Luxaire G8D-UH, G8D-DN Installation Instructions Manual

INSTALLATION
MID-EFFICIENCY GAS-FIRED
INSTRUCTION
CONTENTS
GENERAL INFORMATION. . . . . . . . . . . . . . . . . . . . . . . . . 3
UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
VENTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
UPFLOW/HORIZONTAL MODELS - . . . . . . . . . . . . . . . . 10
FILTERS INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . 10
UPFLOW/HORIZONTAL MODELS - . . . . . . . . . . . . . . . . 11
TUBULAR HEAT EXCHANGER SERIES
MODELS: P*DU & G8D-UH (Upflow / Horizontal)
P*DD & G8D-DN (Downflow)
57 - 120 MBH INPUT
DOWNFLOW MODEL APPLICATION . . . . . . . . . . . . . . . 12
OPERATION AND MAINTENANCE. . . . . . . . . . . . . . . . . 23
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
FURNACE ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . 28
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . 29
WIRING DIAGRAM - UPFLOW / HORIZONTAL . . . . . . . 30
WIRING DIAGRAM - DOWNFLOW . . . . . . . . . . . . . . . . . 31
CAUTION: READ ALL SAFETY GUIDES BEFORE YOU
START TO INSTALL YOUR FURNACE.
SAVE THIS MANUAL
FOR YOUR SAFETY
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Open windows.
Do not touch any electrical switch;do not use any phone in your building.
Extinguish any open flame.
Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire depart­ment.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and liq­uids in the vicinity of this or any other appliance.
035-14527-000 REV A (599) Form 650.77-N3U
035-14527-000 REV A (599) Form 650.77-N3U
CONTENTS
GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . 3
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
IMPROPER INSTALLATION MAY CREATE A CONDITION WHERE THE OPERATION OF THE PRODUCT COULD CAUSE PERSONAL INJURY OR PROPERTY DAMAGE.
IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE CAN CAUSE INJURY OR PROPERTY DAMAGE. REFER TO THIS MANUAL FOR ASSISTANCE
NOTES, CAUTIONS & WARNINGS. . . . . . . . . . . . . . . . . . . . . . 3
LIMITATIONS AND LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . 3
UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
COMBUSTION AIR. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
VENTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
CATEGORY I VERTICAL VENTING . . . . . . . . . . . . . . . . . . . . . 6
VENT SAFETY CHECK PROCEDURE . . . . . . . . . . . . . . . . . . . 9
DUCTWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
OR ADDITIONAL INFORMATION, CONSULT A QUALIFIED INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER.
UPFLOW/HORIZONTAL MODELS -. . . . . . . . . . . . . . . . . 10
UPFLOW APPLICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
FILTERS INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . 10
(UPFLOW/HORIZONTAL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
UPFLOW/HORIZONTAL MODELS -. . . . . . . . . . . . . . . . . 11
HORIZONTAL APPLICATION . . . . . . . . . . . . . . . . . . . . . . . . . 11
THIS PRODUCT MUST BE INSTALLED IN
ATTIC INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
CRAWL SPACE INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . 12
STRICT COMPLIANCE WITH THE ENCLOSED INSTALLATION INSTRUCTIONS AND ANY APPLICABLE LOCAL, STATE, AND NATIONAL CODES INCLUDING BUT NOT LIMITED TO, BUILDING, ELECTRICAL AND MECHANICAL CODES.
The furnace area must not be used as a broom closet or for any other storage purposes, as a fire hazard bay be created. Never store items such as the following on, near or in contact with the fur­nace.
1. Spray or aerosol cans, rags, brooms, dust mops, vacuum cleaners or other cleaning tools.
2. Soap powders, bleaches, waxes or other cleaning compounds; plastic items or containers; gasoline, kerosene, cigarette lighter fluid, dry cleaning fluids or other volatile fluid.
3. Paint thinners and other painting compounds.
DOWNFLOW MODEL APPLICATION . . . . . . . . . . . . . . . 12
DOWNFLOW FILTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
SUPPLY AIR DUCTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
GAS PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
ELECTRICAL POWER CONNECTION . . . . . . . . . . . . . . . . . . 14
ELECTRICAL CONTROL CONNECTIONS . . . . . . . . . . . . . . . 14
SAFETY CONTROLS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
START-UP AND ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . 16
IGNITION SYSTEM CHECKOUT/ADJUSTMENT . . . . . . . . . . 17
CHECKING GAS INPUT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
ADJUSTMENT OF MANIFOLD GAS PRESSURE . . . . . . . . . . 18
ADJUSTMENT OF TEMPERATURE RISE . . . . . . . . . . . . . . . 19
ADJUSTMENT OF FAN-OFF CONTROL SETTINGS . . . . . . . 19
ACCESSORY CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . 20
OPERATION AND MAINTENANCE . . . . . . . . . . . . . . . . . 23
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . 23
INTERMITTENT BLOWER - COOLING. . . . . . . . . . . . . . . . . . 23
HEATING OPERATIONAL SEQUENCE . . . . . . . . . . . . . . . . . 23
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
BLOWER CARE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
CLEANING THE HEAT EXCHANGER. . . . . . . . . . . . . . . . . . . 25
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
FURNACE CONTROL DIAGNOSTICS . . . . . . . . . . . . . . . . . . 26
FURNACE ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . 28
4. Paper bags, boxes or other paper products
Never operate the furnace with the blower door removed. To do so could result in serious personal injury and/or equipment damage.
2 Unitary Products Group
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . 29
WIRING DIAGRAM - UPFLOW / HORIZONTAL. . . . . . . . 30
WIRING DIAGRAM - DOWNFLOW . . . . . . . . . . . . . . . . . 31
035-14527-000 REV A (599) Form 650.77-N3U
GENERAL INFORMATION
DESCRIPTION
This Category I furnace is designed for installation in a resi­dential or commercial application. A Category I furnace has a fan assisted combustion system equipped with an integral mechanical means to draw products of combustion through the combustion chamber and heat exchanger. It may be installed in a basement, garage, equipment room, alcove, attic or any other indoor location where all required clear­ances to combustibles and other restrictions are met. It is designed for natural gas-fired operation, but may be con­verted to propane (LP).
High altitude and propane (LP) changes or conversions required in order for the appliance to satisfactorily meet the application must be made by an authorized distributor, dealer, licensed technician or other qualified agency, using factory specified and/or approved parts.
Upflow/horizontal furnaces and downflow furnaces may be used only as Category I units.
The furnace must be installed so that all electrical compo­nents are protected from water.
INSPECTION
As soon as a unit is received, it should be inspected for possi­ble damage during transit. If the damage is evident, the extent of the damage should be noted on the carrier's freight bill.
damage may occur if installation procedures are not handled properly.
Each furnace in this series is a Category I furnace, suitable for common venting with other gas-fired appliances as allowed by the National Fuel Gas Code, NFPA 54/ANSI Z223.1-latest edition
This appliance is not to be used for temporary heating of buildings or structures under construc­tion.
Do not install this furnace in a corrosive or contam­inated atmosphere.
Do not install this furnace in a mobile home or rec­reational vehicle.
Furnaces shall not be installed directly on carpet­ing, tile or other combustible material other than wood flooring.
LIMITATIONS AND LOCATION
This furnace should be installed in accordance with all national/local building/safety codes and requirements, or in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1 - (latest edition) or, in Canada, CAN/CGA B149.1 or.2 - (latest edition), and other applicable codes.
A separate request for inspection by the carrier's agent should be made in writing. Also, before installation, the unit should be checked for screws or bolts which may have loos­ened in transit.
NOTES, CAUTIONS & WARNINGS
The installer should pay particular attention to the words: NOTE, CAUTION and WARNING. NOTES are intended to clarify or make the installation easier. CAUTIONS are given to prevent equipment damage. WARNINGS are given to alert the installer that personal injury and/or equipment or property
Use only the type of gas approved for this furnace; refer to the furnace rating plate.
Only use natural gas in furnaces designed for nat­ural gas. Only use propane (LP) gas for furnaces that have been properly converted to use propane (LP) gas. Do not use this furnace with butane. Using wrong gas could create a hazard, resulting in damage, injury or death.
For installations above 2,000 feet, reduce input 4% for each 1,000 feet above sea level. Canadian installations must be derated 10% for elevations from 2,000 ft. to 4,500 ft. See Form 650.74-N1.1V for information to properly derate fur­nace.
In the U.S. only, furnace shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel.
Unitary Products Group 3
035-14527-000 REV A (599) Form 650.77-N3U
Check the rating plate and power supply to be sure that elec­trical characteristics match. All models use nominal 115 vac, 1phase, 60 Hz. power supply.
A furnace installed in a residential garage must be located so that all burners and burner ignition devices are located no less than 18" above the garage floor, and located or pro­tected to prevent damage by vehicles.
The size of the unit should be based on an acceptable heat loss calculation for the structure. ACCA, Manual J or other approved methods may be used.
The furnace should be located using these guidelines:
1. Where a minimum amount of vent piping and elbows will be required.
2. As centralized with the air distribution as possible.
3. Where adequate combustion air will be available.
4. In an area where ventilation facilities provide for safe lim­its of ambient temperature under normal operating con­ditions.
5. Where it will not interfere with proper air circulation in the confined space.
6. Where the vent will not be blocked or restricted.
7. Where sufficient space is provided to allow proper ser­vice access. Minimum recommended service clearances are as follows:
Twenty-four (24) inches between the front of the fur-
nace and an adjacent wall or another appliance, when access is required for servicing and cleaning.
Eighteen (18) inches at the side where access is
required for passage to the front when servicing or for inspection or replacement of flue/vent connec­tions.
8. Where it will not interfere with the cleaning, servicing or removal of other appliances.
9. Where the following minimum clearances (in inches) to combustibles can be maintained: (Refer to Table1 on page4).
TABLE 1: UNIT CLEARANCES TO COMBUSTIBLES
UPFLOW / HORIZONTAL MODELS - (P*DU & G8D—UH)
APPLICATION TOP FRONT REAR
UPFLOW 1 6 0 0 UPFLOW
B-VENT HORIZONTAL HORIZONTAL
B-VENT
DOWNFLOW MODELS (P&DD & G8D—DN)
APPLICATION TOP FRONT REAR
DOWNFLOW 1 6 0 0 DOWNFLOW
B-VENT
1.
14-1/2” cabinet models only - all other units “0” clearance
2.
14-1/2” cabinet left airflow applications only - all other units and all right hand air flow applications “0” clearance.
3.
Special floor base or air conditioning coil required for use on combustible floor.
4.
Line contact only permitted between lines formed by the intersection of the rear panel and side panel (top in horizontal position) of the furnace jacket and building joists, studs or framing.
1 3 0 0 0 1 COMBUSTIBLE YES YES YES NO
2
6 0 1 0 6 COMBUSTIBLE NO YES YES
3
0 3 0 1 0 1 COMBUSTIBLE NO YES YES
1 3 0 0 0 1
LEFT SIDE
LEFT SIDE
RIGHT
SIDE
1
3
RIGHT
SIDE
1
3
FLUE
FLUE
FLOOR/
BOTTOM
6 COMBUSTIBLE YES YES YES NO
FLOOR/
BOTTOM
6
1"
1"
4
4
CLOSET ALCOVE ATTIC
CLOSET ALCOVE ATTIC
YES YES YES NO
YES YES YES NO
LINE
CONTACT
YES
YES
LINE
CONTACT
3
3
4 Unitary Products Group
035-14527-000 REV A (599) Form 650.77-N3U
UNIT INSTALLATION
COMBUSTION AIR
All installations must comply with Section 5.3, Air for Com­bustion and Ventilation of the National Fuel Gas Code, ANSI Z223.1 or Sections 7.2, 7.3 or 7.4 of CAN/CGA B149.1 or.2 Installation Code - latest editions.
An unconfined space: is not less than 50 cubic feet per 1000 Btu/hr input rating for all appliances installed in that area.
Rooms communicating directly with the space containing the appliances are considered part of the unconfined space, if openings are not furnished with doors.
A confined space: is an area with less than 50 cubic feet per 1000 Btu/hr input rating for all appliances installed in that area.
The following must be considered to obtain proper air for combustion and ventilation in confined spaces.
Air Source from Inside the Building -
Two permanent openings, one within 12 inches of the top of the confined space and one within 12 inches of the bottom, shall each have a free area of not less than one square inch per 1,000 Btuh of total input rating of all appliances located in the space. The openings shall communicate freely with inte­rior areas having adequate infiltration from the outside.
NOTE : At least 100 square inches free area shall be used for each opening.
Air Source from Outdoors -
1. Two permanent openings, one within 12 inches of the top of the confined space and one within 12 inches of the bottom, shall communicate directly, or by means of ducts, with the outdoors or to such crawl or attic spaces that freely communicate with the outdoors.
a. Vertical Ducts - Each opening must have a free
area of not less than one square inch per 4,000 Btuh of total input of all appliances located in the space.
EXAMPLE:
NOTE: Ducts must have the same cross-sectional area as the free area in the opening to which they are connected. The minimum dimension of rectangular ducts shall be three inches.
2. One permanent opening, commencing within 12 inches of the top of the enclosure shall be permitted where the equipment has clearances of at least 1 inch from the sides and back and 6 inches from the front of the appli­ance. The opening shall communicate through a vertical or horizontal duct to the outdoors, or spaces (crawl or attic) that freely communicate with the outdoors and shall have a minimum free area of:
a. 1 sq. in. per 3000 Btu per hr of the total input rating
of all equipment located in the enclosure.
b. Not less than the sum of the areas of all vent con-
nectors in the confined space.
3. Louvers, Grilles and Screens
a. In calculating free area, consideration must be given
to the blocking effects of louvers, grilles and screens.
To estimate free area of a specific louver or grille (Refer to Table2 on page5)..
TABLE 2: ESTIMATED FREE AREA
Wood or Metal
Louvers or Grilles
2
Screens
1.
Do not use less than 1/4 in. mesh
2.
Free area or louvers an grilles varies widely; installer should follow louver or grille manufacturer’s instruc­tions.
Wood 20-25%
Metal 60-70%
1/4 in. mesh or larger 100%
NOTE: If mechanically operated louvers are used, a means to prevent main burner ignition and operation must be pro­vided should louvers close during startup or operation.
Special Combustion and Ventilation Considerations
Operation of a mechanical exhaust, such as an exhaust fan, kitchen ventilation system, clothes dryer or fireplace may cre­ate conditions requiring special attention to avoid unsatisfac­tory operation of gas appliances.
1 1
Total Input of All Appliances
= Square Inches Free Area
4000
b. Horizontal Ducts - Each opening must have a free
area of not less than one square inch per 2,000 Btuh
of total input of all appliances located in the space.
Unitary Products Group 5
Specially Engineered Installations
The above requirements shall be permitted to be waived where special engineering, approved by the authority having jurisdiction, provides an adequate supply of air for combus­tion, ventilation and dilution of flue gases.
035-14527-000 REV A (599) Form 650.77-N3U
Combustion Air Quality
The recommended source of combustion air is to use the out­door air supply. Excessive exposure to contaminated com­bustion air will result in safety and performance related problems. However, the use of indoor air in most applications is acceptable, except as follows:
1. If the furnace is installed in a confined space it is recom­mended that the necessary combustion air come from the outdoors by way of attic, crawl space, air duct or direct opening.
2. If outdoor combustion air is used, there must be no expo­sure to the installations or substances listed in 3" below.
3. The following types of installations may require OUT­DOOR AIR for combustion, due to chemical exposure.
a. Commercial buildings b. Buildings with indoor pools c. Furnaces installed in laundry rooms d. Furnaces installed in hobby or craft rooms e. Furnaces installed near chemical storage areas
Exposure to the following substances in the combustion air supply may also require OUTDOOR AIR for combustion.
VENTING
It is the responsibility of the installer to verify proper vent system operation.
CATEGORY I VERTICAL VENTING
Category I venting consists of vertically venting one or more appliances in B-vent or masonry chimney (as allowed), using single wall metal pipe or B-vent connectors. Type B-vent sys­tem extends in a general vertical direction and does not con­tain offsets exceeding 45 degrees, except that a vent system having not more than one 60-degree offset is permitted.
NOTE: This appliance may be common vented with another gas appliance as allowed by the following codes and stan­dards.
The furnace rating plate lists the maximum vent gas tempera­ture. This temperature must be used to select appropriate venting materials and clearances. A typical example is shown below.
f. Permanent wave solutions g. Chlorinated waxes and cleaners h. Chlorine based swimming pool chemicals i. Water softening chemicals j. De-icing salts or chemicals k. Carbon tetrachloride l. Halogen type refrigerants m. Cleaning solvents (such as perchloroethylene) n. Printing inks, paint removers, varnishes, etc. o. Hydrochloric acids p. Cements and glues q. Antistatic fabric softeners for clothes dryers r. Masonry acid washing chemicals
CATEGORY 1 - 450 F. MAX. VENT TEMP.
All installations must be vented in accordance with the National Fuel Gas Code, NFPA 54/ANSI Z223.1 - latest edi­tion. For reference, the National Fuel Gas Code Handbook, available from NFPA (item JP-54HB96) is recommended. The appliance must also be vented in compliance with all local utility and code requirements. In Canada, the furnace must be vented in accordance with the National Standard of Canada, CAN/CGA-B149.1 and.2 - latest editions.
A furnace shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel.
6 Unitary Products Group
035-14527-000 REV A (599) Form 650.77-N3U
Models P*DU &
G8D—UH
A B C D E F
57 / 46 / 800 / “A” 14-1/2 13-1/4 10-1/8 3 10-1/8 4-3/16 80 / 64 / 1200 / “A” 14-1/2 13-1/4 10-1/8 4 10-1/8 3-3/4 80 / 64 / 1600 / “B” 17-1/2 16-1/4 13-1/8 4 11-5/8 3-3/4
100 / 80 / 1200 / “B” 17-1/2 16-1/4 13-1/8 4 11-5/8 3-3/4
100 / 80 2000 / “C” 21 19-3/4 16-5/8 4 13-3/8 3-3/4
120 / 92 / 1600 / “C” 21 19-3/4 16-5/8 4 13-3/8 3-3/4 120 / 80 / 2000 / “C” 21 19-3/4 16-5/8 4 13-3/8 3-3/4
* Input / Output / CFM / Cabinet
All dimensions are in inches and are approximate
FIGURE 1: 2-STAGE UPFLOW/HORIZONTAL FURNACE DIMENSIONS
TABLE 3: 2-STAGE UPFLOW/HORIZONTAL RATINGS & PHYSICAL/ELECTRICAL DATA
MODELS P* DU & G8D--UH CAB INE T
INPU T
MBH H/L
OUTPUT MBH H/L
NOM.
CFM
WIDTH (IN.)
57/42 46/34 800 “A” 14-1/2 80 25 - 55 35 - 65 165 1/4 9 x 6 9.0 20 14 105 80/59 64/48 1200 “A” 14-1/2 80 30 - 60 40 - 70 175 1/3 10 x 7 9.0 20 14 117
80/59 64/48 1600 “B” 17-1/2 80 25 - 55 25 - 55 160 3/4 11 x 8 12.0 20 14 126 100/65 80/53 1200 “B” 17-1/2 80 25 - 55 40 - 70 170 1/2 10 x 8 12.0 20 14 128 100/65 80/53 2000 “C” 21 80 25 - 55 30 - 60 160 1 11 x 10 12.0 20 14 145 120/78 96/64 1600 “C” 21 80 25 - 55 45 - 75 180 1/2 10 x 10 12.0 20 14 145 120/78 96/64 2000 “C” 21 80 25 - 55 35 - 65 170 1 11 x 10 12.0 20 14 147
1.
AFUE numbers are determined in accordance with DOE test procedures.
2.
Wire size and overcurrent protection must comply with the National Electrical Code (NFPA-70-latest edition).
• For altitudes above 2,000 ft., reduce capacity 4% for each 1,000 ft. above sea level. Refer to Form 650.74-N1.1V.
• Wire size based on copper conductors, 60° C, 3% voltage drop.
• Continuous return air temperature must not be below 55° F.
AFU E
1
LOW FIRE
TEMP RISE
HIGH
°F
FIRE
TEMP
RISE °F
MAX.
OUTLET
AIR TEMP
°F
BLOWER TOTAL
HP SIZE (IN)
UNIT
AMPS
MAX.
OVER-
CUR REN T
PROTECT
MIN WIRE
(AWG) @
2
ONE WA Y
SIZE
75 FT.
2
OPER
WGT.
(L BS )
Unitary Products Group 7
035-14527-000 REV A (599) Form 650.77-N3U
Models P*DD &
G8D—DN
A B C D E F
57 / 46 / 800 / “A” 14-1/2 13-1/4 12-1/4 3 10-1/8 4-3/16 80 / 64 / 1200 / “A” 14-1/2 13-1/4 12-1/4 4 10-1/8 3-3/4 80 / 64 / 1600 / “B” 17-1/2 16-1/4 15-1/4 4 11-5/8 3-3/4
100 / 80 / 1200 / “B” 17-1/2 16-1/4 15-1/4 4 11-5/8 3-3/4
120 / 80 / 2000 / “C” 21 19-3/4 18-3/4 4 13-3/8 3-3/4
* Input / Output / CFM / Cabinet
All dimensions are in inches and are approximate.
FIGURE 2 : 2-STAGE DOWNFLOW FURNACE DIMENSIONS
TABLE 4: 2-STAGE RATINGS & PHYSICAL/ELECTRICAL DATA
M ODE LS P *DD & G8D--DN CABI NET
INPUT
MBH
H/L
OU TPU T
MBH H /L
NOM.
CFM
WIDT H (IN.)
57/42 46/34 800 “A” 14-1/2” 80 20 - 50 30 - 60 160 1/4 10 x 6 9.0 20 14 110 80/59 64/48 1200 “A” 14-1/2” 80 25 - 55 30 - 60 160 1/2 10 x 8 12.0 20 14 120
80/59 64/48 1600 “B” 17-1/2” 80 20 - 50 25 - 55 160 3/4 11 x 10 12.0 20 14 130 100/65 80/52 1200 “B” 17-1/2” 80 25 - 55 40 - 70 170 1/2 10 x 8 12.0 20 14 125 120/78 96/64 2000 “C” 21” 80 25 - 55 30 - 60 160 1 11 x 10 12.0 20 14 150
1.
AFUE numbers are determined in accordance with DOE test procedures.
2.
Wire size and overcurrent protection must comply with the National Electrical Code (NFPA-70-latest edition).
• For altitudes above 2,000 ft., reduce capacity 4% for each 1,000 ft. above sea level. Refer to Form 650.74-N1.1V.
• Wire size based on copper conductors, 60° C, 3% voltage drop.
• Continuous return air temperature must not be below 55° F.
A FUE
1
LOW FIRE
TEMP
R IS E °F
HIGH
FIRE
TEMP
R IS E °F
MAX.
OUT LE T
AIR T EMP
°F
B LOWE R TOTAL
HP SI ZE (IN)
AMPS
UNIT
MAX. OVER-
CUR REN T
PROTECT
MIN WIRE
SIZE (AWG)
2
@ 75 F T.
ONE WA Y
2
OPER
WGT.
(L BS )
8 Unitary Products Group
035-14527-000 REV A (599) Form 650.77-N3U
VENT SAFETY CHECK PROCEDURE
If this furnace is replacing a common-vented fur­nace, it may be necessary to resize the existing vent line and chimney to prevent oversizing prob­lems for the new combination of units. Refer to the National Fuel Gas Code, ANSI Z223.1 or CAN/ CGA B149.1 or.2 Installation Code - latest edi­tions.
The following steps shall be followed with each appliance connected to the venting system placed in operation, while any other appliances connected to the common venting sys­tem are not in operation.
1. Seal any unused openings in the common venting sys­tem.
2. Inspect venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code ANSI Z223.1 or the CAN/CGA B149 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion or other deficiencies which could cause an unsafe condition.
3. Insofar as is practical, close all building doors and win­dows and all doors between the space in which the appli­ance(s) connected to the venting system are located and other spaces of the building. Turn on clothes dryers and any other appliances not connected to the common vent­ing system. Turn on any clothes dryers and any appli­ance not connected to the venting system.
7. If improper venting is observed during any of the above tests, the venting system must be corrected.
8. Any corrections or resizing of the common venting sys­tem must be in accordance with the National Fuel Gas Code, ANSI Z223.1 or Section 7, Venting Systems and Air Supply for Appliances, CAN/CGA B149.1 or.2 Instal­lation Code - latest editions. If the common vent system must be resized, it should be resized to approach the minimum size as determined using the appropriate tables in Appendix G of the above codes or the venting tables supplied with the furnace.
DUCTWORK
The duct system's design and installation must:
1. Handle an air volume appropriate for the served space and within the operating parameters of the furnace spec­ifications.
2. Be installed in accordance with standards of NFPA (National Fire Protection Association) as outlined in NFPA pamphlets 90A and 90B - (latest editions).
3. Create a closed duct system. The supply system must be connected to the furnace outlet and the return duct system must be connected to the furnace inlet. Both sup­ply and return duct systems must terminate outside the space containing the furnace.
4. Generally complete a path for heated or cooled air to cir­culate through the air conditioning and heating equip­ment and to and from the conditioned space.
Turn on any exhaust fans, such as range hoods and bathroom exhausts so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fire­place dampers.
4. Follow the lighting instructions. Place the appliance being operated in operation. Adjust thermostat so appli­ance will operate continuously.
5. Test for draft hood equipped appliance spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle.
6. After it has been determined that each appliance con­nected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliance to their previous conditions of use.
Unitary Products Group 9
The cooling coil must be installed in the supply air duct downstream of the furnace.
When the furnace is used in conjunction with a cooling coil, the furnace must be installed parallel with, or on the upstream side of the cooling unit to avoid condensation in the primary heat exchanger.
When a parallel flow arrangement is used, the dampers or other means used to control air flow must be adequate to pre­vent chilled air from entering the furnace, and if manually operated, must be equipped with means to prevent operating of either unit unless the damper is in the full heat or cool posi­tion.
035-14527-000 REV A (599) Form 650.77-N3U
UPFLOW/HORIZONTAL MODELS -
UPFLOW APPLICATION
Supply Plenum Connection
Attach the supply plenum to the fur­nace outlet duct connection flanges. This is typically through the use of S cleat material when a metal plenum is used. The use of an approved flexible duct connector is recommended on all installations. This connection should be sealed to prevent air leakage.
If a matching cooling coil is used, it may be placed directly on the furnace outlet and sealed to prevent leakage. Follow the coil instructions for installing the supply plenum.
On all installations without a coil, a removable access panel is recommended in the outlet duct such that smoke or reflected light would be observable inside the casing to indi­cate the presence of leaks in the heat exchanger. This access cover shall be attached in such a manner as to pre­vent leaks.
FIGURE 3 : FURNACE FILTER SLOT LOCATIONS
Return Duct Connection
Return air may enter the furnace through the side(s) or bot­tom depending on the type of application. Return air may not be connected into the rear panel of the unit. See the specific type application installation for details. Be sure to see the Fil­ters section of this instruction.
FILTERS INSTALLATION
(UPFLOW/HORIZONTAL)
All applications require the use of a filter. A high velocity filter and retainer are provided for field installation.
Internal Installation
1. Select desired filter position (left/right side, or bottom). Remove the corresponding cabinet cut-outs per instruc­tions provided.
2. Install snap-in retainer clips into the corresponding slots from the outside rear of the cabinet. (Refer to Figure 3 on page10) To prevent cabinet air leaks, install snap-in plugs (provided) into the unused slots at the outside rear of the cabinet.
3. Install the wire retainer inside the cabinet. Insert the open ends of the wire retainer into the clip loops at the rear of the blower compartment. The retainer wire should pivot freely like a hinge, on the clips at the rear of the
FIGURE 4 : SIDE FILTER RETAINER PLACEMENT
4. Install the filter(s) provided. Cut filter if necessary to match air opening in cabinet. Filter should extend beyond opening edge as much as possible to prevent air from bypassing the filter. DO NOT remove stiffening rods from inside the filter. Shorten the rods, if necessary, to match final filter size.
5. Position the filter between the wire retainer and the cabi­net wall (or floor) so it completely covers the cabinet air opening and secure the filter in place at the front of the cabinet by fastening the closed (looped) end of the retainer wire under the flanged edge of the cabinet. When properly installed the filter should fit flush with all four sides of the cabinet wall.
NOTE: Air velocity through throw-away type filters may not exceed 300 feet per minute. All velocities over this require the use of high velocity filters.
10 Unitary Products Group
Loading...
+ 22 hidden pages