)
GND.
SCREW
CONTACTOR
T2
T1
L2
L1
M
R
LorX
Y
O
W
G
T
2
E
2
R
R
Y
Y
O
O
W2
W
W1
C
C
X/L
G
W1
BK
GND.
LUG
CIRCUIT BREAKER***
POWER WIRING 24V CONTROL WIRING
(NEC CLASS 2)
JUMPER TERMINALS E AND W TO HEAT ON FIRST STAGE DURING EMERGENCY HEAT.
TERMINAL NOT USED ON ALL THERMOSTATS.
POWER WIRING
208/230-1-60
230-1-50
CHECK THE LOW VOLTAGE TERMINAL BLOCK ON THE INDOOR UNIT FOR THE ACTUAL ARRANGEMENT OF THE TERMINALS. CONNECT POWER WIRING TO TERMINAL BLOCK 3TB ON UNITS WITHOUT ELECTRIC HEAT OR CIRCUIT BREAKER.
BorC
ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES
RED
BLK
YEL
ORG
BRN
PUR
WHT
CC
GRY
/66
GRAY FOR USE WITH OPTIONAL OUTDOOR THERMOSTAT KITS.
5
1
2
3
4
5
1
3,4
445073-LTG-A-0109
TYPICAL FIELD WIRING
Johnson Controls Unitary Products 9
445073-LTG-A-0109
COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO. THRD18S41S1 INDOOR COIL MODEL NO. F6FP18
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
IDCFM 450 600 750
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 18.1 19.9 20.3 22.0 23.3 19.9 21.2 21.3 22.8 23.9 21.8 22.5 22.4 23.5 24.6
S.C. 18.0 16.0 14.2 14.1 12.1 19.9 18.4 15.6 15.2 12.7 21.7 20.7 17.0 16.3 13.3
KW 1.3 1.3 1.3 1.3 1.3 1.4 1.4 1.4 1.4 1.4 1.4 1.5 1.5 1.5 1.5 T.C. 17.2 18.6 18.9 20.7 22.0 18.9 19.8 19.8 21.4 22.7 20.5 20.9 20.8 22.1 23.3 S.C. 17.1 15.4 13.5 13.5 11.5 18.8 17.6 14.9 14.6 12.1 20.5 19.7 16.4 15.8 12.7
KW 1.3 1.4 1.4 1.4 1.4 1.4 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.6 1.6 T.C. 16.3 17.4 17.5 19.4 20.8 17.8 18.3 18.3 20.1 21.4 19.3 19.3 19.1 20.8 22.1 S.C. 16.2 14.9 12.8 12.8 10.8 17.8 16.8 14.3 14.1 11.5 19.3 18.7 15.8 15.4 12.1
KW 1.4 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.6 1.6 1.6 1.6 1.6 1.7 1.7 T.C. 15.4 16.1 16.1 18.1 19.6 16.7 16.9 16.8 18.7 20.2 18.1 17.7 17.5 19.4 20.8 S.C. 15.3 14.3 12.1 12.2 10.1 16.7 16.0 13.6 13.6 10.8 18.1 17.7 15.2 14.9 11.5
KW 1.5 1.5 1.5 1.6 1.6 1.6 1.6 1.6 1.7 1.7 1.7 1.7 1.7 1.8 1.8 T.C. 14.1 14.1 13.7 16.5 18.2 15.4 14.8 14.7 17.0 18.7 16.7 15.6 15.8 17.5 19.2 S.C. 14.1 12.9 11.0 11.6 9.5 15.3 14.2 12.6 12.9 10.2 16.6 15.5 14.2 14.3 10.9
KW 1.6 1.6 1.6 1.7 1.7 1.7 1.7 1.7 1.8 1.8 1.8 1.8 1.8 1.8 1.9 T.C. 12.8 12.1 11.2 15.0 16.9 14.0 12.8 12.6 15.3 17.2 15.2 13.5 14.1 15.6 17.6 S.C. 12.8 11.5 9.9 10.9 8.8 14.0 12.5 11.6 12.3 9.6 15.2 13.4 13.3 13.6 10.3
KW 1.7 1.7 1.7 1.8 1.8 1.8 1.8 1.8 1.8 1.9 1.9 1.9 1.9 1.9 2.0 T.C. 11.5 10.1 8.8 13.4 15.5 12.7 10.7 10.6 13.6 15.7 13.8 11.4 12.3 13.7 15.9 S.C. 11.5 10.1 8.8 10.3 8.2 12.6 10.7 10.5 11.6 9.0 13.7 11.3 12.3 12.9 9.7
KW 1.7 1.8 1.7 1.9 1.9 1.9 1.9 1.8 1.9 2.0 2.0 2.0 1.9 2.0 2.1
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler Coil T.C. S.C. KW
MV12B FC/MC18B 1.00 1.00 1.00 MV12B FC/MC24B 1.00 1.00 1.00 MV12B FC/MC30B 1.00 1.00 1.00 AV24 1.00 1.00 1.00 F6FP24 1.00 1.00 1.00
Variable Speed Furnace
L*(8,L)C*A12 FC/MC/PC/UC24A 1.00 1.00 1.00 L*(8,L)C*B12 FC/MC/PC/UC24B 1.00 1.00 1.00 L*9C*B12 FC/MC/PC/UC24B 1.00 1.00 1.00 L*(8,L)C*A12 FC/MC/PC/UC30A 1.00 1.00 1.00 L*(8,L)C*B12 FC/MC/PC/UC30B 1.00 1.00 1.00 L*9C*B12 FC/MC/PC/UC30B 1.00 1.00 1.00 L*(8,L)C*A12 HC30 1.00 1.00 1.00
Coil T.C. S.C. KW
10 Johnson Controls Unitary Products
COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO. THRD24S41S1 INDOOR COIL MODEL NO. F6FP24
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES I N CL UDE INDOO R FAN HEAT AT 1250 BTUH/1000 CFM.
IDCFM 600 800 1000
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 24.4 26.0 26.9 29.5 30.7 26.4 26.3 28.0 30.4 31.4 28.4 26.5 29.0 31.4 32.0
S.C. 23.8 21.5 18.7 18.8 15.3 25.7 23.7 20.9 20.2 15.9 27.7 25.9 23.0 21.7 16.4
KW 1.6 1.6 1.7 1.7 1.7 1.7 1.7 1.8 1.8 1.8 1.8 1.8 1.8 1.9 1.9 T.C. 22.6 24.0 24.2 27.3 28.9 24.7 24.7 25.3 28.1 29.7 26.8 25.4 26.5 28.8 30.4 S.C. 22.1 20.6 17.5 17.8 14.6 24.1 22.7 19.8 19.5 15.3 26.1 24.8 22.0 21.1 16.0
KW 1.7 1.7 1.7 1.8 1.8 1.8 1.8 1.8 1.9 1.9 1.9 1.9 1.9 2.0 2.0 T.C. 20.9 21.9 21.4 25.2 27.1 23.0 23.1 22.7 25.8 28.0 25.1 24.3 24.0 26.3 28.8 S.C. 20.4 19.8 16.4 16.9 13.8 22.4 21.8 18.7 18.7 14.7 24.5 23.7 21.1 20.5 15.6
KW 1.8 1.8 1.8 1.9 2.0 1.9 1.9 1.9 2.0 2.1 2.1 2.1 2.0 2.1 2.2 T.C. 19.1 19.9 18.7 23.1 25.3 21.3 21.6 20.1 23.4 26.3 23.5 23.2 21.5 23.8 27.3 S.C. 18.6 18.9 15.2 16.0 13.1 20.8 20.8 17.6 18.0 14.1 23.0 22.7 20.1 19.9 15.2
KW 1.9 1.9 1.9 2.0 2.1 2.0 2.0 2.0 2.1 2.2 2.2 2.2 2.1 2.2 2.3 T.C. 17.4 17.8 16.4 20.1 23.3 19.3 19.8 17.8 20.8 24.1 21.3 21.8 19.1 21.5 24.9 S.C. 16.9 17.1 14.2 14.9 12.2 18.9 19.2 16.2 17.0 13.4 20.8 21.2 18.2 19.1 14.6
KW 2.0 2.0 1.9 2.1 2.2 2.1 2.1 2.1 2.2 2.3 2.3 2.3 2.2 2.3 2.4 T.C. 15.6 15.6 14.2 17.2 21.3 17.4 18.0 15.4 18.2 22.0 19.1 20.3 16.7 19.1 22.6 S.C. 15.2 15.2 13.3 13.8 11.2 17.0 17.5 14.8 16.0 12.6 18.7 19.8 16.3 18.3 14.0
KW 2.1 2.1 2.0 2.1 2.3 2.2 2.3 2.1 2.3 2.4 2.4 2.4 2.3 2.4 2.5 T.C. 13.9 13.5 11.9 14.2 19.4 15.4 16.2 13.1 15.5 19.8 16.9 18.9 14.4 16.8 20.3 S.C. 13.5 13.4 11.9 12.6 10.3 15.0 15.9 13.1 15.0 11.9 16.5 18.4 14.4 16.8 13.5
KW 2.2 2.1 2.1 2.2 2.4 2.3 2.4 2.2 2.3 2.5 2.5 2.6 2.4 2.5 2.7
445073-LTG-A-0109
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler Coil T.C. S.C. KW
MV12B FC/MC24B 1.00 1.00 1.00 MV12B FC/MC30B 1.00 1.00 1.00 AV24 1.00 1.00 1.00
Variable Speed Furnace
L*(8,L)C*A12 FC/MC/PC/UC24A 1.00 1.00 1.00 L*(8,L)C*B12 FC/MC/PC/UC24B 1.00 1.00 1.00 L*9C*B12 FC/MC/PC/UC24B 1.00 1.00 1.00 L*(8,L)C*A12 FC/MC/PC/UC30A 1.00 1.00 1.00 L*(8,L)C*B12 FC/MC/PC/UC30B 1.00 1.00 1.00 L*9C*B12 FC/MC/PC/UC30B 1.00 1.00 1.00 L*(8,L)C*A12 HC30 1.00 1.00 1.00
Coil T.C. S.C. KW
Johnson Controls Unitary Products 11
445073-LTG-A-0109
COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO. THRD30S41S1 INDOOR COIL MODEL NO. F6FP30
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
IDCFM 800 1000 1200
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 29.7 32.9 32.9 35.3 38.2 31.8 33.6 33.9 36.4 39.1 33.9 34.4 34.8 37.5 40.0 S.C. 29.1 26.1 22.6 22.0 18.5 31.2 29.0 24.5 23.9 19.4 33.3 31.8 26.4 25.8 20.3
KW 2.0 2.0 2.0 2.1 2.1 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.3 2.3 T.C. 28.1 30.6 30.6 33.2 36.0 30.1 31.5 31.5 34.2 36.9 32.1 32.3 32.5 35.2 37.7 S.C. 27.5 25.1 21.5 21.2 17.6 29.5 27.8 23.4 23.1 18.6 31.5 30.4 25.4 25.0 19.5
KW 2.1 2.1 2.1 2.2 2.3 2.2 2.3 2.3 2.3 2.4 2.4 2.4 2.4 2.4 2.5 T.C. 26.4 28.3 28.2 31.1 33.9 28.4 29.3 29.2 32.1 34.6 30.4 30.3 30.2 33.0 35.4 S.C. 25.9 24.1 20.4 20.3 16.8 27.8 26.6 22.4 22.2 17.7 29.8 29.0 24.4 24.2 18.6
KW 2.2 2.3 2.3 2.4 2.4 2.4 2.4 2.4 2.5 2.5 2.5 2.5 2.5 2.6 2.6 T.C. 24.8 26.1 25.9 29.1 31.8 26.7 27.1 26.9 29.9 32.4 28.6 28.2 27.9 30.7 33.0 S.C. 24.3 23.1 19.3 19.4 15.9 26.2 25.4 21.4 21.4 16.8 28.0 27.6 23.5 23.4 17.8
KW 2.4 2.4 2.4 2.5 2.6 2.5 2.5 2.5 2.6 2.7 2.7 2.6 2.6 2.7 2.8 T.C. 23.1 23.6 23.5 26.8 29.4 24.8 25.0 24.4 27.5 30.0 26.6 26.4 25.3 28.2 30.6 S.C. 22.6 21.9 18.3 18.5 14.9 24.4 23.9 20.4 20.5 15.9 26.1 25.9 22.4 22.4 16.9
KW 2.5 2.5 2.5 2.7 2.8 2.7 2.7 2.7 2.8 2.9 2.8 2.8 2.8 2.9 3.0 T.C. 21.4 21.1 21.2 24.6 27.1 23.0 22.9 21.9 25.1 27.6 24.6 24.6 22.7 25.7 28.2 S.C. 21.0 20.7 17.3 17.6 13.9 22.5 22.4 19.3 19.5 14.9 24.1 24.1 21.4 21.4 16.0
KW 2.7 2.7 2.7 2.8 2.9 2.8 2.8 2.8 2.9 3.0 3.0 3.0 2.9 3.0 3.1 T.C. 19.7 18.7 18.8 22.3 24.8 21.2 20.7 19.4 22.8 25.3 22.6 22.8 20.1 23.2 25.8 S.C. 19.3 18.7 16.2 16.7 12.9 20.7 20.7 18.3 18.5 14.0 22.1 22.3 20.1 20.4 15.1
KW 2.8 2.8 2.8 3.0 3.1 3.0 3.0 2.9 3.1 3.2 3.2 3.2 3.1 3.2 3.3
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler Coil T.C. S.C. KW
MV16C FC/MC35C 1.00 1.00 1.00 MV12B FC/MC43B 1.00 1.00 1.00 MV16C FC/MC43C 1.00 1.00 1.00 AV36 1.00 1.00 1.00 F6FP36 1.00 1.00 1.00
Variable Speed Furnace
L*(8,L)C*B12 FC/MC/PC/UC43B 1.00 1.00 1.00 L*9C*B12 FC/MC/PC/UC43B 1.00 1.00 1.00 L*(8,L)C*C16 FC/MC/PC/UC43C 1.00 1.00 1.00 L*9C*C16 FC/MC/PC/UC43C 1.00 1.00 1.00 L*(8,L)C*C16 HC42 1.00 1.00 1.00 L*9C*C16 HC42 1.00 1.00 1.00
Coil T.C. S.C KW
12 Johnson Controls Unitary Products
COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO. THRD36S41S1 INDOOR COIL MODEL NO. F6FP36
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES I N CL UDE INDOO R FAN HEAT AT 1250 BTUH/1000 CFM.
IDCFM 1000 1200 1400
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 35.0 37.8 37.8 41.8 46.1 37.3 39.1 39.1 43.1 47.3 39.5 40.5 40.5 44.4 48.5 S.C. 34.7 31.0 26.5 26.4 22.0 36.9 34.3 28.6 28.4 23.3 39.1 37.6 30.6 30.4 24.5
KW 2.4 2.5 2.5 2.5 2.6 2.5 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.7 2.7 T.C. 32.9 34.9 34.9 38.9 43.4 35.0 36.1 36.1 40.2 44.4 37.1 37.2 37.3 41.4 45.5 S.C. 32.6 29.7 25.2 25.2 20.9 34.6 32.4 27.2 27.2 22.1 36.7 35.2 29.2 29.2 23.3
KW 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.9 T.C. 30.8 32.0 32.0 36.0 40.7 32.7 33.0 33.1 37.2 41.6 34.6 34.0 34.1 38.4 42.5 S.C. 30.4 28.4 23.9 24.0 19.7 32.3 30.6 25.9 26.0 20.9 34.2 32.8 27.9 28.0 22.1
KW 2.7 2.8 2.8 2.8 2.9 2.8 2.9 2.9 2.9 3.0 3.0 2.9 2.9 3.0 3.1 T.C. 28.6 29.1 29.2 33.1 38.0 30.4 30.0 30.0 34.3 38.8 32.1 30.8 30.9 35.4 39.5 S.C. 28.3 27.1 22.6 22.8 18.6 30.1 28.8 24.6 24.8 19.7 31.8 30.4 26.5 26.8 20.8
KW 2.9 2.9 2.9 3.0 3.1 3.0 3.0 3.0 3.1 3.2 3.1 3.1 3.1 3.2 3.3 T.C. 26.1 26.4 25.7 29.7 34.3 27.8 27.6 26.4 30.6 35.3 29.5 28.8 27.2 31.6 36.3 S.C. 25.8 25.2 21.1 21.4 17.3 27.5 26.9 23.0 23.4 18.4 29.2 28.5 24.8 25.4 19.6
KW 3.1 3.1 3.0 3.1 3.3 3.2 3.2 3.1 3.3 3.4 3.3 3.3 3.2 3.4 3.5 T.C. 23.6 23.6 22.2 26.2 30.6 25.2 25.2 22.8 27.0 31.8 26.9 26.9 23.4 27.8 33.1 S.C. 23.3 23.3 19.6 20.1 15.9 25.0 25.0 21.4 22.0 17.2 26.6 26.6 23.2 23.9 18.4
KW 3.2 3.2 3.2 3.3 3.5 3.4 3.4 3.3 3.4 3.6 3.5 3.5 3.4 3.5 3.7 T.C. 21.1 20.8 18.7 22.7 26.9 22.6 22.8 19.2 23.3 28.4 24.2 24.9 19.7 24.0 29.8 S.C. 20.8 20.8 18.1 18.7 14.6 22.4 22.8 19.2 20.6 15.9 24.0 24.6 19.7 22.5 17.2
KW 3.4 3.4 3.3 3.5 3.7 3.5 3.5 3.4 3.6 3.8 3.7 3.7 3.5 3.7 3.9
445073-LTG-A-0109
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler Coil T.C. S.C. KW
MV16C FC/MC35C 1.00 1.00 1.00 MV16C FC/MC43C 1.02 1.00 1.00 AV36 1.02 1.00 1.00
Variable Speed Furnace
L*(8,L)C*C16 FC/MC/PC/UC43C 1.00 1.00 1.00 L*9C*C16 FC/MC/PC/UC43C 1.00 1.00 1.00 L*(8,L)C*C20 FC/MC/PC/UC43C 1.00 1.00 1.00 L*9C*C20 FC/MC/PC/UC43C 1.00 1.00 1.00 L*(8,L)C*C16 HC42 1.00 1.00 1.00 L*9C*C16 HC42 1.00 1.00 1.00 L*(8,L)C*C20 HC42 1.00 1.00 1.00 L*9C*C20 HC42 1.00 1.00 1.00
Coil T.C. S.C. KW
Johnson Controls Unitary Products 13
445073-LTG-A-0109
COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO. THRD42S41S1 INDOOR COIL MODEL NO. F6FP42
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
IDCFM 1200 1400 1600
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 43.1 45.7 46.2 51.4 56.6 45.5 46.9 47.2 52.7 57.8 47.9 48.0 48.2 54.0 59.1 S.C. 43.1 40.8 34.9 34.9 28.6 45.5 44.6 37.1 37.1 30.0 47.9 48.0 39.3 39.3 31.3
KW 2.5 2.5 2.5 2.6 2.6 2.6 2.6 2.5 2.6 2.7 2.7 2.6 2.6 2.7 2.8 T.C. 40.3 42.3 42.3 47.4 52.5 42.5 43.6 43.6 48.6 53.9 44.7 44.8 44.8 49.8 55.2 S.C. 40.3 39.3 33.1 33.2 26.9 42.5 42.4 35.4 35.4 28.4 44.7 44.8 37.8 37.6 29.8
KW 2.7 2.6 2.6 2.7 2.8 2.8 2.7 2.7 2.8 2.9 2.8 2.8 2.8 2.9 3.0 T.C. 37.6 38.9 38.4 43.5 48.5 39.6 40.3 40.0 44.5 49.9 41.6 41.7 41.5 45.6 51.4 S.C. 37.6 37.7 31.2 31.5 25.3 39.6 40.3 33.7 33.7 26.8 41.6 41.7 36.2 35.9 28.2
KW 2.9 2.8 2.8 2.9 3.0 2.9 2.9 2.9 3.0 3.1 3.0 3.0 3.0 3.1 3.2 T.C. 34.8 35.4 34.5 39.6 44.5 36.6 37.0 36.3 40.5 46.0 38.4 38.5 38.1 41.4 47.5 S.C. 34.8 35.4 29.4 29.9 23.7 36.6 37.0 32.1 32.0 25.2 38.4 38.5 34.7 34.2 26.6
KW 3.0 3.0 3.0 3.0 3.2 3.1 3.1 3.1 3.1 3.3 3.2 3.2 3.2 3.3 3.3 T.C. 29.7 30.7 28.6 33.3 40.4 32.4 32.9 30.2 35.1 40.4 35.1 35.2 31.7 36.9 40.4 S.C. 29.7 30.7 26.6 27.3 22.1 32.4 32.9 28.5 29.9 23.1 35.1 35.2 30.5 32.4 24.1
KW 3.1 3.1 3.1 3.2 3.4 3.2 3.2 3.2 3.3 3.4 3.3 3.3 3.3 3.4 3.5 T.C. 24.5 25.9 22.7 27.1 36.3 28.2 28.9 24.0 29.7 34.8 31.8 31.8 25.3 32.4 33.2 S.C. 24.5 25.9 22.7 24.8 20.5 28.2 28.9 24.0 27.8 21.0 31.8 31.8 25.3 30.7 21.6
KW 3.3 3.3 3.2 3.3 3.5 3.4 3.4 3.3 3.4 3.6 3.5 3.5 3.4 3.5 3.7 T.C. 19.4 21.1 16.8 20.9 32.3 23.9 24.8 17.8 24.4 29.1 28.5 28.5 18.9 27.8 26.0 S.C. 19.4 21.1 16.8 20.9 18.9 23.9 24.8 17.8 24.4 19.0 28.5 28.5 18.9 27.8 19.1
KW 3.4 3.5 3.3 3.5 3.7 3.5 3.6 3.4 3.6 3.8 3.7 3.7 3.5 3.7 3.8
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler Coil T.C. S.C. KW
MV16C FC/MC48C 1.00 1.00 1.00 MV20D FC/MC48D 1.00 1.00 1.00 MV16C FC/MC60C 1.00 1.00 1.00 MV20D FC/MC60D 1.00 1.00 1.00 AV48 1.00 1.00 1.00 AV60 1.00 1.00 1.00 F6FP48 1.00 1.00 1.00
Variable Speed Furnace
L*(8,L)C*C16 FC/MC/PC/UC48C 1.00 1.00 1.00 L*9C*C16 FC/MC/PC/UC48C 1.00 1.00 1.00 L*(8,L)C*C20 FC/MC/PC/UC48C 1.00 1.00 1.00 L*9C*C20 FC/MC/PC/UC48C 1.00 1.00 1.00 L*9C*D20 FC/MC/PC/UC48D 1.00 1.00 1.00 L*(8,L)C*C16 FC/PC/UC60C 1.00 1.00 1.00 L*9C*C16 FC/PC/UC60C 1.00 1.00 1.00 L*(8,L)C*C20 FC/PC/UC60C 1.00 1.00 1.00 L*9C*C20 FC/PC/UC60C 1.00 1.00 1.00 L*9C*D20 FC/MC/PC/UC60D 1.00 1.00 1.00 L*9C*D20 HC60 1.00 1.00 1.00
Coil T.C. S.C. KW
14 Johnson Controls Unitary Products
COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO. THRD48S41S1 INDOOR COIL MODEL NO. F6FP48
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES I N CL UDE INDOO R FAN HEAT AT 1250 BTUH/1000 CFM.
IDCFM 1400 1600 1800
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 48.9 52.7 52.5 58.0 62.8 50.9 53.6 53.6 59.0 64.0 52.9 54.6 54.8 60.0 65.2 S.C. 48.9 46.4 39.4 39.3 31.8 50.9 49.7 41.6 41.3 32.9 52.9 53.1 43.8 43.4 33.9
KW 3.1 3.2 3.2 3.3 3.5 3.2 3.2 3.3 3.4 3.6 3.2 3.3 3.3 3.6 3.7 T.C. 46.2 48.8 48.8 54.3 59.2 48.2 49.8 49.8 55.2 60.0 50.3 50.8 50.8 56.2 60.8 S.C. 46.2 44.5 37.7 37.7 30.4 48.2 47.5 39.8 39.7 31.5 50.3 50.5 42.0 41.8 32.6
KW 3.3 3.4 3.4 3.5 3.7 3.4 3.5 3.5 3.7 3.8 3.5 3.5 3.6 3.8 3.9 T.C. 43.4 44.9 45.1 50.5 55.6 45.5 45.9 45.9 51.5 56.0 47.6 46.9 46.8 52.4 56.5 S.C. 43.4 42.7 35.9 36.0 28.9 45.5 45.3 38.0 38.1 30.1 47.6 46.9 40.2 40.2 31.2
KW 3.5 3.6 3.6 3.7 3.9 3.6 3.7 3.7 3.9 4.0 3.8 3.8 3.8 4.0 4.1 T.C. 40.6 40.9 41.3 46.7 52.0 42.8 42.0 42.1 47.7 52.1 44.9 43.0 42.8 48.6 52.1 S.C. 40.6 40.8 34.1 34.4 27.5 42.8 42.0 36.2 36.5 28.7 44.9 43.0 38.3 38.6 29.8
KW 3.7 3.8 3.7 4.0 4.1 3.9 3.9 3.9 4.1 4.2 4.0 4.0 4.0 4.2 4.3 T.C. 37.2 37.4 36.7 43.0 47.9 39.3 38.9 37.4 43.7 48.2 41.4 40.4 38.1 44.4 48.4 S.C. 37.2 37.4 32.0 32.8 25.9 39.3 38.9 34.1 34.9 27.0 41.4 40.4 36.3 36.9 28.1
KW 3.9 4.0 3.9 4.1 4.3 4.1 4.1 4.0 4.3 4.4 4.3 4.2 4.1 4.4 4.5 T.C. 33.7 33.8 32.1 39.2 43.9 35.8 35.8 32.8 39.7 44.3 37.8 37.8 33.4 40.2 44.7 S.C. 33.7 33.8 29.9 31.2 24.4 35.8 35.8 32.1 33.2 25.4 37.8 37.8 33.4 35.2 26.5
KW 4.1 4.1 4.1 4.3 4.6 4.3 4.3 4.2 4.5 4.7 4.5 4.5 4.3 4.6 4.8 T.C. 30.3 30.2 27.5 35.4 39.8 32.3 32.7 28.1 35.7 40.4 34.3 35.2 28.7 35.9 40.9 S.C. 30.3 30.2 27.5 29.6 22.9 32.3 32.7 28.1 31.5 23.8 34.3 35.2 28.7 33.5 24.8
KW 4.4 4.3 4.2 4.5 4.8 4.5 4.5 4.4 4.7 4.9 4.7 4.7 4.5 4.8 5.0
445073-LTG-A-0109
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler Coil T.C. S.C. KW
MV20D FC/MC60D 1.00 1.00 1.00 MV20D FC/MC62D 1.00 1.00 1.00 AV48 1.00 1.00 1.00 AV60 1.00 1.00 1.00 F6FP60 1.00 1.00 1.00
Variable Speed Furnace
L*(8,L)C*C20 FC/MC62D 1.00 1.00 1.00 L*9C*C20 FC/MC62D 1.00 1.00 1.00 L*9C*D20 FC/MC62D 1.00 1.00 1.00
Coil T.C. S.C. KW
Johnson Controls Unitary Products 15
445073-LTG-A-0109
COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO. THRD60S41S1 INDOOR COIL MODEL NO. FC/MC62
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
IDCFM 1400 1600 1800
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 54.0 57.1 56.9 62.3 67.6 56.0 57.9 57.8 63.4 69.1 58.0 58.7 58.7 64.4 70.5 S.C. 56.0 51.0 43.4 42.9 34.8 58.1 54.4 45.4 45.0 36.2 60.1 57.7 47.4 47.1 37.6
KW 2.8 2.8 2.8 2.9 2.9 2.8 2.8 2.8 2.9 2.9 2.8 2.8 2.8 2.9 2.9 T.C. 51.9 54.1 53.9 59.2 64.5 53.7 54.9 54.8 60.2 65.7 55.5 55.7 55.6 61.2 66.9 S.C. 53.8 49.8 42.0 41.7 33.5 55.7 52.7 44.1 43.8 34.8 57.5 55.6 46.1 45.8 36.2
KW 3.2 3.2 3.2 3.3 3.3 3.2 3.2 3.2 3.3 3.3 3.2 3.2 3.2 3.3 3.3 T.C. 49.7 51.1 51.0 56.2 61.4 51.3 51.9 51.8 57.1 62.4 53.0 52.7 52.6 58.0 63.4 S.C. 51.6 48.6 40.7 40.5 32.2 53.2 51.1 42.8 42.5 33.4 54.9 53.6 44.9 44.6 34.7
KW 3.6 3.6 3.6 3.6 3.7 3.6 3.6 3.6 3.7 3.7 3.6 3.6 3.6 3.7 3.7 T.C. 47.6 48.1 48.1 53.1 58.3 49.0 48.9 48.8 54.0 59.0 50.4 49.7 49.5 54.8 59.8 S.C. 49.4 47.4 39.3 39.2 30.9 50.8 49.5 41.5 41.3 32.0 52.3 51.5 43.6 43.3 33.2
KW 4.0 4.0 4.0 4.0 4.1 4.0 4.0 4.0 4.1 4.1 4.0 4.0 4.0 4.1 4.1 T.C. 44.3 44.6 44.1 48.7 53.5 45.6 45.5 44.6 49.3 54.1 46.8 46.3 45.2 50.0 54.7 S.C. 45.9 44.7 37.6 37.4 29.0 47.2 46.3 39.7 39.4 30.2 48.5 48.0 41.8 41.5 31.3
KW 4.5 4.5 4.5 4.5 4.6 4.5 4.5 4.5 4.5 4.6 4.5 4.5 4.5 4.5 4.6 T.C. 41.1 41.3 40.2 44.4 48.9 42.2 42.2 40.6 44.9 49.4 43.3 43.1 41.0 45.3 49.9 S.C. 42.6 42.0 35.9 35.7 27.3 43.8 43.3 37.9 37.7 28.4 44.9 44.6 40.0 39.7 29.5
KW 4.9 5.0 4.9 5.0 5.0 5.0 5.0 4.9 5.0 5.0 5.0 5.0 5.0 5.0 5.0 T.C. 37.9 37.9 36.2 40.1 44.3 38.8 38.8 36.5 40.4 44.6 39.8 39.8 36.8 40.7 45.0 S.C. 39.3 39.3 34.2 33.9 25.5 40.3 40.3 36.2 35.9 26.6 41.2 41.3 38.2 37.9 27.7
KW 5.4 5.4 5.4 5.4 5.5 5.4 5.4 5.4 5.4 5.5 5.4 5.4 5.4 5.4 5.5
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler Coil T.C. S.C. KW
MV20D FC/MC62D 1.01 1.00 1.00 F6FP60 1.01 1.00 1.00
Variable Speed Furnace
L*(8,L)C*C20 FC/MC62D 0.99 1.00 1.00 L*9C*C20 FC/MC62D 0.97 1.00 1.00 L*9C*D20 FC/MC62D 0.98 1.00 1.00
Coil T.C. S.C. KW
16 Johnson Controls Unitary Products
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO THRD18S41S1 EVAPORATOR COIL MODEL NO F6FP18
AIR TEMP.
ENTERING
OUTDOOR UNIT
60
47
40
30
17
10
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
AIR TEMP. ENTERING
INDOOR COIL
60 22.0 1.6 4.0 23.6 1.5 4.3 25.3 1.4 4.7 70 20.6 1.6 3.6 22.2 1.6 3.9 23.7 1.5 4.3 80 19.2 1.7 3.2 20.7 1.6 3.5 22.2 1.6 3.8 60 18.7 1.5 3.6 18.3 1.4 3.7 18.0 1.2 3.8 70 17.3 1.5 3.2 17.6 1.4 3.4 18.0 1.4 3.5 80 15.9 1.5 2.9 16.9 1.5 3.1 17.9 1.5 3.3 60 16.5 1.4 3.3 17.4 1.4 3.5 18.2 1.3 3.7 70 15.3 1.4 3.0 16.2 1.4 3.2 17.1 1.4 3.4 80 14.0 1.4 2.7 15.0 1.4 2.9 16.0 1.4 3.0 60 13.7 1.3 2.9 14.4 1.3 3.0 15.1 1.3 3.2 70 12.5 1.3 2.6 13.3 1.3 2.8 14.1 1.3 2.9 80 11.2 1.3 2.4 12.1 1.3 2.5 13.0 1.3 2.7 60 10.2 1.2 2.4 10.8 1.1 2.5 11.4 1.1 2.6 70 9.0 1.1 2.2 9.6 1.1 2.3 10.2 1.1 2.4 80 7.8 1.1 1.9 8.4 1.1 2.0 9.0 1.1 2.1 60 7.7 1.1 2.0 8.1 1.1 2.0 8.5 1.1 2.1 70 7.0 1.1 1.8 7.5 1.1 1.9 7.9 1.1 1.9 80 6.4 1.1 1.6 6.9 1.1 1.7 7.3 1.1 1.8
MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P.
450 600 750
ID CFM
445073-LTG-A-0109
Multipliers for determining the performance with other indoor sections.
Air Handler Coil MBH KW COP
MV12B FC/MC18B 1.00 1.00 1.00 MV12B FC/MC24B 1.00 1.00 1.00 MV12B FC/MC30B 1.00 1.00 1.00 AV24 1.00 1.00 1.00 F6FP24 1.00 1.00 1.00
Variable Speed Furnace
L*(8,L)C*A12 FC/MC/PC/UC24A 1.00 1.00 1.00 L*(8,L)C*B12 FC/MC/PC/UC24B 1.00 1.00 1.00 L*9C*B12 FC/MC/PC/UC24B 1.00 1.00 1.00 L*(8,L)C*A12 FC/MC/PC/UC30A 1.00 1.00 1.00 L*(8,L)C*B12 FC/MC/PC/UC30B 1.00 1.00 1.00 L*9C*B12 FC/MC/PC/UC30B 1.00 1.00 1.00 L*(8,L)C*A12 HC30 1.00 1.00 1.00
Coil MBH KW COP
Johnson Controls Unitary Products 17
445073-LTG-A-0109
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO THRD24S41S1 EVAPORATOR COIL MODEL NO F6FP24
AIR TEMP. ENTERING
OUTDOOR UNIT
60
47
40
30
17
10
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
AIR TEMP.
ENTERING
INDOOR COIL
60 27.6 1.8 4.3 28.9 1.7 4.6 30.2 1.6 4.9 70 25.9 1.9 3.8 27.2 1.8 4.1 28.5 1.7 4.4 80 24.1 2.0 3.4 25.5 1.9 3.7 26.8 1.8 3.9 60 22.7 1.6 3.8 23.8 1.6 4.0 24.9 1.5 4.2 70 21.4 1.7 3.5 22.4 1.7 3.6 23.4 1.6 3.8 80 20.1 1.8 3.1 21.0 1.7 3.3 21.8 1.7 3.4 60 20.3 1.6 3.6 21.0 1.5 3.7 21.8 1.5 3.8 70 19.1 1.6 3.2 19.8 1.6 3.4 20.5 1.6 3.5 80 17.9 1.7 2.9 18.5 1.6 3.0 19.1 1.6 3.1 60 15.9 1.4 3.0 17.0 1.4 3.2 18.1 1.4 3.4 70 15.4 1.5 2.8 16.2 1.5 2.9 17.0 1.5 3.0 80 14.9 1.6 2.6 15.4 1.5 2.7 15.8 1.5 2.7 60 12.8 1.3 2.6 13.5 1.3 2.7 14.2 1.3 2.8 70 11.7 1.3 2.4 12.2 1.3 2.4 12.7 1.3 2.5 80 10.6 1.3 2.1 10.9 1.3 2.2 11.2 1.3 2.2 60 1.0 1.7 0.2 6.2 1.5 1.1 11.4 1.2 2.4 70 5.0 1.5 0.9 7.6 1.4 1.5 10.2 1.2 2.1 80 9.0 1.2 1.9 9.1 1.2 1.9 9.1 1.2 1.9
MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P.
600 800 1000
ID CFM
Multipliers for determining the performance with other indoor sections.
Air Handler Coil MBH KW COP
MV12B FC/MC24B 1.00 1.00 1.00 MV12B FC/MC30B 1.00 1.00 1.00 AV24 1.00 1.00 1.00
Variable Speed Furnace
L*(8,L)C*A12 FC/MC/PC/UC24A 1.00 1.00 1.00 L*(8,L)C*B12 FC/MC/PC/UC24B 1.00 1.00 1.00 L*9C*B12 FC/MC/PC/UC24B 1.00 1.00 1.00 L*(8,L)C*A12 FC/MC/PC/UC30A 1.00 1.00 1.00 L*(8,L)C*B12 FC/MC/PC/UC30B 1.00 1.00 1.00 L*9C*B12 FC/MC/PC/UC30B 1.00 1.00 1.00 L*(8,L)C*A12 HC30 1.00 1.00 1.00
Coil MBH KW COP
18 Johnson Controls Unitary Products
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO THRD30S41S1 EVAPORATOR COIL MODEL NO F6FP30
AIR TEMP.
ENTERING
OUTDOOR UNIT
60
47
40
30
17
10
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
AIR TEMP. ENTERING
INDOOR COIL
60 33.1 2.2 4.1 31.7 2.1 4.0 30.2 2.0 3.9 70 31.6 2.3 3.8 31.4 2.2 3.8 31.1 2.2 3.8 80 30.1 2.4 3.4 31.1 2.4 3.5 32.1 2.3 3.7 60 26.7 2.0 3.6 27.6 2.0 3.8 28.5 1.9 3.9 70 25.5 2.1 3.3 26.3 2.1 3.4 27.1 2.0 3.5 80 24.4 2.2 3.0 25.1 2.2 3.1 25.8 2.1 3.2 60 22.8 1.9 3.3 23.5 1.8 3.4 24.2 1.8 3.5 70 22.1 2.0 3.1 22.8 1.9 3.1 23.5 1.9 3.2 80 21.5 2.1 2.8 22.2 2.0 2.9 22.9 2.0 3.0 60 20.5 1.8 3.1 20.2 1.7 3.1 19.9 1.7 3.1 70 18.9 1.8 2.8 18.8 1.8 2.8 18.7 1.7 2.8 80 17.3 1.8 2.5 17.4 1.8 2.5 17.5 1.8 2.5 60 15.6 1.6 2.6 15.8 1.6 2.6 16.0 1.5 2.7 70 13.4 1.5 2.3 14.2 1.6 2.4 15.0 1.6 2.4 80 11.3 1.5 2.0 12.6 1.6 2.1 14.0 1.6 2.2 60 13.2 1.5 2.4 13.5 1.5 2.4 13.9 1.5 2.4 70 12.0 1.5 2.1 12.3 1.5 2.1 12.5 1.5 2.1 80 10.8 1.5 1.9 11.0 1.5 1.9 11.2 1.5 1.9
MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P.
800 1000 1200
ID CFM
445073-LTG-A-0109
Multipliers for determining the performance with other indoor sections.
Air Handler Coil MBH KW COP
MV16C FC/MC35C 1.00 1.00 1.00 MV12B FC/MC43B 1.02 1.03 0.99 MV16C FC/MC43C 1.02 1.03 0.99 AV36 1.02 1.03 0.99 F6FP36 1.02 1.03 0.99
Variable Speed Furnace
L*(8,L)C*B12 FC/MC/PC/UC43B 1.02 1.03 0.99 L*9C*B12 FC/MC/PC/UC43B 1.02 1.03 0.99 L*(8,L)C*C16 FC/MC/PC/UC43C 1.02 1.03 0.99 L*9C*C16 FC/MC/PC/UC43C 1.02 1.03 0.99 L*(8,L)C*C16 HC42 1.02 1.03 0.99 L*9C*C16 HC42 1.02 1.03 0.99
Coil MBH KW COP
Johnson Controls Unitary Products 19
445073-LTG-A-0109
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO THRD36S41S1 EVAPORATOR COIL MODEL NO F6FP36
AIR TEMP. ENTERING
OUTDOOR UNIT
60
47
40
30
17
10
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
AIR TEMP.
ENTERING
INDOOR COIL
60 46.1 2.7 4.4 47.6 2.6 4.8 49.0 2.5 4.8 70 44.0 2.9 4.0 45.5 2.8 4.3 46.9 2.7 4.3 80 42.0 3.0 3.6 43.3 2.9 3.9 44.7 2.9 3.9 60 38.1 2.5 4.0 39.4 2.4 4.3 40.8 2.3 4.2 70 36.1 2.6 3.6 37.4 2.5 3.9 38.7 2.5 3.8 80 34.2 2.7 3.2 35.4 2.7 3.5 36.6 2.6 3.4 60 34.0 2.4 3.7 34.9 2.3 3.9 35.7 2.2 3.8 70 32.2 2.5 3.3 33.2 2.4 3.6 34.2 2.4 3.5 80 30.3 2.6 3.0 31.4 2.6 3.2 32.6 2.5 3.1 60 27.7 2.2 3.1 28.8 2.2 3.4 29.8 2.1 3.3 70 26.5 2.3 2.9 27.4 2.3 3.1 28.2 2.2 3.0 80 25.3 2.4 2.7 26.0 2.4 2.9 26.6 2.3 2.7 60 21.5 2.0 2.7 22.2 2.0 2.9 23.0 2.0 2.7 70 20.2 2.0 2.5 20.9 2.0 2.7 21.6 2.0 2.5 80 19.0 2.1 2.3 19.6 2.1 2.4 20.3 2.0 2.3 60 18.7 1.9 2.5 19.3 1.9 2.6 19.9 1.9 2.5 70 17.2 1.9 2.2 17.8 1.9 2.4 18.5 1.9 2.3 80 15.7 1.9 2.0 16.3 1.9 2.2 17.0 1.9 2.1
MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P.
1000 1200 1400
ID CFM
Multipliers for determining the performance with other indoor sections.
Air Handler Coil MBH KW COP
MV16C FC/MC35C 1.00 1.00 1.00 MV16C FC/MC43C 1.03 1.06 1.00 AV36 1.03 1.06 1.00
Variable Speed Furnace
L*(8,L)C*C16 FC/MC/PC/UC43C 1.03 1.06 1.00 L*9C*C16 FC/MC/PC/UC43C 1.03 1.06 1.00 L*(8,L)C*C20 FC/MC/PC/UC43C 1.03 1.06 1.00 L*9C*C20 FC/MC/PC/UC43C 1.03 1.06 1.00 L*(8,L)C*C16 HC42 1.03 1.06 1.00 L*9C*C16 HC42 1.03 1.06 1.00 L*(8,L)C*C20 HC42 1.03 1.06 1.00 L*9C*C20 HC42 1.03 1.06 1.00
Coil MBH KW COP
20 Johnson Controls Unitary Products
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO THRD42S41S1 EVAPORATOR COIL MODEL NO F6FP42
AIR TEMP.
ENTERING
OUTDOOR UNIT
60
47
40
30
17
10
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
AIR TEMP. ENTERING
INDOOR COIL
60 47.6 4.6 2.7 47.5 4.7 2.6 47.5 4.8 2.5 70 46.0 4.3 2.9 46.4 4.3 2.8 46.7 4.4 2.7 80 44.4 3.9 3.1 45.2 4.0 3.0 46.0 4.1 2.9 60 41.6 4.3 2.6 42.2 4.4 2.5 42.9 4.5 2.4 70 39.8 3.9 2.7 40.7 4.0 2.6 41.6 4.1 2.6 80 38.0 3.6 2.8 39.1 3.7 2.8 40.3 3.8 2.8 60 37.8 4.1 2.4 38.9 4.2 2.4 39.9 4.3 2.4 70 36.1 3.7 2.6 37.1 3.8 2.5 38.1 3.9 2.5 80 34.4 3.4 2.7 35.4 3.5 2.6 36.4 3.6 2.6 60 32.1 3.7 2.3 32.5 3.7 2.2 32.8 3.7 2.2 70 30.6 3.4 2.4 31.2 3.4 2.4 31.8 3.4 2.3 80 29.1 3.1 2.5 29.9 3.1 2.5 30.8 3.2 2.4 60 25.9 3.1 2.1 26.5 3.2 2.1 27.2 3.2 2.1 70 24.4 2.9 2.2 25.1 2.9 2.2 25.7 3.0 2.2 80 23.0 2.6 2.3 23.6 2.7 2.2 24.3 2.7 2.2 60 21.9 2.8 2.0 21.8 2.8 2.0 21.7 2.7 1.9 70 19.7 2.5 2.0 20.0 2.5 2.0 20.3 2.5 2.0 80 17.5 2.2 2.0 18.2 2.3 2.0 18.9 2.3 2.0
MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P.
1200 1400 1600
ID CFM
445073-LTG-A-0109
Multipliers for determining the performance with other indoor sections.
Air Handler Coil MBH KW COP
MV16C FC/MC48C 1.00 1.00 1.00 MV20D FC/MC48D 1.00 1.00 1.00 MV16C FC/MC60C 1.01 1.01 1.00 MV20D FC/MC60D 1.01 1.01 1.00 AV48 1.01 1.01 1.00 AV60 1.01 1.01 1.00 F6FP48 1.01 1.01 1.00
Variable Speed Furnace
L*(8,L)C*C16 FC/MC/PC/UC48C 1.00 1.00 1.00 L*9C*C16 FC/MC/PC/UC48C 1.00 1.00 1.00 L*(8,L)C*C20 FC/MC/PC/UC48C 1.00 1.00 1.00 L*9C*C20 FC/MC/PC/UC48C 1.00 1.00 1.00 L*9C*D20 FC/MC/PC/UC48D 1.00 1.00 1.00 L*(8,L)C*C16 FC/PC/UC60C 1.01 1.01 1.00 L*9C*C16 FC/PC/UC60C 1.01 1.01 1.00 L*(8,L)C*C20 FC/PC/UC60C 1.01 1.01 1.00 L*9C*C20 FC/PC/UC60C 1.01 1.01 1.00 L*9C*D20 FC/MC/PC/UC60D 1.01 1.01 1.00 L*9C*D20 HC60 1.01 1.01 1.00
Coil MBH KW COP
Johnson Controls Unitary Products 21
445073-LTG-A-0109
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO THRD48S41S1 EVAPORATOR COIL MODEL NO F6FP48
AIR TEMP. ENTERING
OUTDOOR UNIT
60
47
40
30
17
10
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
AIR TEMP.
ENTERING
INDOOR COIL
60 54.5 3.0 4.7 53.4 2.9 4.7 52.4 2.8 4.6 70 53.4 3.3 4.3 53.5 3.2 4.3 53.6 3.1 4.4 80 52.4 3.6 3.9 53.6 3.5 4.0 54.9 3.4 4.1 60 48.5 2.9 4.4 49.5 2.8 4.4 50.5 2.8 4.5 70 46.4 3.1 3.9 47.2 3.1 3.9 48.1 3.2 3.9 80 44.2 3.3 3.6 44.9 3.4 3.5 45.6 3.5 3.3 60 43.1 2.8 4.0 44.2 2.7 4.1 45.2 2.7 4.2 70 40.0 2.9 3.6 41.6 2.9 3.7 43.2 2.9 3.8 80 36.9 3.0 3.2 39.1 3.0 3.3 41.3 3.0 3.4 60 36.4 2.6 3.6 37.2 2.6 3.7 38.1 2.5 3.7 70 34.5 2.7 3.3 35.4 2.7 3.3 36.2 2.7 3.4 80 32.7 2.8 3.0 33.5 2.8 3.0 34.3 2.8 3.1 60 28.9 0.0 22.6 29.5 1.2 5.4 30.2 2.3 3.1 70 27.3 1.3 4.9 27.7 1.8 3.6 28.1 2.4 2.9 80 25.8 2.5 2.6 25.9 2.5 2.6 26.0 2.5 2.6 60 24.8 2.2 2.8 25.3 2.3 2.8 25.9 2.3 2.8 70 23.1 2.3 2.5 23.6 2.3 2.5 24.1 2.3 2.5 80 21.4 2.4 2.3 21.8 2.4 2.3 22.3 2.4 2.3
MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P.
1400 1600 1800
ID CFM
Multipliers for determining the performance with other indoor sections.
Air Handler Coil MBH KW COP
MV20D FC/MC60D 1.00 1.00 1.00 MV20D FC/MC62D 1.00 1.00 1.00 AV48 1.00 1.00 1.00 AV60 1.00 1.00 1.00 F6FP60 1.00 1.00 1.00
Variable Speed Furnace
L*(8,L)C*C20 FC/MC62D 1.00 1.00 1.00 L*9C*C20 FC/MC62D 1.00 1.00 1.00 L*9C*D20 FC/MC62D 1.00 1.00 1.00
Coil MBH KW COP
22 Johnson Controls Unitary Products
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO THRD60S41S1 EVAPORATOR COIL MODEL NO FC/MC62
AIR TEMP.
ENTERING
OUTDOOR UNIT
60
47
40
30
17
10
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
AIR TEMP. ENTERING
INDOOR COIL
60 65.7 4.7 4.1 66.7 4.6 4.2 67.6 4.6 4.3 70 64.7 5.1 3.7 65.4 5.0 3.8 66.1 4.9 3.9 80 63.8 5.5 3.4 64.1 5.4 3.5 64.5 5.3 3.6 60 56.9 4.4 3.8 57.4 4.4 3.9 58.0 4.3 4.0 70 55.8 4.8 3.4 56.3 4.8 3.5 56.8 4.7 3.5 80 54.7 5.2 3.1 55.2 5.2 3.1 55.6 5.1 3.2 60 51.9 4.3 3.5 51.7 4.3 3.5 51.4 4.3 3.5 70 50.6 4.8 3.1 51.1 4.7 3.2 51.7 4.7 3.2 80 49.3 5.2 2.8 50.6 5.1 2.9 51.9 5.0 3.0 60 44.1 5.0 2.6 43.6 5.0 2.5 43.1 5.0 2.5 70 45.3 4.6 2.9 44.8 4.6 2.9 44.4 4.6 2.8 80 46.5 4.2 3.2 46.1 4.2 3.2 45.6 4.1 3.2 60 36.6 5.0 2.2 36.8 4.9 2.2 36.9 4.9 2.2 70 36.0 4.5 2.4 36.5 4.5 2.4 37.1 4.4 2.4 80 35.3 4.0 2.6 36.3 4.0 2.6 37.3 4.0 2.7 60 27.3 4.7 1.7 27.7 4.6 1.7 28.1 4.6 1.8 70 30.4 4.4 2.0 31.2 4.3 2.1 32.0 4.3 2.2 80 33.4 4.0 2.4 34.7 4.0 2.5 35.9 4.0 2.7
MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P.
1600 1800 2000
ID CFM
445073-LTG-A-0109
Multipliers for determining the performance with other indoor sections.
Air Handler Coil MBH KW COP
MV20D FC/MC62D 1.00 1.00 1.00 F6FP60 1.00 1.00 1.00
Variable Speed Furnace
L*(8,L)C*C20 FC/MC62D 0.98 0.98 1.00 L*9C*C20 FC/MC62D 0.99 0.97 1.03 L*9C*D20 FC/MC62D 0.99 0.99 1.00
Coil MBH KW COP
Johnson Controls Unitary Products 23
NOTES
Subject to change without notice. Printed in U.S.A. 445073-LTG-A-0109 Copyright © 2008 by Johnson Controls, Inc. All rights reserved. Supersedes: Nothing
Johnson Controls Unitary Products