Lutz-Jesco TOPAX MC Operating Instructions Manual

Multi-channel controller TOPAX® MC
Dosing
Conveying
Control
s
Operating instructions
Read the operating manual!
BA-46020-02-V01
The user responsible for installation and operation related mistakes!
Liquids Gases System
Multi-Channel Controller TOPAX
Table of Contents
®
MC
Operating instructions
1 Notes for the Reader ..........................................................4
1.1 General non-discrimination ...................................................... 4
1.2 Explanation of the signal words ................................................ 4
1.3 Explanation of the warning signs .............................................. 4
1.4 Identification of warnings ......................................................... 4
1.5 Identification of action instructions ........................................... 4
2 Safety .................................................................................5
2.1 General warnings ..................................................................... 5
2.2 Working in a safety-conscious manner .....................................5
2.3 Personnel qualification .............................................................5
3 Intended use ......................................................................7
3.1 Notes on product warranty ....................................................... 7
3.2 Intended purpose ..................................................................... 7
4 Product description ...........................................................8
4.1 Scope of delivery .....................................................................8
4.2 Design and function ................................................................. 8
4.3 Rating plate ............................................................................. 9
5 Technical data .................................................................. 10
5.1 TOPAX® MC...........................................................................10
5.2 Input modules ........................................................................10
5.3 Output modules .....................................................................11
10 Maintenance ....................................................................33
10.1 Maintenance intervals ..........................................................33
10.2 Keeping logfiles ...................................................................33
10.3 Updating software................................................................33
10.4 Battery change ....................................................................33
10.5 Replacing the fuse ...............................................................34
10.6 Resetting the settings ..........................................................34
10.7 Finishing maintenance .........................................................34
11 Troubleshooting ............................................................... 35
12 Modbus addresses ........................................................... 36
13 EU Declaration of Conformity ........................................... 42
14 Warranty claim .................................................................43
15 Glossary ...........................................................................44
16 Index .................................................................................45
6 Dimensions ......................................................................11
6.1 Outside dimensions ...............................................................11
6.2 Drillhole dimensions ..............................................................11
7 Installation ....................................................................... 12
7.1 Principles ..............................................................................12
7.2 Installation on the wall ...........................................................12
7.3 Electrical installation ..............................................................12
7.4 Terminal connection ...............................................................13
7.5 Connecting sensors ...............................................................14
7.6 Connecting actors ..................................................................15
7.7 Digital inputs .........................................................................16
7.8 RC protection for relay ............................................................16
7.9 Connecting Ethernet ..............................................................17
7.10 RS485-interface ..................................................................17
8 Commissioning ................................................................ 18
8.1 First steps ..............................................................................18
8.2 Configuration .........................................................................19
8.3 Password protection ..............................................................24
8.4 Network settings ....................................................................25
9 Operation ..........................................................................26
9.1 Confirming a message ...........................................................26
9.2 Logbook ................................................................................26
9.3 Viewing the trend display .......................................................27
9.4 Manual mode .........................................................................27
9.5 Adjustment ............................................................................27
9.6 Setpoints and Setpoint sets ....................................................31
9.7 Access via network ................................................................32
© Lutz-Jesco GmbH 2019 Subject to technical changes. 190729
BA-46020-02-V01
Table of Contents
3
Multi-Channel Controller TOPAX
®
1 Notes for the Reader
MC
Operating instructions
This operating manual contains information and behaviour rules for the safe and designated operation of the device.
Observe the following principles:
nRead the entire operating manual prior to starting-up the device. nEnsure that everyone who works with or on the device has read the
operating manual and follows it.
nMaintain the operating manual throughout the service life of the de-
vice.
nPass the operating manual on to any subsequent owner of the device.
1.1 General non-discrimination
In this operating manual, only the male gender is used where grammar allows gender allocation. The purpose of this is to make the text easy to read. Men and women are always referred to equally. We would like to ask female readers for understanding of this text simplification.
1.2 Explanation of the signal words
Different signal words in combination with warning signs are used in this operating manual. Signal words illustrate the gravity of possible injuries if the risk is ignored:
Signal word Meaning
DANGER
WARNING!
CAUTION
Refers to imminent danger. Ignoring this sign may lead to death or the most serious injuries.
Refers to a potentially hazardous situation. Failure to follow this instruction may lead to death or severe injuries.
Refers to a potentially hazardous situation. Failure to follow this instruction may lead to minor injury or damage to property.
1.3 Explanation of the warning signs
Warning signs represent the type and source of a danger:
Warning sign Type of danger
General danger
Danger from electrical voltage
Danger from poisonous substances
Danger of damage to machine or functional
influences
Table 2: Explanation of the warning signs
1.4 Identification of warnings
Warnings are intended to help you recognise risks and avoid negative consequences.
This is how warnings are identified:
Warning sign
Description of danger.
Consequences if ignored.
The arrow signals a safety precaution to be taken to eliminate the
ð
danger.
SIGNAL WORD
NOTE
Table 1: Explanation of the signal words
Notes for the Reader
4
Identification of action instructions
Refers to a danger which, if ignored, may lead to risk to the machine and its function.
1.5 Identification of action instructions
This is how pre-conditions for action are identified:
Pre-condition for action which must be met before taking action.
ü
@A resource such as a tool or auxiliary materials required to perform
the operating instructions.
This is how instructions for action are identified:
èSeparate step with no follow-up action.
1. First step in a series of steps.
2. Second step in a series of steps.
4Result of the above action.
Action completed, aim achieved.
ü
BA-46020-02-V01
© Lutz-Jesco GmbH 2019
Multi-Channel Controller TOPAX
®
MC
2 Safety
2.1 General warnings
The following warnings are intended to help you eliminate the dangers that can arise while handling the device. Risk prevention measures al­ways apply regardless of any specific action.
Safety instructions warning against risks arising from specific activities or situations can be found in the respective sub-chapters.
DANGER
Operating instructions
Hazards due to non-compliance with the safety instructions
Failure to follow the safety instructions may endanger not only persons, but also the environment and the device.
The specific consequences can be:
nFailure of major unit und system functions. nFailure of required maintenance and repair methods. nDanger for individuals through dangerous dosing media. nDanger to the environment from overdosing.
Mortal danger from electric shock!
Incorrectly connected, incorrectly placed and damaged cables can cause injury.
Replace damaged cables immediately.
ð
Do not use extension cables.
ð
Do not bury cables.
ð
Secure cables to avoid being damaged by other equipment.
ð
CAUTION
Increased risk of accidents due to insufficient qualifica­tion of personnel!
The device may only be installed, operated and maintained by person­nel with sufficient qualifications. Insufficient qualification will increase the risk of accidents.
Ensure that all action is taken only by personnel with sufficient and
ð
corresponding qualifications.
Prevent access to the system for unauthorised persons.
ð
NOTE
Do not dispose of the device in the domestic waste!
Do not dispose of electric devices via the domestic waste.
The device and its packaging must be disposed of in accordance
ð
with locally-valid laws and regulations.
Dispose of different materials separately and ensure that they are
ð
recycled.
2.2 Working in a safety-conscious manner
Besides the safety instructions specified in this operating manual, further safety rules apply and must be followed:
nAccident prevention regulations. nSafety and operating provisions. nSafety regulations on handling hazardous substances. nEnvironmental protection provisions. nApplicable standards and legislation.
2.3 Personnel qualification
Any personnel who work on the device must have appropriate special knowledge and skills.
Anybody who works on the device must meet the conditions below:
nAttendance at all the training courses offered by the owner. nPersonal suitability for the respective activity. nSufficient qualification for the respective activity. nTraining in how to handle the device. nKnowledge of safety equipment and the way this equipment functions. nKnowledge of this operating manual, particularly of safety instructions
and sections relevant for the activity.
nKnowledge of fundamental regulations regarding health and safety
and accident prevention.
All persons must generally have the following minimum qualification:
nTraining as specialists to carry out work on the device unsupervised. nSufficient training that they can work on the device under the supervi-
sion and guidance of a trained specialist.
© Lutz-Jesco GmbH 2019 Subject to technical changes. 190729
BA-46020-02-V01
Personnel qualification
Safety
5
Multi-Channel Controller TOPAX
®
MC
These operating instructions differentiate between these user groups:
2.3.1 Specialist staff
Thanks to their professional training, knowledge, experience and knowl­edge of the relevant specifications, specialist staff are able to perform the job allocated to them and recognise and/or eliminate any possible dan­gers by themselves.
2.3.2 Trained electricians
Due to their professional training, knowledge and experience as well as knowledge of specific standards and provisions, trained electricians are able to do the electrical work assigned to them and to recognise and avoid any potential dangers by themselves.
They are specially trained for their specific working environment and are familiar with relevant standards and provisions.
They must comply with the legally binding regulations on accident pre­vention.
2.3.3 Trained persons
Trained persons have received training from the operator about the tasks they are to perform and about the dangers stemming from improper be­haviour.
Trained persons have attended all trainings offered by the operator.
Operating instructions
2.3.4 Personnel tasks
In the table below you can check what qualifications are the pre-condi­tion for the respective tasks. Only people with appropriate qualifications are allowed to perform these tasks!
Qualification Activities
nTransportation nMechanical installation nCommissioning
Specialist staff
Trained electricians
Trained persons
Table 3: Personnel qualification
nTaking out of operation nFault rectification nMaintenance nRepairs nDisposal
nElectrical installation
nControl
Safety
6
Personnel qualification
BA-46020-02-V01
© Lutz-Jesco GmbH 2019
Multi-Channel Controller TOPAX
3 Intended use
®
MC
Operating instructions
3.1 Notes on product warranty
Any non-designated use of the device can impair its function and the pro­tection provided. This leads to invalidation of any warranty claims!
Please note that liability is on the side of the user in the following cases:
nThe device is operated in a manner which is not consistent with these
operating instructions, particularly safety instructions, handling in­structions and the section "Intended Use".
nInformation on usage and environment (section 5 “Technical data” on
page10) is not adhered to.
nIf people operate the device who are not adequately qualified to carry
out their respective activities.
nUnauthorised changes are made to the device.
3.2 Intended purpose
The controller monitors the current measured values during water treat­ment and controls the dosing systems connected for water treatment. In this way, the controller ensures constant water values in various applica­tions and can be deployed universally. One of the main applications is the maintenance of water quality in industry and public swimming pools by measuring and evaluating the water parameters chlorine value, pH value, redox value, total chlorine as well as conductivity and the control of chlo­rine gas dosing systems.
3.2.3 Incorrect operation
nProtective equipment not functioning correctly or dismantled. nUnauthorised modification of the controller. nIgnoring of alarm or error messages. nThe elimination of alarm or error messages by insufficiently-qualified
personnel.
nBridging the external fuse. nDifficult operation due to insufficient lighting or poor access to the de-
vice.
nOperation not possible due to dirty or illegible display.
3.2.4 Incorrect maintenance
nCarrying out maintenance during ongoing operation. nNo adequate or regular inspection of correct functioning. nNo replacement of damaged parts or cables. nNo securing against reactivation during maintenance work. nUse of the wrong spare parts.
Foreseeable misuse
The following section provides information regarding the device applica­tions which are classified as non-intended use. This section is intended to allow you to detect possible misuse in advance and to avoid it.
Foreseeable misuse is assigned to the individual stages of the product lifetime:
3.2.1 Incorrect assembly
nConnecting the mains voltage without a protective earth. nNon-fused or non-standard mains voltage. nNot possible to immediately or easily disconnect the power supply. nWrong connecting cables for mains voltage. nSensors and actors connected to the incorrect terminals or incorrectly
configured.
nProtective earth removed.
3.2.2 Incorrect start-up
nCommissioning with damaged or obsolete sensors. nCommissioning without the establishment of all protective measures,
fastenings etc.
© Lutz-Jesco GmbH 2019 Subject to technical changes. 190729
BA-46020-02-V01
Intended use
Intended purpose
7
Multi-Channel Controller TOPAX
Sensors Input
Control
Output
Actors
®
MC
4 Product description
4.1 Scope of delivery
Please compare the delivery note with the scope of delivery. The follow­ing items are part of the scope of delivery:
nController nOperating instructions nMounting set nSensors (optional) nCable connection from the device to the sensors (optional)
4.2 Design and function
4.2.1 Functional diagram
Operating instructions
modules
Free
chlorine
Current module
Compensation
Disturbance
variable
On/Off
Digital 1
Virtual 1
(Effective chlorine)
pH
pH/Redox
module
Compensation
Fig. 1: Functional diagram of a two-channel controller
Gap Field Description
Sensors
1. Free chlorine
2. Disturbance variable
3. pH
pH /
Temp
system
Controller 1
Disturbance
variable
modules
Module 1
Function
(External stop)
Temp
1. Measuring the free chlorine
2. The disturbance variable is a variable flow volume which can be taken into account
Controller 2
Module 2
3. Measuring the pH value
Input modules
Control system
Output modules
Table 4: Explanation
Product description
8
Design and function
1. Current module
2. Digital 1
3. Virtual 1
4. pH/Redox module
1. Controller 1
2. Controller 2
1. Module 1
2. Module 2
1. Module for 4 − 20 mA signals and sensors with 24 V voltage supply
2. Digital input for the external control of a function (here: external stop)
3. Parameter calculated (here effective chlorine)
4. Module for pH and Redox sensors
1. Controlling the free chlorine inc. pH/temperature compensation and disturbance variable
2. Controlling the pH value inc. temperature compensation
1. Module on slot 1 to connect an actor (here: MAGDOS LD)
2. Module on slot 2 to connect an actor (here: MEMDOS LP)
BA-46020-02-V01
© Lutz-Jesco GmbH 2019
Multi-Channel Controller TOPAX
®
MC
Operating instructions
4.2.2 Functions of the device
The stationary device measures the water values using sensors. Con­trolling actors such as dosing pumps controls the water values to the de­sired setpoint.
4.2.3 Main view
The main menu view will appear upon the start of the device or 5 minutes after the last input. The main view shows the current values from up to four sensors and further information.
1
6
4
Fig. 2: Main view with three sensors
Item Function
1 Login/password settings
2 Date/time
3 Measured values
4 Main menu
5 File Browser
2
3
5
4.3 Rating plate
There is information on the equipment about safety or the product's way of functioning. The information must stay legible for the duration of the service life of the product.
1
2
4
3
Fig. 3: Rating plate TOPAX® MC
Item Description
1 Product name
2 Technical specifications
Label showing conformity with applicable European
3
directives
4 WEEE label
5 Serial number
6 Part number
7 Month/year of manufacture
Table 6: Rating plate
7
6
5
6 Status row for messages
Table 5: Components
© Lutz-Jesco GmbH 2019 Subject to technical changes. 190729
BA-46020-02-V01
Product description
Rating plate
9
Multi-Channel Controller TOPAX
®
MC
5 Technical data
5.1 TOPAX® MC
Information Value
Voltage supply 100 − 240 V AC, 50/60 Hz
Power consumption max. 20 W
Housing dimensions (W x H x D) 302 x 240 x 107 mm
Load capacity of the alarm relay 250 V AC, 8 A (ohmic load)
Analogue outputs for remote transmission 4 x 0/4 − 20 mA, max. 500 Ω
Operating instructions
Disturbance variable input
0/4 − 20 mA Intervention of the disturbance variable, amplification between 0.1 − 10 times
Ethernet Modbus TCP/IP
Interfaces
RS485 Modbus RTU (optional)
Protection class IP65
Ambient temperature -5 to +45 °C
Air humidity max. 95 %, non condensing
Control characteristic
Table 7: Technical data
P, PI, PID or PD behaviour, control direction selectable with disturbance variable feed forward, 2-side control selectable
5.2 Input modules
All input modules consist of an input for temperature measurement via Pt100 and a second input for the measurement of a further water parameter. On some input modules, this input will measure a number of different parameters.
Sampling system Value
Temperature input -10 to +90 °C
Measurement input pH Redox module
pH value pH 0 – pH 14
Redox 0 − 1000 mV
(Free chlorine)
Cl
Measurement input potentiostat module
2
ClO
(Chlorine dioxide)
2
Excess chlorine measuring cell CS120 Measuring range dependant on the slope up to c. 20 mg/l.
Measurement input current module
Diaphragm-covered measuring cell, conductivity or another 0/4−20mA sensor
Voltage current module 24 V
Table 8: Technical data
10
Technical data
Input modules
BA-46020-02-V01
Measuring range dependant on the slope up to c. 18 mg/l.
0/4 − 20 mA, max. 500 Ω
© Lutz-Jesco GmbH 2019
Multi-Channel Controller TOPAX
®
MC
5.3 Output modules
Output Value
Relay module 2 x 230 V AC, 5 A (ohmic resistive load)
Optocoupler module 2 x 80 V DC, 5 mA
Operating instructions
Servomotor relay
Servomotor mA
Table 9: Technical data
6 Dimensions
All dimensions in millimeter (mm).
6.1 Outside dimensions
302
Output 230 V AC, 5 A (ohmic resistive load)
Input 1 − 10 kΩ
Output 0/4− 20 mA, max. working resistance 500 Ω
Input 0/4 − 20 mA
6.2 Drillhole dimensions
267
240
171
Fig. 4: Outside dimensions
© Lutz-Jesco GmbH 2019 Subject to technical changes. 190729
Fig. 5: Dimensions for wall mounting
BA-46020-02-V01
Dimensions
Drillhole dimensions
11
Multi-Channel Controller TOPAX
i
7 Installation
®
MC
Operating instructions
7.1 Principles
Make sure that the installation location complies with the following re­quirements:
nThe display is easily accessible and is visible. nPlan to leave min. 20 cm free space for the installation of the cable
underneath the device. You must be able to install the cable without kinking or damage.
nVarious lines (e.g. voltage supply, data cable and sensitive lines for
measuring purposes) must be installed separately. The different lines should only cross at 90° so as to prevent falsifications.
nElectrical, magnetic and electromagnetic fields affect signal transmis-
sion and can destroy electronic components.
nCompliance with the permissible ambient temperatures (section 5
“Technical data” on page10).
7.2 Installation on the wall
Resources required:
@Assembly kit
@Drill
@Slotted screwdriver
Perform the following steps:
1. Drill the four drillholes for wall mounting. The exact dimensions are stated in section 6 “Dimensions” on page11.
2. Unscrew the screw on the right-hand side of the device and pull out the rod.
4You can now open the device.
3. Open the device and use the screws for wall mounting. Ensure that the device is secured to the wall.
4. Close the device again using the rod.
@Wire end sleeves 0.75 − 2.5 mm²
DANGER
Mortal danger from electric shock!
Improper installation or damaged components of the electrical instal­lation may result in injury.
Ensure that work on the electrical installation is only carried out by
ð
a qualified electrician.
Make sure that work on the eelectrical installation is only carried out
ð
when it is voltage-free.
Ensure that power supply is protected by a residual current circuit
ð
breaker.
Replace damaged cables or components immediately..
ð
1. Fit wire end sleeve to the cable ends if the supply cable does not have them.
2. Open the device housing.
3. Lead the supply cable through a cable screw connection to the un-
derside of the device.
4. Turn the cable screw connection union nut until the line is fixed in the screw connection so that the screws connection performs strain re­lief. Ensure that the feed cable is installed loosely.
5. Connect the voltage supply to the clamps 44 − 52. Observe the divi­sion into protective earth (PE), neutral conductor (N) and the phase (L) on the circuit board.
The device is fitted on the wall.
ü
7.3 Electrical installation
The voltage supply to your device can now be performed via a normal Schuko plug or a control cabinet. Perform the specifications of this sec­tion for devices without a pre-fitted Schuko plug.
Precondition for action:
The device was installed in accordance with section 7.2 Installation
ü
on the wall.
A voltage supply with 100 − 240 V AC (50/60 Hz) is available.
ü
The voltage supply is deactivated before the start and secured
ü
against reactivation.
The housing is open.
ü
Resources required:
@Grounding-type plug
Installation
12
Electrical installation
Fig. 6: Connected voltage supply
Electrically installation
ü
BA-46020-02-V01
Only 3 of 9 clamps are required for connection of the voltage supply. You can use the free clamps to supply further devices with voltage.
The contact load rating amounts to max. 4A.
© Lutz-Jesco GmbH 2019
Multi-Channel Controller TOPAX
7.4 Terminal connection
®
MC
Operating instructions
Input 1
Output 1
Input 2
Input 3
Output 2
Input 4
Output 3
Ethernet
USB
LED outputs
B
A
0/4 – 20mA
8192 3 4 5 6 7 10
111213141516 17181920
Digital inputs
29303132333435 3621222324252627 2837383940
Output 4
Alarm relay
41 42
43
RS485
Fig. 7: Overview of the connection clamps
Terminal Function Description
1 LED output 1 (red) +
2 LED output 1 (green) +
3 LED output 2 (red) +
4 LED output 2 (green) +
5 LED output 3 (red) +
5 V with 220 Ω series resistance for LEDs of the water sampling stations
6 LED output 3 (green) +
7 LED output 4 (red) +
8 LED output 4 (green) +
9 − 10 LED output GND - Ground for the LEDs
11
12 -
13
14 -
15
16 -
17
18 -
19
20 -
Disturbance variable input
Analogue output 1
Analogue output 2
Analogue output 3
Analogue output 4
+
0/4 − 20 mA
+
+
0/4 − 20 mA, max. working resistance 500 Ω
+
+
21 − 36 Digital inputs 1 − 8 Function configurable
37 − 40 Ethernet connection
41 − 43 Alarm relay
44 − 46
47 − 49 Neutral line (N)
Connection supply voltage
Clamps 41+42 normal on Clamps 42+43 normal off
Protective earth (PE)
50 − 52 Phase (L)
Table 10: Terminal connection
47
44
48
45
49 50 51
46
52
Voltage
© Lutz-Jesco GmbH 2019 Subject to technical changes. 190729
BA-46020-02-V01
Installation
Terminal connection
13
Multi-Channel Controller TOPAX
5
®
MC
Operating instructions
7.5 Connecting sensors
Up to four input modules can be connected to the device. A water param­eter and the temperature can be measured with every module.
Precondition for action:
The voltage supply has been disconnected and protected against
ü
re-connection.
The housing is open.
ü
Resources required:
@Sensors
@Connecting cable
Perform the following steps:
1. Lead the cable through one of the cable screw connections on the underside into the interior of the housing.
2. Connect the wires onto the clamp block of the input modules. Comply with the terminal plans in the following sections.
Sensor connection completed.
ü
NOTE
Electronic distortion of the measurement results.
Incorrect installation of the electrical cables can distort the measure­ment results. As a result, the control of connected devices can be faulty.
Do not route the connecting cable parallel to the mains and control
ð
connections, and always with a clearance of at least 15cm. Lay connection junctions at an angle of 90°.
7.5.2 Potentiostat module input circuit board
1 2 3 4 5
Fig. 10: Module for the potentiostats
Terminal Function Sensors
1 Temperature input
2 Temperature input
Resistance thermometer TE110/Pt100
3 Measuring electrode
3 electrode potentiostat4 Counter electrode
5 Reference electrode
Table 12: Terminal connection
7.5.3 Current module input circuit board
A number of sensors require an operating voltage for their measurement. These sensors are connected to the current module and supplied with 24V.
1
2 3 4
Fig. 11: Current module
7.5.1 pH Redox module input circuit board
1 2
3 4
Fig. 8: Module for measuring the pH and Redox
Terminal Function Sensors
1 Temperature input
2 Temperature input
3 - (wire with Ø 1.5 mm)
4 + (wire with Ø 2 mm)
Table 11: Terminal connection
Ø 2
Ø 1,5
Fig. 9: Connect the cable from the pH or Redox sensors correctly
Resistance thermometer TE110/Pt100
pH single-rod measuring chain PE110/rH-single-rod measuring chain ME110
Centre conductor
Screen
Terminal Function Sensors
1 Temperature input
2 Temperature input
3 - -
Resistance thermometer TE110/Pt100
Excess chlorine measuring cell CS120/conductivity
+
4
(for 4 − 20 mA or CS120)
measuring cell
Total chlorine measuring
­cell GCM/diaphragm-cov-
ered measuring cell Cl 4.1/
5 24 V DC output +
diaphragm-covered measuring cell CD 4 MA*
Table 13: Terminal connection
* Requires 24 V supply module
Installation
14
Connecting sensors
BA-46020-02-V01
© Lutz-Jesco GmbH 2019
Multi-Channel Controller TOPAX
®
MC
Operating instructions
7.6 Connecting actors
Depending on the equipment of the device, you have various possibilities of actuating actors such as dosing pumps or regulation valves.
7.6.1 Alarm relay
The alarm relay on the main board forwards alarms.
41 42
Fig. 12: Alarm relay
Terminal Function Description
41 + 42 normal on
42 + 43 normal off
Table 14: Terminal connection
7.6.2 Output circuit board relay
Fig. 13: Output circuit board with relay
43
The relay works on these clamps as an opener.
The relay works on these clamps as a closer.
4 3 2 1
7.6.3 Output circuit board optocoupler
4 3 2 1
Fig. 14: Output circuit board with optocoupler
Terminal Function Description
1 +
Optocoupler X.2 Second digital output
2 -
3 +
Optocoupler X.1 First digital output
4 -
Table 17: Terminal connection
Actors Configuration
MAGDOS dosing pumps
Pulse frequencyMEMDOS dosing pumps
MEMDOS SMART dosing pumps
Table 18: Actors and configuration
7.6.4 Servomotor relay output circuit board
This output is suitable for connecting a servomotor with or without feed­back via a potentiometer from 1 – 10 kΩ.
Terminal Function Description
1
Relay X.2 Second digital output
2
3
Relay X.1 First digital output
4
Table 15: Terminal connection
Actors Configuration
MAGDOS dosing pumps On/Off
MEMDOS dosing pumps On/Off
MEMDOS SMART dosing pumps On/Off
MIDIDOS/MINIDOS dosing pumps On/Off
Peristaltic pumps Pulse length
Table 16: Actors and configuration
6 5
4
Fig. 15: Servomotor relay
Terminal Function Description
1 − 2
Opening the regulation valve
Relay output
2 − 3 Closing the regulation valve Relay output
4
5
6
Table 19: Terminal connection
0 %
Feedback via potentiom­eter
100 %
Actors Configuration
C7700 chlorine control valve
Table 20: Actors and configuration
Servomotor with potentiometer/ servomotor without potentiometer
3
2
1
© Lutz-Jesco GmbH 2019 Subject to technical changes. 190729
BA-46020-02-V01
Installation
Connecting actors
15
Multi-Channel Controller TOPAX
79829_1
EASYCON
®
MC
Operating instructions
7.6.5 Output circuit board servomotor 20 mA
The output connects a servosmotor with or without feedback.
Fig. 16: Output module ATE (20 mA) with feedback
Terminal Function Description
1 - GND
2 Input (feedback) 4 − 20 mA
3 Output 4 − 20 mA
Table 21: Terminal connection 20 mA
Actors Configuration
C7700 chlorine control valve
Servomotor with 20 mA/ continuous output (20 mA)
3. Enter a value between 0 and 100 % and check whether the actor re­acts as desired.
Actor has been tested.
ü
Testing the analogue outputs
3 2 1
You can also test the connection of terminals 13 to 20.
Precondition for action:
The device housing cover is closed.
ü
The voltage supply has been established and the device has been
ü
switched on.
Instruction:
1. Working in the main menu, navigate to System > Outputs > Ana­logue.
4You will now see all analogue outputs (terminals 13 – 20).
2. Press “Test signal”.
3. Set the mA value.
4. Press "Start”.
Analogue outputs tested.
ü
EASYZON chlorine dioxide plant
MAGDOS dosing pumps
MEMDOS dosing pumps
MEMDOS SMART dosing pumps
Table 22: Actors and configuration
7.6.6 Testing the outputs
You can use manual mode to test the correct connection of an actor.
Take the alarm chain into account before conducting the test and inform any connection points or interrupt the alarm chain for the period of the test.
Test the connected actors
Precondition for action:
The actors have been connected in accordance with section 7.6
ü
“Connecting actors” on page15.
The device housing cover is closed.
ü
The voltage supply has been established and the device has been
ü
switched on.
Instruction:
1. Working in the main menu, navigate to “Manual mode” (section 9.4 “Manual mode” on page27).
Continuous output (20 mA)
4You will now see all the outputs.
2. Select the output to which you have connected the actor and which you wish to test.
7.7 Digital inputs
You can use up to 8 digital inputs to evaluate switching statuses and to detect them as alarm message which are to be documented in the log­files.
Further information about the settings of the digital inputs can be found in section 8.2.1.6 “Digital inputs” on page21.
7.8 RC protection for relay
When connecting to the relay, note that inductive loads must be sup­pressed. If this is not possible, the relay contact on the device terminal must be protected by an RC protective circuit/interference suppression element.
If devices with inductive loads from a nominal current of 1 A are connect­ed to a relay, the contacts in the relay may become bonded. Thus, the de­vice will operate in an uncontrolled manner. To prevent bonding if the load circuit suffers a short-circuit, the relays must be protected separately on the maximum relay switching current.
Precondition for action:
You would like to connect an inductive load to the relay.
ü
Instruction:
1. Switch off the device.
2. Clamp the interference suppression element parallel to the inductive
load.
3. Should it prove impossible to perform point 2, clamp the interference suppression element parallel to the relay output.
Installation
16
RC protection for relay
ü
BA-46020-02-V01
RC element clamped.
© Lutz-Jesco GmbH 2019
Multi-Channel Controller TOPAX
i
®
MC
Operating instructions
7.9 Connecting Ethernet
You can use the Ethernet connection for the following actions:
nReading / writing via Modbus TCP/IP protocol (PLC or Computer) nAccess via web browser nAccess via TFTP server
The device is fitted with a network input in the form or a 4-pole and D-coded M12x1 socket. Lutz-Jesco GmbH offers different lengths of spe­cial twisted-pair network cables to make the typical Ethernet RJ-45 plug connection. If you use third-party cables, choose a Category 3 cable with an impedance of 100 Ω or above.
Pin Assignment Wire colours
1 TX- yellow
2 TX+ orange
3 RX- white
4 RX+ blue
- Screen -
Table 23: Ethernet connection socket
Ethernet port
Fig. 17: Ethernet socket
Installing a wired network
During installation, comply with the following points:
nThe Ethernet is cabled in a star topology. The maximum cable length
is 100 m.
nOnly use screened cables and connectors. nOnly use CAT5 cables or better.
7.10 RS485-interface
ON OFF
A B
Fig. 18: Jumper position on RS485
When using multiple devices on a data line, you must activate a 120 Ω resistance on the last device.
You can activate the resistance by setting the jumper to “ON” as shown in Fig. 18.
Your device can have an optional RS485-interface. Using a two-paired data cable you can connect up to 14 devices with a PC or a PLC. Modbus RTU protocol serves as a protocol for data transfer. You can use the ad­dresses 1 to 14. The addresses 0 and 15 are reserved for internal purpos­es and are not supported.
RS485 Modbus settings:
nBaud rate: 9600 nWord length: 8 Bit nStop bit: 1 Bit nParity: None nYou can read out a maximum of 40 addresses at once.
The list of Modbus commands can be found in section 12 “Modbus ad­dresses” on page36.
Perform the following steps:
1. Open the device housing.
2. Connect a two-paired data cable to terminals A and B of the RS485
module.
3. Connect the device with your network.
Device connected with network.
ü
A B
© Lutz-Jesco GmbH 2019 Subject to technical changes. 190729
BA-46020-02-V01
Installation
RS485-interface
17
Multi-Channel Controller TOPAX
i
®
8 Commissioning
Outputs
Relays
Optocoupler
Servomotor
relay
Servomotor
20 mA
x On/Off
x x
x
x
x
x Continuous output
x
Table 24: Functions of the individual controllers
MC
Controller functions Behaviour
nThe output switches if a value is exceeded. nHysteresis can be set from 0.1 – 50 %.
nRelay: 10 – 100 pulses per minute nOptocoupler: 10 – 350 pulses per minute
Pulse frequency or 2 sides pulse frequency
Pulse length or 2 sides pulse length
Servomotor with potentiometer
Servomotor without potentiometer
Servomotor with 20 mA feedback
nThe pulse frequency is dependant on the control deviation and the set control
parameters.
nWith a control output power of Y = 25 % and a maximum pulse frequency of
100pulses/min., the controller would output 25 pulses/min.
n0 – 3600 seconds cycle duration nRelay output (e.g. for solenoid valve) nDepending on the control deviation and the defined control parameters, the relay
pulls in or drops out for the set cycle duration. If the cycle lasts 30 seconds and the controller output power is 40% the relay applies for example for 12 seconds, followed by 18 seconds of non-application.
nA feedback potentiometer can be connected (1 – 10 kΩ) for servomotors with
position feedback.
nCompensate the feedback potentiometer. During compensation, the servomotor is
first started and then stopped automatically.
nFor servomotors without feedback. nMeasure and set the runtime of the servomotor.
nContinuous control output from 0/4 – 20 mA for the actuation of constant actors.
nServomotors which are controlled via 4 – 20 mA and have a 4 – 20 mA position
feedback.
Operating instructions
8.1 First steps
You need to make a number of basic settings before operating the device. This section leads you through initial commissioning.
Precondition for action:
The device has been installed in accordance with section 7 “Installa-
ü
tion” on page12.
Configuration assistant
With initial commissioning, a configuration wizard will lead you through the basic settings: Your preferred language, the measured values, con­troller assignments and switch outputs. With the exception of the lan­guage, the values configured here can only be set in the configuration as­sistant. The finer settings are made in the sub-menus.
Working in the configuration assistant, determine the tasks of the in­stalled modules, the controller and the output modules.
The finer settings such as the behaviour of these modules are made later, e.g in the “Outputs” menu item.
Commissioning
18
First steps
Perform the following steps:
1. Set the preferred language and press on the arrow.
2. Measured values: Determine the desired measured value for the in-
stalled input modules. Press the right-hand arrow.
Controller: You can assign inputs for up to four controllers in this tab.
Select a sensor, a virtual input or a timer. Set the centre row of the control function (Table 24: Functions of the individual controllers) and press the right-hand arrow. Controllers 1 − 4 must be assigned to the output modules 1 − 4 in a fixed fashion.
3. Control output: You can assign a function to outsput modules in this tab. Only the output modules which are still free are displayed. Press the right-hand arrow.
4. Confirm the security query with “Yes” to save the configuration.
The configuration assistant has been ended.
ü
Start the configuration assistant manually in System > Setup > Configuration > “Configuration assistant”.
BA-46020-02-V01
© Lutz-Jesco GmbH 2019
Multi-Channel Controller TOPAX
®
MC
Operating instructions
8.2 Configuration
The device is set up variably and can be individually adapted to meet your requirements. As such, it is necessary to adjust the configuration of the inputs and outputs to the sensors and actors used.
The following section leads you through the device configuration.
8.2.1 Inputs
You can connect up to four sensors for various water parameters and the temperature to the device. You can also use eight digital inputs.
8.2.1.1 Sensors inputs
The sensors in the device must be configured individually to enable pre­cise and error-free measurement of the water parameters. You can per­form various settings.
Perform the following steps:
1. In the main menu, navigate from System > Inputs to the “Sensors” tab.
2. In the “Sensors” tab, configure every connected sensor and state the following information.
3. Input: Select the input module of the sensor which you wish to con­figure.
4. Signal: Enter the type of the sensor signal. Depending on the input module, the signal type has been specified or you can select a signal type.
5. Value: Here, you can check which water parameters are measured. This setting can only be changed in the configuration assistant.
6. Unit: Select the appropriate unit.
7. Measuring range: Enter the maximum measuring range of the sensor.
8. Min-alarm: Activate or deactivate the minimum alarm and state a
value under which the alarm will be triggered.
9. Max-alarm: Activate or deactivate the maximum alarm and state that will trigger the alarm if itis exceeded.
10. Delay: Set a time delay for the minimum and maximum alarm.
Configuration of the sensors completed.
ü
8.2.1.2 Temperature input
You can connect up to four temperature sensors to the device. This ena­bles you to measure the temperatures at various positions.
8.2.1.3 Compensation
The water parameters which you measure with the device can be falsi­fied by interference (e.g. with temperature or pH value).
The device can compensate these interferences automatically.
Perform the following steps:
1. Working in the main menu under System > Inputs, navigate to the “Compensation” tab.
2. Working in the “Compensation” tab, configure every sensor connect­ed for which the measured value is to be compensated and state the following information.
3. Temperature: If it is possible to compensate for the influence of the temperature, you can select a fixed reference value or one of the four temperature inputs.
4. pH value: If it is possible to compensate for the pH value error, you can select a fixed reference value or a sensor input.
Configuration of the compensation completed.
ü
8.2.1.4 Disturbance variable
You can connect the measurement of a disturbance variable (e.g. a flow volume) to an analogue 4 − 20 mA input. The disturbance variable can then be taken into account with a factor (0.1 to 10) during the calculation of the control variable Y. The control variable Y will be multiplied with the disturbance variable during the calculation.
Example: If the factor = 2 and the disturbance variable amounts to 42%, the controller can be set to a maximum of the control variable Y = 84 %. If the factor = 0.5 and the disturbance variable amounts to 42%, the con­troller can be set to a maximum of the control variable Y=21%.
Perform the following steps:
1. Working in the main menu under System > Controller, navigate to the “Flow input” tab and state the following information.
2. Disturbance variable: Set the disturbance variable to an input signal of 4–20mA or 0–20mA. You can also deactivate the disturbance variable.
3. Unit: As a rule, the disturbance variable is the measurement of a flow. Select the desired unit.
Configuration of the disturbance variable input completed.
ü
Perform the following steps:
1. In the main menu under System > Inputs, navigate to the “Tempera­ture” tab.
2. In the “Temperature” tab, configure every connected temperature sensor and state the following information.
3. Measurement: Chose between “On” and “Off”.
4. Min-alarm: Activate or deactivate the “Minimum-alarm” and enter a
temperature under which the alarm will be triggered.
5. Max-alarm: Activate or deactivate the “Maximum-alarm” and enter a temperature to exceed which the alarm will be triggered.
Configuration of the temperature sensors completed.
ü
© Lutz-Jesco GmbH 2019 Subject to technical changes. 190729
BA-46020-02-V01
Commissioning
Configuration
19
Multi-Channel Controller TOPAX


®
MC
Operating instructions
8.2.1.5 Virtual inputs
You can calculate a new value from multiple measurements or reference values using a virtual input. You can assign the new virtual value to a con­troller in the configuration assistant.
In this way, you can calculate a difference, the combined chlorine and the effective chlorine and use them as a basis for controlling your actors.
Difference
You can calculate the difference between two measured values or the dif­ference between a measured value and a fixed reference value.
Perform the following steps:
1. Working in the main menu under System > Inputs, navigate to the “Virtual” tab.
2. State the following information.
3. Calculation: Select “difference”.
4. Select a sensor.
5. Select a second sensor or a reference value. The second sensor must
output the same measured value as the first. You will need to enter the reference value manually.
6. Min-alarm: Activate or deactivate the minimum alarm and state a dif­ference value which, if it falls below a value, will trigger an alarm.
7. Max-alarm: Activate or deactivate the maximum alarm and state a difference value which, if exceeded, will trigger an alarm.
8. Delay: Set a time delay for the minimum and maximum alarm.
Configuration of the difference completed.
ü
Combined chlorine
Combined chlorine is calculated from the difference between the total chlorine and the free chlorine:
Combined chlorine = total chlorine - free chlorine
At least one total chlorine measurement is required to calculate com­bined chlorine. The chlorine value can be entered manually as a single reference value or a corresponding sensor input is selected.
Perform the following steps:
1. Working in the main menu under System > Inputs, navigate to the “Virtual” tab.
2. Working in the “Virtual” tab, configure the desired calculation of the combined chlorine and state the following information.
3. Calculation: Select “Combined chlorine” to calculate the combined chlorine.
4. Total chlorine: Select the sensor which measures the total chlorine.
5. Free chlorine: Select the sensor which measures the free chlorine. If
no sensor is present, you can enter a reference value measured once which can be used for the calculation.
6. Min-alarm: Activate or deactivate the minimum alarm and state a value under which the alarm will be triggered.
7. Max-alarm: Activate or deactivate the maximum alarm and state a value over which the alarm will be triggered.
8. Delay: Set a time delay for the minimum and maximum alarm.
Configuration of the combined chlorine completed.
ü
Effective chlorine
The disinfectant effect of the free chlorine is highly dependant on the pH value of the process water. The pH value influences the reactivity of the Chlorine ions. This relationship is underscored by the dissociation curve (Fig. 19 “Dissociation curve of the effective chlorine” on page 20) of the chlorine.
The actual disinfectant effect of the chlorine is generated by the hy­pochlorous acid (HClO). The figure shows that the proportion of the HClO is largest between pH 2 and pH 7.5. The disinfectant effect is very low outside this pH value.
For photometric measurements the pH value of the sample is buffered to approx. pH 6.5. As a result the measurement has a higher effective chlo­rine content than is actually in the process water. For high pH-values sig­nificant differences will therefore occur between the expected and actual disinfection if assessed by photometric analysis. The calculation of the ef­fective chlorine can be used to display the proportion of the hypochlorous acid (HCIO), i.e. the proportion which contributes to the disinfectant effect.
 
100 %
50
10
0,5
0,1
5
1
  


0





 
































  




2






 
 
 
 








\

I








1















4
6 8




\

\
\
\

\

\



14
12
10
(pH)
     +    + 
+
     
Fig. 19: Dissociation curve of the effective chlorine
+ 
Perform the following steps:
1. Working in the main menu under System > Inputs, navigate to the “Virtual” tab.
2. Working in the “Virtual” tab, configure the desired calculation of the effective chlorine and state the following information.
3. Calculation: Select “effective chlorine” to calculate the effective chlo­rine.
4. Free chlorine: Select the sensor which measures the free chlorine.
5. pH value: Select the sensor which measures the pH value. If no sen-
sor is present, you can enter a reference value measured once which can be used for the calculation.
Commissioning
20
Configuration
BA-46020-02-V01
© Lutz-Jesco GmbH 2019
Multi-Channel Controller TOPAX
®
MC
Operating instructions
6. Temperature: A temperature value is required to calculate the effec­tive chlorine. Select the temperature input which can be used for the calculation. If no temperature sensor is present, you can set a refer­ence value measured once which can be used for the calculation.
7. Min-alarm: Activate or deactivate the minimum alarm and state a value under which the alarm will be triggered.
8. Max-alarm: Activate or deactivate the maximum alarm and state a value over which the alarm will be triggered.
9. Delay: Set a time delay for the minimum and maximum alarm.
Configuration of the calculation of the effective chlorine
ü
completed.
8.2.1.6 Digital inputs
You can use up to 8 digital inputs to evaluate switching statuses and to detect them as alarm message which are to be documented in the log­book.
Perform the following steps:
1. In the main menu under System > Inputs, navigate to the “Digital” tab.
2. In the “Digital” tab, configure the inputs and state the following infor­mation.
3. Action: Choose between “OK = open” (N.O., working contact) or “OK=contact” (N.C., break contact).
4. Function: Select a function from Table 25 depending on the desired reaction of your device to the input.
Function Reaction
Off
Setpoint changeover
Sample water missing All controller outputs will be switched off.
External stop All controller outputs will be switched off.
Pre-alarm 1 − 4
The switching of the contact has no influence on the measurement or control.
You can use the contact to switch between setpoint sets.
Only display as an alarm message. Nothing is switched off.
8.2.2 Outputs
Depending on the equipment, you can connect a range of actors to the device and actuate them. Make sure that you actuate the actor with the correct signal type and select an appropriate output module with the con­figuration.
An alarm relay, four analogue outputs and the possibility of connecting external LEDs (e.g. for water sampling stations) are always available.
8.2.2.1 Controller outputs
You can configure and use up to four controllers.
Precondition for action:
You have used the configuration assistant to assign an input and a
ü
control function to a controller ( “Configuration assistant” on page18).
Perform the following steps:
1. Working in the main menu under System > Outputs, navigate to the “Controller” tab.
2. Working in the “Controller” tab, configure the controller output and state the following information.
3. Y-alarm: Activate the Y alarm. The Y alarm is a safety cut-out. If the controller output power amounts to more than 95% (e.g. through a malfunction) over the set time, the Y alarm will be triggered and the corresponding controller output will be set to 0%. You can set a time between 0 and 200 minutes.
4. Baseload: Depending on the controller function, you can set a base load which is always active independently of the control variable. With a base load of 10 %, the actor is always actuated with a mini­mum of 10 %.
5. Limit: Depending on the controller function, you can set a limit of be­tween 5 − 100 %. State the value at which the actor should be actu­ated as maximum.
6. Further settings are dependant on the function of the controller. Fur­ther information is available in Table 24 “Functions of the individual controllers” on page18.
Configuration of the controller outputs completed.
ü
Master alarm 1 − 4
Others
Table 25: Digital functions
Configuration of the digital inputs completed.
ü
© Lutz-Jesco GmbH 2019 Subject to technical changes. 190729
The appendant controller output is switched off. The other outputs remain unaffected.
You can assign an individual name to this digital input. The name is displayed in the alarm messages during switching the contacts.
8.2.2.2 Actuation via a timer
The output can be used for direct actuation via a timer. This is required e.g. to run the flocculant pump or the peristaltic pumps over a certain time.
Precondition for action:
ü
Perform the following steps:
1. Working in the System menu, navigate to System > Outputs and con-
BA-46020-02-V01
Using the configuration assistant, you have assigned a controller to the “timer” input ( “Configuration assistant” on page18).
figure the output (8.2.2 “Outputs” on page21).
Commissioning
Configuration
21
Multi-Channel Controller TOPAX
®
MC
Operating instructions
2. Navigate to the setpoints menu. Here, you can set the desired set control output directly from 0 to 100 %. Working in the “Setpoint set” tab, you can set various control outputs and via the timers in the “Switch-over” tab, you can determine when the control output should be changed. The checkmark must be set against “Switch set­points automatically”. Further information pertaining to switching is found in section 9.6 “Setpoints and Setpoint sets” on page31.
Actuation configured via a timer.
ü
8.2.2.3 Controller parameters
You can configure the behaviour of the individual controller channels. Ex­planations of the various functions can be found in Table 24 “Functions of the individual controllers” on page18 and in section 15 “Glossary” on page44.
Perform the following steps:
1. Working in the main menu under System > Controller, navigate to the “parameter” tab.
2. Working in the “Parameter” tab, configure every control channel and state the following information.
3. Control direction: Configure the direction of control. If a switch is to be made between a 1- and a 2-side control, this must be set in the configuration assistant.
4. Function: Set the desired controller function. Possible: P-, PI-, PD­and PID controller.
5. Kp, Ki, and Kd: You can configure these parameters depending on the control function that has been set.
6. Disturbance variable and factor: If you have activated a disturbance variable (8.2.1.4 “Disturbance variable” on page 19), you can con­figure the influence of this disturbance variable on the selected con­troller channel. You can switch the influence on or off and set a factor between 0.1 and 10.
Configuration of the controller parameters completed.
ü
8.2.2.4 Digital output signals
You can use digital output signals via the outputs of the alarm relay, an optocoupler circuit board or a relay circuit board. The following sections describe the configurations that you can perform.
6. Output triggers at: Select which alarms should trigger the alarm re­lay. The relay switches as soon as one of the selected alarms is ac­tive.
7. Alarm delay: Determine the earliest point (in seconds) at which the relay should switch after activation of the alarm.
Configuration of the alarm relay completed.
ü
Further alarm outputs
In addition to the alarm relay, you can use the unused outputs of the opto­coupler circuit board or relay circuit boards for further alarm messages.
Precondition for action:
You have used the configuration assistant to assign the “alarm out-
ü
put” function to a free output ( “Configuration assistant” on page18).
Perform the following steps:
1. In the main menu under System > Outputs, navigate to the “Digital” tab.
2. Working under “Digital output” select the desired output.
4The free outputs will be displayed which you have configured as an
“alarm output” in the configuration assistant. Example: “Relay 1.2”. The first digit stands for the number of the output circuit board (1.X) and the second digit stands for the number of the output on the cir­cuit board (X.2).
3. Working under the “Function” display, check whether the function with “alarm output” is displayed.
4. Configure the alarm output by entering the following data.
5. Action: Choose between “normal opened” (N.O., make contact) or
“normal closed” (N.C., break contact).
6. Latching: “On“= the alarm output is active until all alarms have been manually confirmed. “Off” = the output will be deactivated automati­cally if the alarms are no longer active.
7. Output triggers at: Select from the list of all possible alarms those which should trigger the output. The output switches as soon as one of the selected alarms is active.
8. Alarm delay: Determine the earliest point (in seconds) at which the output should switch after activation of the alarm.
Configuration of the alarm output completed.
ü
Alarm relay as an alarm output.
You can use the alarm relay (terminals 41 – 43) on the main board as an output for alarm messages.
Perform the following steps:
1. In the main menu under System > Outputs, navigate to the “Digital” tab.
2. Working under “Digital output”, select the “alarm relay” output.
3. Configure the alarm relay by entering the following data.
4. Action: Choose between “normal opened” (N.O., make contact) or
“normal closed” (N.C., break contact).
5. Latching: “On “= the alarm relay is active until all alarms have been manually confirmed. “Off” = the relay is automatically deactivated if the active alarms are no longer pending.
Commissioning
22
Configuration
BA-46020-02-V01
Limit value control
You can use unused outputs from optocoupler circuit boards or relay cir­cuit boards as a limit value control (including “DIN contact”).
An output for limit value control switches if all measured values are locat­ed within the defined limits.
Precondition for action:
You have used the configuration assistant to assign the “limit value
ü
control” function to a free output ( “Configuration assistant” on page18).
Perform the following steps:
1. In the main menu under System > Outputs, navigate to the “Digital” tab.
© Lutz-Jesco GmbH 2019
Multi-Channel Controller TOPAX
i
®
MC
Operating instructions
2. Working under “Digital output” select the desired output.
4The free outputs will be displayed which you have configured as
“limit value control” in the configuration assistant. Example: “Relay
1.2”. The first digit stands for the number of the output circuit board (1.X) and the second digit stands for the number of the output on the circuit board (X.2).
3. Working in the “Function” display, check whether the function with a “limit value control” is displayed.
4. Configure the limit value control by entering the following data.
5. Action: Choose between “normal opened” (N.O., make contact) or
“normal closed” (N.C., break contact).
6. Delay: The contact switches only if all water parameters are continu­ally over the set lag time within the limits set. The lag time can be set between 0 and 10.
7. Parameter: Set the measured values in which the water parameters must be located so that the output switches. Press the minimum or maximum value that you wish to change.
Configuration of the limit value control completed.
ü
8.2.2.5 Analogue output signals
The basic configuration of the device includes four analogue 4 – 20 mA outputs. You can use the outputs to transmit the measured values to a control room or a PLC (programmable logic controller).
8.2.2.6 Actuation of the LEDs for the water sampling stations
Some water sampling stations have multiple LEDs which display whether a water parameter is in the desired range. You can configure the actuation of the LEDs.
Perform the following steps:
1. Working in the main menu under System > Outputs, navigate to the “External LEDs” tab.
2. Working under “LED”, select the desired LED.
3. Configure the LED by entering the following data.
4. Function: Select the reaction criteria for the LED. Selection of “Sam-
ple water missing” standardly results in a green LED. If the digital contact “Sample water missing” is active, it will illuminate red. Fur­ther options are the measured values of the sensor inputs 1 – 4.
5. Minimum and maximum: If you have decided to use a measured val­ue, you must establish a minimum and a maximum value. The LED will illuminate red if the minimum value is undercut or the maximum value exceeded. It illuminates green between the values.
6. Testsignal: You can test the configuration of the LEDs.
Configuration of the external LED outputs completed.
ü
Some actuators such as dosing pumps can be controlled directly via this output.
Perform the following steps:
1. In the main menu under System > Outputs, navigate to the “Ana­logue” tab.
2. Working under “Analogue”, select the desired output.
3. Configure the analogue output by entering the following data.
4. 20 mA type: You can choose between the following signal types:
4–20mA, 0 – 20 mA, 20 – 4 mA or 20 – 0 mA.
5. Testsignal: You can test the configuration of the analogue outputs. Check the actuation on the external device.
6. Output: Determine what should be outputted on the selected output. You can choose between the measurement and temperature values or outputs (controller outputs).
7. Minimum: Determine a minimum value. The minimum value indi­cates for which measured value the signal is the weakest.
8. Maximum: Determine a maximum value. The maximum value indi­cates for which measured value the signal is the strongest.
The values for “minimum” and “maximum” serve the scaling of the analogue output signal. Example: Sensor 1 has a meas­uring range of 0 − 10 mg/l. 4 − 20 mA was selected as the 20mA type. If the complete sensor measuring range is to be covered by the analogue signal, 0 mg/l should be selected for “Minimum” and 10 mg/l for “Maximum”. At 0 mg/l, a 4 mA signal will be issued; at 10 mg/l a 20 mA signal will be issued.
Configuration of the analogue outputs completed.
ü
© Lutz-Jesco GmbH 2019 Subject to technical changes. 190729
BA-46020-02-V01
Commissioning
Configuration
23
Multi-Channel Controller TOPAX
i
i
®
MC
Operating instructions
8.2.3 Second overview
In the main view, the device shows the measured values of the installed input modules. This display is pre-determined and cannot be changed.
However, you can activate a “second overview” and adapt your needs in­dividually (Fig. 20 “Individual second overview” on page24).
8.2.3.1 Activating the second overview
Perform the following steps:
1. In the main menu under System > Setup, navigate to the “Display” tab.
2. 2. Overview: Activate the second overview with “On”.
3. Number windows: Select how many individual and freely-configur-
able windows should be displayed.
Second overview activated.
ü
8.2.4 Colours of the alarm messages
You can edit the colours of the different messages.
Perform the following steps:
1. In the main menu under System > Setup, navigate to the “Alarm col­our” tab.
2. Look in the “Alarm colour” tab for the message for which you wish to edit the alarm colour.
3. Press on the row of the alarm and then on “Edit”.
4You can chose between four colour fields.
Alarm colour edited.
ü
8.2.5 Save the configuration
You can save your individual configuration and load it later to rectify prob­lems quickly.
Recommendation: Leave the factory-set configuration file un­changed and save your personal configuration in a new file. Given problems with the configuration, this enables you to re­turn to a functioning configuration quickly.
Perform the following steps:
Fig. 20: Individual second overview
8.2.3.2 Configuring the second overview
Perform the following steps:
1. Press the “Main menu” button (bottom left on the display) until the second overview with the individually-settable windows appears.
2. A gear wheel icon is displayed in the top right-hand corner of every window. Press on the icon to configure the selected window and state the following information.
3. Name: Give each window an individual name.
4. Display 1 – 5: Up to five displays can be configured depending on the
size of the window. You can choose between the measured values, the virtual values, the outputs, the setpoints, the disturbance variable, the digital inputs and the external LED outputs.
Configuration of the second overview completed.
ü
1. In the main menu under System > Setup, navigate to the “Configura­tion” tab.
2. Press “save” and enter an existing file name to overwrite the file or a new name to generate a new configuration file.
3. Press on the green checkmark to confirm the entry.
Configuration saved.
ü
8.3 Password protection
The password protection of your device has been deactivated at the fac­tory. You can provide your device with password protection against ac­cess to specific functions in three levels.
n1. Level: Only simple settings are accessible here. This level is suita-
ble for daily operation.
n2. Level: The configuration of the inputs and outputs and the adjust-
ment of the sensors are accessible here. This level is required for de­vice configuration and should only be operated by experienced users.
n3. Level: The service menu is accessible here. This level is mainly re-
quired for maintenance work such as changing the sensor, performing software updates or network settings.
The following passwords are factory-set:
1. Level: 0001
2. Level: 0002
3. Level: 0003
Commissioning
24
Password protection
BA-46020-02-V01
© Lutz-Jesco GmbH 2019
Multi-Channel Controller TOPAX
®
MC
Configuring the password protection
Fig. 21: Configuring the password protection
Perform the following steps:
1. Press the lock icon in the left-hand upper corner to configure the password protection.
2. Password active: Select whether password protection should be acti­vated or deactivated. Password protection can only be deactivated if you are logged in to level 3.
4Password protection must be activated to unlock the following
steps.
3. Select one of the three password levels into which you wish to log on.
4. Login: Login with the password for the password level previously se-
lected.
5. Change password: You can edit the password of the level in which you are logged in.
Operating instructions
Password protection configured.
ü
8.4 Network settings
You may need to perform settings in order to be able to use the device in a network.
Further information about using the device in a network can be found in section 9.7 “Access via network” on page32.
Perform the following steps:
1. In the main menu under System > Service, navigate to the “Network” tab.
2. In the “Network” tab, configure the output and state the following in­formation.
3. IP address: Give the device a unique IP address through which it can be reached in the network. If this IP address is already being used by another device, errors can result.
4. Subnetmask: Enter the subnetmask.
5. TFTP server: “On” = Access via TFTP protocol activated on the device
memory. “OFF” = Access via TFTP protocol de-activated on the de­vice memory.
6. Modbus RTU address: Enter a number between 1 and 14 in the de­vice if your device is fitted with a RS485 network connection.
Network settings performed.
ü
© Lutz-Jesco GmbH 2019 Subject to technical changes. 190729
BA-46020-02-V01
Commissioning
Network settings
25
Multi-Channel Controller TOPAX
i
®
MC
9 Operation
When in operation, the device will display the main view with the current values and the status row with status messages.
Operating instructions
9.2.1 Display the files
You can display the logbook files on the device.
9.1 Confirming a message
You can view device alarm, error and service messages in the status row. The status row flashes in the colour set for the message type. Inactive messages are displayed white.
You must confirm a message on the device to end the display of inactive messages in the status row. Active messages will still be displayed, even if they have been cleared.
Perform the following steps:
1. When a message is displayed, press on the status row or go to the “Reports” menu.
2. Select one or more messages and press either “Confirm” or “Confirm all”.
4The confirmed message is marked with a green tick.
Message confirmed.
ü
History
You can follow the course of the messages in a history.
In the main menu, press “Reportss” and the tab “History”.
9.2 Logbook
Perform the following steps:
1. Press the USB icon in the status row (below right).
4The files saved on the USB flash drive will be displayed in a file
browser.
2. Open one of the file folders.
3. Select the desired file and press “Open file”.
File opened.
ü
9.2.2 Opening files externally
You can open the logbook files on an external device once you have re­moved the USB flash drive.
DANGER
Mortal danger from electric shock!
When the device housing is open, you can touch live parts. There is the danger that you could suffer an electric shock.
Ensure that the device has been disconnected from the voltage sup-
ð
ply and is not live when conducting work with an open housing.
Secure the voltage supply against reactivation.
ð
The messages and service entries are saved in the device on a USB flash drive. You can display the files on the device or connect the USB flash drive to an external device.
The USB flash drive in the device contains the following logbook files:
Log Format Description
REPORTS CSV Messages
TREND DAT Trend data
SERVICE CSV Service entries
CHANGES CSV Changes to the configuration
SETUP SET Configuration
ADJUSTMENT CSV Adjustment
Table 26: Logbook
You can open and analyse CSV files with a suitable programme (e.g. MS Excel). You can also view all CSV files on the device.
Precondition for action:
The voltage supply is deactivated before the start and secured
ü
against reactivation.
Perform the following steps:
1. Open the housing.
2. Remove the USB flash drive.
3. Connect the USB flash drive with an external device and open it.
4You can now access the logbook files.
Files opened.
ü
26
Operation
Logbook
BA-46020-02-V01
© Lutz-Jesco GmbH 2019
Multi-Channel Controller TOPAX
i
®
MC
Operating instructions
9.3 Viewing the trend display
You can view the trend progression of up to four measured values in the last 24 hours.
Perform the following steps:
1. In the main menu, press “Trend”.
4The device will show the trend.
2. You can configure the display in accordance with your wishes. Press the “Display” tab and activate up to four values which are to be dis­played in the trend.
3. You can set the scaling of the individual trend display for every value individually. Press on the “Scaling” tab, select a sensor and define "minimum” and “maximum”.
Trend display configured.
ü
9.4 Manual mode
You can manually control a controller output in the menu item “Manual mode” and set an output capacity between 0 and 100 %.
If a controller is in manual mode, this is indicated by a blue Y display in the main view and by a hand icon.
Working in the menu item “Manual mode”, you can also switch the auto­matic switching of the setpoints on or off (9.6 “Setpoints and Setpoint sets” on page31).
9.5.1 pH
Calibration of the pH electrode can be performed as a 2-point calibration with 2 buffer solutions or a single point calibration with subsequent input of the slope of the sensor.
The actual voltage of the electrode and the ideal value of the set buffer solution is displayed during calibration.
The reaction time of a new electrode amounts to a few seconds and has been set when the physical value has become stable. Older electrodes can have a longer reaction time.
To perform the calibration performed here, you will require a buffer solution with a known pH value. Buffer solutions have a restricted storage life and their pH value changes depending on their duration of storage and the storage conditions.
Comply with the manufacturer’s instructions pertaining to the correct storage; use buffer solutions only within the scope of their life period and never submerge a sensor in a buffer solu­tion immediately after removing it from a different buffer solu­tion.
9.5.1.1 2-point calibration
Pre-conditions for actions:
Two different buffer solutions are ready.
ü
The sensor is clean.
ü
9.5 Adjustment
You must first adjustment the sensors before you can detect the correct measured values. All adjustment processes in the device are monitored for plausibility (zero point and slope) and the measured values document­ed. Measured values resulting from an unadjusted sensor are marked in the main overview. In this case, the measured values are displayed in red. If the measurement input is displayed individually in the main view, the information “Improper adjustment” will be displayed.
The current calibration and slope can be found in the “Adjustment” menu in the “Overview” tab.
Perform the following steps:
1. Working in the Main menu under “Adjustment”, navigate to the “Sen­sors” tab.
2. Working under “sensor”, select the sensor that measures the pH and which you wish to calibrate.
3. Press the “2 points” button.
42-point calibration begins.
4. Shut off the sample water of the sensor block.
5. Unscrew the pH electrode from the sensor block.
6. Rinse the electrode with water and dab it dry. Rubbing can cause
electrical discharge on the glass membrane, which results in a de­layed display.
7. Hold the dry electrode in the first buffer solution. It is not important, which of the two buffer solutions you start with.
8. Enter the pH value of the first buffer solution. This pH value serves as a reference value for the device. The ideal voltage value and the cur­rent voltage value is displayed in mV. If these values deviate too greatly from one another, the best value is displayed red. Too great a level of deviation is an indication that the electrode needs to be re­placed.
9. Wait until the value has stabilised.
10. Confirm the entry with the green checkmark.
11. Repeat point 6 to 10 for the second buffer solution.
12. A window with the actual slope of the sensor will open.
2-point calibration completed.
ü
© Lutz-Jesco GmbH 2019 Subject to technical changes. 190729
BA-46020-02-V01
Operation
Adjustment
27
Multi-Channel Controller TOPAX
i
®
MC
Operating instructions
9.5.1.2 1-point calibration
Pre-conditions for actions:
A buffer solution is on hand for calibration.
ü
The slope of the electrode was measured in a laboratory beforehand.
ü
Perform the following steps:
1. Working in the main menu under “Adjustment”, navigate to the “Sen­sors” tab.
2. Working under “sensor”, select the sensor that measures the pH and which you wish to calibrate.
3. Press the “1 point” button.
41-point calibration begins.
4. Shut off the sample water of the sensor block.
5. Unscrew the pH electrode from the sensor block.
6. Rinse the electrode with water and dab it dry. Rubbing can cause
electrical discharge on the glass membrane, which results in a de­layed display.
7. Hold the electrode in the buffer solution and move back and forth for a short time.
8. Enter the pH value of the buffer solution. This pH value serves as a reference value for the device. The ideal voltage value and the cur­rent voltage value is displayed in mV. If these values deviate too greatly from one another, the best value is displayed red. Too great a level of deviation is an indication that the electrode needs to be re­placed.
9. Wait until the value has stabilised.
10. Confirm the entry with the green checkmark.
11. You will be requested to set the slope. Enter the slope.
12. Confirm the entry with the green checkmark.
1-point calibration completed.
ü
9.5.1.3 Offset compensation
External influences can cause the pH value measured with the photome­ter to deviate from the electrometric measurement of the pH value by a constant value. The offset compensation enables you to compensate for this constant difference (zero-point deviation).
9.5.2 Redox
The Redox value is measured using the Redox sensor. The sensor meas­ures the voltage present in the water due to oxidizing and reducing ions. You must calibrate the sensor during commissioning.
Pre-conditions for actions:
A buffer solution is on hand for calibration.
ü
Perform the following steps:
1. Working in the main menu under “Adjustment”, navigate to the “Sen­sors” tab.
2. Working under “Sensor”, select the sensor that measures the Redox and which you wish to calibrate.
3. Press the “1 point” button.
41-point calibration begins.
4. Shut off the sample water of the sensor block.
5. Unscrew the Redox electrode from the sensor block.
6. Rinse the electrode with water and dab it dry. Rubbing can cause
electrical discharge on the glass membrane, which results in a de­layed display.
7. Hold the electrode in the buffer solution and move back and forth for a short time.
8. Enter the voltage value in mV which is recorded on the buffer solu­tion. The voltage value entered and the current measured voltage value are displayed in mV. If these values deviate too greatly from one another, the best value is displayed red. Too great a level of devi­ation is an indication that the electrode needs to be replaced.
9. Wait until the value has stabilised.
10. Confirm the entry with the green checkmark.
1-point calibration completed.
ü
With older sensors, the reaction time can increase or the measured value can differ considerably from the buffer solu­tion value. This indicates that the Redox sensor must be checked and replaced if necessary.
Perform the following steps:
1. Working in the Main menu under “Adjustment”, navigate to the “Sen­sors” tab.
2. Working under “Sensor”, select the sensor that measures the pH and which you wish to calibrate.
3. Press the “Offset” button.
4. You can enter a pH offset from -0.30 pH to max +0.30 pH.
5. Confirm the entry with the green checkmark.
Offset compensation completed.
ü
Operation
28
Adjustment
BA-46020-02-V01
© Lutz-Jesco GmbH 2019
Multi-Channel Controller TOPAX
i
®
MC
Operating instructions
9.5.3 3-Electrode potentiostat and excess chlorine measuring cell CS120
You should calibrate a 3-electrode potentiostat or the potentiostatic measuring cells (chlorine sensors) as single-point calibration as a matter of course. You will require a photometrically measured value in accord­ance with the DPD method as a reference value.
With operation in a hot water system, electrochemical pro­cesses on the measuring electrode can result in a displace­ment of the zero point. In this case, 2-point calibration is nec­essary in which you calibrate the zero point using chlorine-free hot water. The second point is determined using the DPD method with chlorinated water as usual.
9.5.3.1 1-point calibration
To calibrate chlorine sensors, you will require a photometer with which to measure the reference value using the DPD method.
Pre-conditions for actions:
A measurement device for determining the DPD value is already
ü
present.
The sensor is operated with sample water.
ü
Perform the following steps:
1. Working in the Main menu under “Adjustment”, navigate to the “Sen­sors” tab.
2. Working under “Sensor”, select the sensor that you wish to calibrate.
3. Press the “1 point” button.
41-point calibration begins.
4. Take sample water in immediate proximity to the measuring cell and confirm with “OK”.
5. Determine the concentration in the sample water using the DPD method.
6. Enter the measured concentration. This serves the device as a refer­ence value with which to permit correct measurement.
7. Confirm the entry with the green checkmark.
4. You will be asked to set the first reference value; this is the zero point.
If the zero point was mal-set by accident, set it by pinching off the measuring electrode and entering a value of zero. Should real 2-point calibration be performed, e.g. due to hot water, you must first per­form calibration with chlorine-free and then with chlorinated water. Enter a value for the zero point.
5. Confirm the entry with the green checkmark.
6. Take sample water in immediate proximity to the measuring cell and
confirm with “OK”. This means that the current signal at the time of the sample water extraction is saved to rule out signal fluctuation as a measurement error during the DPD ascertainment.
7. Determine the concentration in the sample water using the DPD method.
8. First enter the determined DPD value.
9. Confirm the entry with the green checkmark.
2-point calibration completed.
ü
9.5.4 Temperature
You can connect a temperature sensor to every input module. You can ad­just the temperature sensor by setting a reference value.
When setting the reference value, the device will automatically correct the measurement of the temperature sensor by the difference.
Pre-conditions for actions:
A thermometer is available.
ü
You have activated the measurement of the temperature (8.2.1.2
ü
“Temperature input” on page19).
Perform the following steps:
1. Working in the Main menu under “Adjustment”, navigate to the “Temperature” tab.
2. Working under “input”, select the input module for which you wish to set a reference value.
3. Press the “Reference value” button.
4. Enter the reference temperature measured beforehand.
5. Confirm with the green checkmark.
1-point calibration completed.
ü
9.5.3.2 2-point calibration
Pre-conditions for actions:
A measurement device for determining the DPD value is already
ü
present.
The sensor is operated with sample water.
ü
Perform the following steps:
1. Working in the main menu under “Adjustment”, navigate to the “Sen­sors” tab.
2. Working under “Sensor”, select the sensor that you wish to calibrate.
3. Press the “2 points” button.
Calibration completed.
ü
42-point calibration begins.
© Lutz-Jesco GmbH 2019 Subject to technical changes. 190729
BA-46020-02-V01
Operation
Adjustment
29
Multi-Channel Controller TOPAX
®
MC
Operating instructions
9.5.5 Servomotor relay
9.5.5.1 Servomotor with position feedback
You can connect servomotors with a position feedback to your device and control them via an output. Before you can control the servomotor exact­ly, you must first adjust the control via your device and the position of the servomotor.
During adjustment, the servomotor is first driven to the end position and then back.
This section only applies to servomotors with a feedback potentiometer.
Pre-conditions for actions:
The servomotor is switched on and has been connected properly.
ü
The output has been configured correctly (Table 24 “Functions of the
ü
individual controllers” on page18).
Perform the following steps:
1. Working in the Main menu under “Adjustment”, navigate to the “Out­puts” tab.
2. Working under “Output”, select the output which is to be adjusted.
3. Press the “Setup servo motor” button.
4. A further window with a progress bar opens; this indicates the posi-
tion feedback.
5. Adjustment is started using the “Start” button.
4The motor now opens up completely and closes again. This can take
a number of minutes.
6. Completion of the adjustment is signalled with “Adjustment OK”.
Adjustment completed.
ü
9.5.5.2 Servomotor without position feedback
You can actuate servomotors without a position feedback. To this end, you need to measure how quickly the motor starts and then set the controller accordingly.
6. Deactivate manual mode with “Off”.
7. Working in the main menu under “Outputs” navigate to the “Control-
ler” tab.
8. Working under “Output”, select the output of the runtime which you have just measured.
9. Working under “Runtime”, enter the time which you have just meas­ured.
Runtime set.
ü
9.5.6 Servomotor mA
You can connect servomotors with a 20 mA actuation and a 20 mA feed­back to the device. The servomotors must be calibrated with the actua­tion before commissioning. You can calibrate the 20 mA output signal with ±1 mA.
9.5.6.1 Correction
Pre-conditions for actions:
The servomotor is switched on and has been connected properly.
ü
The output has been configured correctly (Table 24 “Functions of the
ü
individual controllers” on page18).
Perform the following steps:
1. Working in the Main menu under “Adjustment”, navigate to the “Out­puts” tab.
2. Working under “Output”, select the output which is to be adjusted.
3. Press the “Correction” button.
4A further window with a progress bar opens; this indicates the posi-
tion feedback.
4. Adjustment is started using the “Start” button.
5. The motor starts and opens up, then stops. This can take a number of
minutes.
6. Completion of the adjustment is signalled with “Adjustment OK”.
Correction completed.
ü
Precondition for action:
The servomotor is switched on and has been connected properly.
ü
The output has been configured correctly (Table 24 “Functions of the
ü
individual controllers” on page18).
@Timer
Perform the following steps:
1. Working in the main menu, navigate to the “Manual mode” menu item.
2. Activate the manual mode of the output with “On” and set the control output as 0 %.
4The servomotor closes completely.
3. Observe the drive and wait until it has closed completely.
4. Set the output to 100 % and at the same time, start to measure the
time for the complete opening of the drive.
4The servomotor now starts and opens up.
5. Observe the drive and wait until it opened up completely.
30
Operation
Adjustment
BA-46020-02-V01
9.5.6.2 Calibrating the 20 mA output
If, whilst performing the previous compensation, you have determined that the output signal does not completely conform with the motor posi­tion, you can adjust the output signal. You can adjust both the lower signal range (0/4 mA) and the upper signal range (20 mA) to the motor position.
Perform the following steps:
1. Working in the Main menu under “Adjustment”, navigate to the “Out­puts” tab.
2. Working under “Outputs”, select the output that you wish to adjust.
3. Press the “1 point” button to calibrate just the upper area or the “2
points” button for the upper and lower areas.
4A further window will open in which you can set a tolerance. You can
change this by maximum -50 to +50 depending on whether you wish to calibrate the upper or lower area. The maximum change cor­responds c. to a current of 1 mA.
© Lutz-Jesco GmbH 2019
Multi-Channel Controller TOPAX
®
MC
Operating instructions
4. Check the output signal using a multimeter or a servomotor and make sure that the motor is now under exact control.
5. Save the current offset by pressing the “Save” button.
Calibration completed.
ü
9.6 Setpoints and Setpoint sets
You can determine various setpoints which should actuate the device. You have four different sets of setpoints; the controller can switch between them automatically. The setpoint sets can be used to vary the control at different times of the day or in different operating conditions.
The following section describes the possibilities of controlling using set­points and their configuration.
9.6.1 Setting the setpoints
You can configure and save the setpoints via the menu item “Setpoints”.
Perform the following steps:
1. Working in the main menu under “Setpoints” navigate to the “Active” tab.
2. Active: You can view the setpoint set currently active in the “Active” tab.
4The individual setpoints are displayed. If you change one of the val-
ues, it will immediately be activated as a new setpoint.
3. Save: You can save the active setpoints as a setpoint set. Select a setpoint set for this and press “Save".
4. Setpoints 1 − 4: The possible setpoints for the controller follow in se­quence. The following information is displayed from left to right:
- S1 − S4/V1 − V4 indicates the sensor input or virtual input.
- O1 − O4 indicates the output. The “timer” indicates that the output is actuated directly.
- This is followed by the measured value of this input, e.g. free chlo­rine, pH or the text “No output” if this controller is inactive.
An upwards or downwards arrow indicates the control direction. Raise or lower.
- This is followed by the setpoint. Pressing on the setpoint enables you to change it immediately. If it is a 2-side control, two setpoints must be entered. Both for the control direction “Lift” or “Lower”. Changing these setpoints does not have an impact on the savable setpoint sets. To do so, you must perform step 3.
5. Flow rate: You can activate or deactivate the flow. This enables you to reduce the flow by between 0 % − 100 %. The value of the flow is multiplied with the output Y. If the output is e.g. 80 % but the flow is only 50 %, this produces an output capacity of: Control variable Y=80 % ∙ 50 % = 40 %.
2. Select the desired setpoint set.
3. Press "Load”.
4The desired setpoint set is active immediately.
Setpoint set loaded.
ü
9.6.3 Switching between setpoints
The setpoint sets set in the previous section can be switched manually or automatically. You have two possibilities to activate automatic switching.
1. Working in the “Setpoints” menu item, navigate to the “Switch-over” tab. Set a checkmark against “Switch setpoints automatically”.
2. Working in the “Manual mode” menu, set a checkmark against “Switch setpoints automatically”.
You can use a digital input (9.6.3.1 “Switching via digital input” on page 31) and multiple internal timers (9.6.3.2 “Switching via tim­er-switch” on page 32) for automatic switching. The switching via a digital input has priority. Switching via a timer only occurs if no switching is active via a digital input.
9.6.3.1 Switching via digital input
Before you can use a digital input for switching to a particular setpoint set, you must configure the digital input in accordance with section
8.2.1.6 “Digital inputs” on page21.
Switching can be performed in three different forms: externally-con­trolled switching; switching via an internal timer and the “ECO control” function, which includes the limit value control.
External switching
In the case of external actuation, switching to the desired setpoint set is performed as long as the digital input has been activated.
If the digital input is deactivated, the device switches back to the previous setpoint set.
To configure, working in the “Setpoints” menu item, select the “Switch­over” tab and perform the following steps:
1. Configure the switching and state the following information.
2. Automatically switching the setpoint sets: Set a checkmark here.
3. Switch-over: Select “Digital input”.
4. Function: Select the point “External switching”.
5. Setpoint set: Select the setpoint set to which is to be switched.
6. Digital input: The digital input in use is indicated here.
Configuration completed.
ü
Setpoints set.
ü
9.6.2 Loading setpoint sets
You can load a setpoint set.
Perform the following steps:
1. Working in the main menu under “Setpoints”, navigate to the “Set­point set” tab.
© Lutz-Jesco GmbH 2019 Subject to technical changes. 190729
BA-46020-02-V01
Switching via a timer
During switching via a timer, the desired setpoint set is active until the set period has been completed. The previous setpoint set is re-activated after the time has elapsed.
You can also start the timer manually, thereby e.g. triggering shock chlo­rination.
To configure, working in the “Setpoints” menu item, select the “Switch­over” tab and perform the following steps:
Setpoints and Setpoint sets
Operation
31
Multi-Channel Controller TOPAX
i
®
MC
Operating instructions
1. Configure the switching and state the following information.
2. Automatically switching the setpoint sets: Set a checkmark here.
3. Switch-over: Select “Digital input”.
4. Function: Go to “Timer“.
5. Setpoint set: Select the setpoint set to which is to be switched.
6. Digital input: The digital input in use is indicated here.
7. Time: Configure the timer to the desired duration.
8. “Off” or “Active”: It will be displayed here whether the timer is cur-
rently active. If this is the case, the display will show how long it is still active.
9. “Start” and “Stop” button: The timer can be started or stopped manu­ally. For example, for a shock chlorination.
Configuration completed.
ü
Switching via ECO control
A limit value control is defined for the "Eco control”. The limit value con­trol is generally used to reduce the circulation capacity.
If the measured values are located within the setpoints, the output is closed. If the digital input is also switched for switching to another set­point set, “Economy mode” is active and the switch will be made to the desired setpoint set.
Precondition for action:
The limit value control is configured as described in section “Limit
ü
value control” on page22.
To configure, working in the “Setpoints” menu item, select the “Switch­ing” tab and perform the following steps:
1. Automatically switching the setpoint sets: Set a checkmark here.
2. Switch-over: Select “Switching input”.
3. Function: Select “ECO control”.
4. Setpoint set: Select the setpoint set to which is to be switched.
5. Digital input: The digital input in use is indicated here.
Configuration completed.
ü
9.6.3.2 Switching via timer-switch
Up to ten switches can be configured parallel to the switching via a digital switching input (9.6.3.1 “Switching via digital input” on page 31). Times are defined for the point at which the switches should switch to a certain setpoint set.
6. Setpoint set: Select the setpoint set to which is to be switched.
Configuration completed.
ü
9.7 Access via network
Accessing the device via a network requires that it is connected to an ex­isting Ethernet or RS485 network.
Further information about connection to an existing network is specified in sections 7.9 “Connecting Ethernet” on page 17, 7.10 “RS485-inter­face” on page17 and 8.4 “Network settings” on page25.
If connection problems are experienced during access via net­work, check the configuration of your security software.
Modbus
You can access certain data on the device via the Modbus protocol using both Ethernet and the RS485. You need the Modbus protocol e.g. For the connection with a control panel or a PLC. Modbus TCP/IP is supported for Ethernet and Modbus RTU is supported for the RS485 interface.
The Modbus addresses of your device are stated in section 12 “Modbus addresses” on page36.
Web browser (only Ethernet)
You can access the device data using all network devices which are fitted with a web browser. You will require the IP address, subnetmask and pos­sibly the MAC address of the device.
The network settings of your device are listed under Main menu > Sys­tem > Service > Network.
Open the web browser of your end device and enter the IP address of the device in the address row. The page of the device will open and provide a range of information.
TFTP protocol (only Ethernet)
You can access the device memory via a TFTP client software as long as TFTP is activated in the network settings. You need the device IP address for access.
The network settings of your device are listed under Main menu > Sys­tem > Service > Network.
To configure, working in the “Setpoints” menu item, select the “Switch­ing” tab and perform the following steps:
1. Automatically switching the setpoint sets: Set a checkmark here.
2. Switch-over: Configure up to ten timer switches and state the follow-
ing information.
3. Off/On: Switch on the timer.
4. Time: Configure a time at which the switch-over is to be made. State
the hour and minutes.
5. Monday - Sunday: Set a checkmark against every weekday on which the timer should be active.
Operation
32
Access via network
BA-46020-02-V01
© Lutz-Jesco GmbH 2019
Multi-Channel Controller TOPAX
i
10 Maintenance
®
MC
Operating instructions
Products by Lutz-Jesco are manufactured to the highest quality stand­ards and have a long service life. However, some parts are subject to op­erational wear. This means that regular visual inspections are necessary to ensure a long operating life. Regular maintenance will protect the de­vice from operation interruptions.
10.1 Maintenance intervals
This table gives you an overview of maintenance work and the intervals at which you must carry it out. The next few sections contain instructions for carrying out this work.
Interval Maintenance
nVisual check
Monthly
Table 27: Maintenance intervals
nTouchscreen function test nCalibrating the measured values
10.2 Keeping logfiles
If you make an entry in the logfiles, the device will issue a reminder when a sensor needs to be replaced.
Perform the following steps:
10.4 Battery change
The device is fitted with a button cell. Check the button cell within the scope of the annual maintenance. The lifetime of the button cell is deter­mined by the device usage and can vary considerably.
You will need to replace the battery more often with devices which are switched off often or over a long period (e.g. over winter).
Fig. 22: CR1220 button cell
10.4.1 Checking the charge
You can check the battery charge easily using the device. Replace the battery if the charge amounts to less than 2.9V.
1. Working in the main menu, navigate to System > Service > Service entry and working under “Service entry”/“Sensor”, select the de­sired sensor.
2. Enter the serial number in the tab and the manufacturing company of the sensor.
3. Activate the reminder function and enter a date for the next sensor change.
Logfiles maintained.
ü
10.3 Updating software
The most up-to-date firmware version can be downloaded from www.Lutz-Jesco.com. Copy this *.BIN file onto the de­vice USB flash drive. The file must be saved in the root directo­ry of the USB flashdrive and may not be stored in a sub-folder.
You can update the device software to a newer version.
Perform the following steps:
1. Working in the main menu, navigate to System > Service > Device.
2. Press “Software update”.
3. Select the *.BIN file with the newer version and press “Load“.
4The software is installed. The device will restart automatically during
this procedure.
Update performed.
ü
èWorking in the main menu, navigate to System > Information > Sys-
tem values and read the current charge state of the battery.
10.4.2 Replace the battery
You must remove the two input circuit boards to be able to replace the battery (Fig. 22 “CR1220 button cell” on page33).
Precondition for action:
The voltage supply has been disconnected and protected against
ü
re-connection.
The housing is open.
ü
Resources required:
@Socket wrench 5.5mm (M3)
@New battery: CR1220, Ø12,5 mm, 3 V, 35 mAh
Perform the following steps:
1. Pull all cable connections from the input circuit boards which you need to dismantle.
2. Using the socket wrench, unscrew the retaining nuts from the white protective plate and remove the plate.
3. Using the socket wrench, unscrew the two nuts from the input circuit boards which you need to remove.
4. Working carefully, slide the input circuit boards from their brackets.
4The battery is now easily accessible.
5. Lever the battery out of its holder without damaging the contact bow.
6. Slide a new battery in the holder.
The battery has been changed.
ü
© Lutz-Jesco GmbH 2019 Subject to technical changes. 190729
BA-46020-02-V01
Maintenance
Battery change
33
Multi-Channel Controller TOPAX
i
®
MC
Operating instructions
10.5 Replacing the fuse
Your device is fitted with an electrical fuse to protect against short circuits or over-voltage. You can change the fuse if it is defective.
44
Fig. 23: Position of the fuse
Precondition for action:
The voltage supply has been disconnected and protected against
ü
re-connection.
The housing is open.
ü
Resources required:
47
45
48
46
49 50 51
52
Internal fuse
@Slotted screwdriver
@New fuse: 5 x 20 mm, 3.15 A, 250 V (delay)
Perform the following steps:
1. The fuse holder in the form of a bayonet catch is located at the bot­tom right-hand side, above the clamps for PE, N and L with the mark­ing “Fuse”. Use the slotted screwdriver to press the catch down­wards and then turn it leftwards.
2. Remove the fuse.
3. Replace the fuse and fix it in place by turning the catch clockwise.
Fuse has been replaced.
ü
10.6 Resetting the settings
3. Confirm with “Yes”.
4The configuration will be deleted. You must proceed with the follow-
ing section.
All factory default settings will be reset.
ü
Reset the configuration
The device configuration will be saved in *.SET files. A factory-set config­uration file with standard settings is already present. You can change these or save your personal configuration in new files.
Recommendation: Leave the factory-set configuration file unchanged and save your personal configuration in a new file. Given problems with the configuration, this enables you to return to a functioning configuration quickly.
Perform the following steps:
1. Working in the main menu, navigate to System > Settings > Configu­ration.
2. Select an existing configuration file.
3. Click “Load” to confirm.
4The device configuration returns to the saved state.
Load the old configuration.
ü
10.7 Finishing maintenance
Perform the following steps:
1. Make a note of the date and scope of the maintenance performed.
2. In the “Service” menu, navigate to the “Service entry” tab. Enter your
company name and notes about the maintenance. Activate the re­minder function and enter a date for the next service. Confirm with the “Save” button .
4Your service action has been saved in the logfiles.
3. To restart the system, proceed in accordance with the instructions in section 8 “Commissioning” on page18.
The instructions differentiate between the internal factory set­tings and the device configuration.
The factory settings contain the basic configuration of the de­vice hardware and cannot be changed.
The configuration file (*.SET) contains the individual device configuration. You can change, save and load the individual settings.
Reset to the factory settings
You can now reset the device to its factory settings. This deletes the con­figuration. You must then either load a configuration file or perform the configuration manually.
Perform the following steps:
1. Working in the main menu, navigate to System > Service > Device.
2. Press “factory settings”.
Maintenance
34
Finishing maintenance
ü
BA-46020-02-V01
Maintenance completed.
© Lutz-Jesco GmbH 2019
Multi-Channel Controller TOPAX
®
MC
Operating instructions
11 Troubleshooting
See below for information about how to rectify faults on the device or the system. If you cannot eliminate the fault, please consult with the manufacturer on further measures or return the device for repair.
Fault Possible cause Remedy
nCheck that the battery is really empty. To do
so, navigate to the menu System >
The device loses all settings after it has been disconnected from the voltage network and then reconnected.
The device is off.
The sensor error is displayed as an alarm.
Table 28: Troubleshooting
The battery is empty.
The power supply has been interrupted. Restore the power supply.
The device fuse is defective.
The sensor has not been installed correctly.
The signal cable to the sensor has a break. Replace the signal cable.
Information > System values. You can view the battery voltage under “Battery”. If the voltage is under 2.9 V, change the battery.
nReplace the battery (section 10.4 “Battery
change” on page33)
Replace the fuse (section 10.5 “Replacing the fuse” on page34)
Make sure that the sensor has been connected correctly (section 7.5 “Connecting sensors” on page14)
© Lutz-Jesco GmbH 2019 Subject to technical changes. 190729
BA-46020-02-V01
Troubleshooting
Finishing maintenance
35
Multi-Channel Controller TOPAX
®
MC
12 Modbus addresses
With a DOUBLE-WORD, the HIGH-WORD is transferred first! Hexadecimal display is shown by a leading “0x”.
Operating instructions
Address
Description Meaning
Read
Write
Data that are not channel-related.
4 x Device type + version
6 – 8 x Software Version:
10 – 11 x Operating hours
13 x Hardware version
2000 – 2002 x Serial number
2003 x Status of the digital inputs
2004 x Status digital outputs
0x0500 + (number of channels -1) A single-channel controller accordingly has the identification: 0x0500
Transfer: ASCII sign e.g. 102 is the software version V1.02
The information consists of a ASCII sign in HIGH-BYTE and one in LOW-BYTE
Serial number: 123456 will thus be transferred as Address 2000: 0x3132 Address 2001: 0x3334 Address 2002: 0x3536
Displays the terminal logic (not the configured software function). The individual bits are assigned directly to the input clamps. Example: 0x01 means that the first digital inputs (clamps 21 + 22) are
actuated.
The individual bits of the output modules. Example: 0x03 means that the upper relay or the upper optocoupler of
the second output module (from the top) is active.
2008 – 2017 x x Name of the device
Table 29: Modbus addresses
Max. of 20 characters Caution! The evaluation must stop at the first zero (string end). The individual letters are located in the HIGH-BYTE and LOW-BYTE of
every address. “GW” thus produces: Address 2008 = 0x4757 Address 2009 = 0x00?? The question marks are undefined. In this case, all other addresses send undefined values.
Modbus addresses
36
BA-46020-02-V01
© Lutz-Jesco GmbH 2019
Multi-Channel Controller TOPAX
®
MC
Operating instructions
Address
Description Meaning
Read
Write
Input-related data. 20 addresses will be held available for each of the 1 to 4 inputs. The address space for the inputs begins at 2020, 2040, 2060 and 2080.
n1 = pH n2 = Redox n3 = Free chlorine n4 = Total chlorine n5 = Chlorine dioxide n6 = Bromine n7 = Chlorite n8 = Hydrogen peroxide
2020 x Medium
n9 = Ozone n10 = Bromite n11 = Fluoride n12 = Salt content n13 = Conductivity n14 = Current n15 = Temperature n16 = Neutral (0 - 100%) n254 = Free entry n255 = No type
2021 – 2022 x Measurement
2023 x Unit
2024 x The assigned input of the controller
Table 29: Modbus addresses
Number of positions after the decimal point, see unit (4 bytes signed int).
Number Unit Decimal places
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
n0 = Sensor 1 n1 = Sensor 2 n2 = Sensor 3 n3 = Sensor 4 n4 = Virtual input 1 n5 = Virtual input 2 n6 = Virtual input 3 n7 = Virtual input 4 n8 = Timer switch
mA µA ppm mg/l µS/cm mS/cm % mV pH min s mV/pH Pulses/min. Fahrenheit Celsius
2 1 2 2 2 2 2 1 2 0 0 1 0 1 1
© Lutz-Jesco GmbH 2019 Subject to technical changes. 190729
BA-46020-02-V01
Modbus addresses
37
Multi-Channel Controller TOPAX
®
MC
Operating instructions
Address
Description Meaning
Read
Write
x Control output Y (active control)
2025
500 = 50,0 % (2 Byte signed int)
x x Control output Y (only manual mode)
2026
x Control output 2 Y2 (active control)
x x Control output 2 Y2 (only manual mode)
2027 – 2028 x x Setpoint 1
500 = 50,0 % (2 Byte signed int) Second side if 2-side control is active.
Number of positions after the decimal point, see unit (4 bytes signed int).
2029 – 2030 x x Setpoint 2 If 2-side control is active (4 byte signed int).
2031 x x Kp
Number of positions after the decimal point, see unit (2 bytes unsigned int).
2032 x x Kd Derivative time in s (2 byte unsigned int).
2033 x x Ki Reset time in s (2 byte unsigned int).
Read: Bit 0 = minimum alarm is active Bit 1 = maximum alarm is active
Read: Bit 0 = Y alarm is inactive Bit 1 = Y alarm is active
2034 x x Minimum and maximum alarm
2035 x x Y alarm
Write: 0 = clear alarm
Write: 0 = clear alarm
2036 x x Manual mode
Bit 0: Manual mode on Bit 1: Lower (with 2-side control)
Input-related data of the virtual inputs. 20 addresses will be held available for each of the 1 to 4 inputs. The address space for the virtual inputs begins at 2100, 2120, 2140 and 2160.
0 = off, no calculation
2100 x Calculation
1 = difference value measurement 2 = combined chlorine 3 = effective chlorine
2101 – 2102 x Measurement
Number of positions after the decimal point, see unit (4 bytes signed int).
Number Unit Decimal places
2 1 2 2 2 2 2 1 2 0 0 1 0 1 1
2103 x Unit
Table 29: Modbus addresses
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
mA µA ppm mg/l µS/cm mS/cm % mV pH min s mV/pH Pulses/min. Fahrenheit Celsius
Modbus addresses
38
BA-46020-02-V01
© Lutz-Jesco GmbH 2019
Multi-Channel Controller TOPAX
®
MC
Operating instructions
Address
2104 x The assigned input of the controller
Description Meaning
Read
Write
n0 = Sensor 1 n1 = Sensor 2 n2 = Sensor 3 n3 = Sensor 4 n4 = Virtual input 1 n5 = Virtual input 2 n6 = Virtual input 3 n7 = Virtual input 4 n8 = Timer switch
x Control output Y (active control)
2105
500 = 50,0 % (2 Byte signed int)
x x Control output Y (only manual mode)
2106
x Control output 2 Y2 (active control)
x x Control output 2 Y2 (only manual mode)
2107 – 2108 x x Setpoint 1
500 = 50,0 % (2 Byte signed int) Second side if 2-side control is active.
Number of positions after the decimal point, see unit (4 bytes signed int).
2109 – 2110 x x Setpoint 2 If 2-side control is active (4 byte signed int).
2111 x x Kp
Number of positions after the decimal point, see unit (2 bytes unsigned int).
2112 x x Kd Derivative time in s (2 byte unsigned int).
2113 x x Ki Reset time in s (2 byte unsigned int).
Read: Bit 0 = minimum alarm is active Bit 1 = maximum alarm is active
Read: Bit 0 = Y alarm is inactive Bit 1 = Y alarm is active
2114 x x Minimum and maximum alarm
2115 x x Y alarm
2116 x x Manual mode
Write: 0 = clear alarm
Write: 0 = clear alarm
Bit 0: Manual mode on Bit 1: Lower (with 2-side control)
Further non channel-related data.
2220 – 2223 x Analogue outputs 1 – 4 421 = 4.21 mA (2 byte signed int)
Table 29: Modbus addresses
© Lutz-Jesco GmbH 2019 Subject to technical changes. 190729
BA-46020-02-V01
Modbus addresses
39
Multi-Channel Controller TOPAX
®
MC
Operating instructions
Address
2225 x
2226 x
Table 29: Modbus addresses
Description Meaning
Read
Write
Alarm status 1
If the bit is set, the associated alarm or message is active.
Alarm status 2
If the bit is set, the associated alarm or message is active.
Message or alarm Bit
Sensor error 1 Sensor error 2 Sensor error 3 Sensor error 4 Sensor 1 maximum alarm Sensor 2 maximum alarm Sensor 3 maximum alarm Sensor 4 maximum alarm Virtual 1 maximum alarm Virtual 2 maximum alarm Virtual 3 maximum alarm Virtual 4 maximum alarm Sensor 1 minimum alarm Sensor 2 minimum alarm Sensor 3 minimum alarm Sensor 4 minimum alarm
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Message or alarm Bit
Virtual 1 minimum alarm Virtual 2 minimum alarm Virtual 3 minimum alarm Virtual 4 minimum alarm Controller 1 Y alarm Controller 2 Y alarm Controller 3 Y alarm Controller 4 Y alarm Temperature 1 maximum alarm Temperature 2 maximum alarm Temperature 3 maximum alarm Temperature 4 maximum alarm Temperature 1 minimum alarm Temperature 2 minimum alarm Temperature 3 minimum alarm Temperature 4 minimum alarm
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Modbus addresses
40
BA-46020-02-V01
© Lutz-Jesco GmbH 2019
Multi-Channel Controller TOPAX
®
MC
Operating instructions
Address
2227 x
2228 x
Description Meaning
Read
Write
Alarm status 3
If the bit is set, the associated alarm or message is active.
Alarm status 4
If the bit is set, the associated alarm or message is active.
Message or alarm Bit
Setpoint changeover Sample water missing External stop Pre-alarm 1 Pre-alarm 2 Pre-alarm 3 Pre-alarm 4 Master alarm 1 Master alarm 2 Master alarm 3 Master alarm 4 Digital input 1 Digital input 2 Digital input 3 Digital input 4 Digital input 5
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Message or alarm Bit
Digital input 6 Digital input 7 Digital input 8 Sensor 1 Improper adjustment Sensor 2 Improper adjustment Sensor 3 Improper adjustment Sensor 4 Improper adjustment Temperature 1 Improper adjustment Temperature 2 Improper adjustment Temperature 3 Improper adjustment Temperature 4 Improper adjustment Output 1 Improper adjustment Output 2 Improper adjustment Output 3 Improper adjustment Output 4 Improper adjustment Next service due
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Alarm status 5
2229 x
If the bit is set, the associated alarm or message is active.
2235 x Temperature input 1
2236 x Temperature input 2
2237 x Temperature input 3
2238 x Temperature input 4
Table 29: Modbus addresses
© Lutz-Jesco GmbH 2019 Subject to technical changes. 190729
BA-46020-02-V01
Message or alarm Bit
Sensor change sensor 1 due Sensor change sensor 2 due Sensor change sensor 3 due Sensor change sensor 4 due
0 1 2 3
235 = 23.5 °C
With an inactive temperature, the return is -10000
(2 byte signed int)
Modbus addresses
41
Multi-Channel Controller TOPAX
(DE) EU-Konformitätserklärung
Hiermit erklären wir, dass das nachfolgend bezeichnete Gerät aufgrund seiner Konzipierung und Bauart sowie in der von uns in Verkehr gebrachten Ausführung den einschlägigen grundlegenden Sicherheits- und Gesundheitsanforderungen der aufgeführten EU-Richtlinien entspricht. Bei einer nicht mit uns abgestimmten Änderung am Gerät verliert diese Erklärung ihre Gültigkeit.
(FR) Déclaration de conformité UE
Nous déclarons sous notre propre responsabilité que le produit ci-dessous mentionné répond aux exigences essentielles de sécurité et de santé des directives UE énumérées aussi bien sur le plan de sa conception et de son type de construction que du modèle que nous avons mis en circulation. Cette déclaration perdra sa validité en cas d’une modification effectuée sur le produit sans notre accord explicite.
(EN) EU Declaration of Conformity
We hereby certify that the device described in the following complies with the relevant fundamental safety and sanitary requirements and the listed EU regulations due to the concept and design of the version sold by us. If the device is modified without our consent, this declaration loses its validity.
(ES) Declaración de conformidad UE
Por la presente declaramos que, dados la concepción y los aspectos constructivos del modelo puesto por nosotros en circulación, el aparato mencionado a conti­nuación cumple con los requisitos sanitarios y de seguridad vigentes de las directivas de la U.E. citadas a continuación. Esta declaración será invalidad por cambios en el aparato realizados sin nuestro consentimiento.
EU-Richtlinien: EU directives:
Dokumentationsbevollmächtigter: Authorized person for documentation:
Bezeichnung des Gerätes:
Descripción de la mercancía:
Description of the unit:
Désignation du matériel:
Typ: Type:
Heinz Lutz Geschäftsführer / Chief Executive Officer Lutz-Jesco GmbH Wedemark, 01.03.2019
Lutz-Jesco GmbH Am Bostelberge 19 30900 Wedemark Germany
Harmonisierte Normen: Harmonized standards:
(PT) Declaração de conformidade UE
Declaramos pelo presente documento que o equipamento a seguir descrito, devido à sua concepção e ao tipo de construção daí resultante, bem como a versão por nós lançada no mercado, cumpre as exigências básicas aplicáveis de segurança e de saúde das directivas CE indicadas. A presente declaração perde a sua validade em caso de alteração ao equipamento não autorizada por nós.
Designação do aparelho:
Mehrkanalregler Multi-Channel Controller Régulateur multi-canaux Controlador multi canal Controlador multi-canal
Topax MC
2014/30/EU 2014/35/EU 2011/65/EU
Die Schutzziele der Niederspannungsrichtlinie 2014/35/EU wurden gemäß Anhang I, Nr. 1.5.1 der Maschinenrichtlinie 2006/42/EG eingehalten.
The protective aims of the Low Voltage Directive 2014/35/EU were adhered to in accordance with Annex I, No. 1.5.1 of the Machinery Directive 2006/42/EC.
DIN EN ISO 12100:2011-03 DIN EN 61000-4-2:2009-12 DIN EN 61000-4-3:2006 + A1:2008 + A2:2010 DIN EN 61000-4-4:2012 DIN EN 61000-4-5:2014 DIN EN 61000-4-6:2014-08 DIN EN 61000-4-11:2005-02 DIN EN 61000-6-2:2016-05 DIN EN 61000-6-3:2011-09 DIN EN 55016-2-3:2010 + A1:2010
Lutz-Jesco GmbH
®
MC
13 EU Declaration of Conformity
Operating instructions
EU Declaration of Conformity
42
BA-46020-02-V01
© Lutz-Jesco GmbH 2019
Multi-Channel Controller TOPAX
®
MC
Operating instructions
14 Warranty claim
Warranty claim
Please copy and send it back with the unit!
If the device breaks down within the period of warranty, please return it in a cleaned condition with the complete warranty claim.
Sender
Company: ............................................................................................................... Phone: .................................. Date: ..........................
Address: ....................................................................................................................................................................................................
Contact person: .........................................................................................................................................................................................
Manufacturer order no.: .......................................................................................... Date of delivery: .........................................................
Device type: ............................................................................................................ Serial number: ...........................................................
Nominal capacity / nominal pressure: .........................................................................................................................................................
Description of fault:.....................................................................................................................................................................................
...................................................................................................................................................................................................................
...................................................................................................................................................................................................................
...................................................................................................................................................................................................................
...................................................................................................................................................................................................................
...................................................................................................................................................................................................................
...................................................................................................................................................................................................................
...................................................................................................................................................................................................................
Service conditions of the device
Point of use / system designation:...............................................................................................................................................................
...................................................................................................................................................................................................................
...................................................................................................................................................................................................................
Accessories used (suction line etc.):............................................................................................................................................................
...................................................................................................................................................................................................................
...................................................................................................................................................................................................................
...................................................................................................................................................................................................................
...................................................................................................................................................................................................................
Commissioning (date): ................................................................................................................................................................................
Duty period (approx. operating hours): ........................................................................................................................................................
Please describe the specific installation and enclose a simple drawing or picture of the chemical feed system, showing materials of const­ruction, diameters, lengths and heights of suction and discharge lines.
© Lutz-Jesco GmbH 2019 Subject to technical changes. 190729
BA-46020-02-V01
Warranty claim
43
Multi-Channel Controller TOPAX
15 Glossary
®
MC
Operating instructions
Limit value control/DIN contact
The limit value control is an output which switches when deter­mined limit values are exceeded or undercut. This function is used to
control an ECO or Night mode in a swimming pool with reduced circula­tion. If there are no swimmers in the swimming pool, energy and dosing media can be saved. The limit value control monitors the maintenance of the parameters.
In Germany, the limit values of the national standard DIN 19643 apply. As such, “DIN contact“ is a widespread name for this function.
Hysteresis
Hysteresis is the delayed response time of a two position controller,
when it reaches the “setpoint Y” and the control switches quickly be­tween raising and lowering. As quick switching or control can have unde­sired effects, you can define hysteresis and achieve a more equal control.
Actual value X
The actual value ‘X’ is the continually measured value of a sensor.
Reset time Ki
The reset time ‘Ki’ is the integral proportion (I proportion) with PI and PID controllers. ‘Ki’ is the time required by the controller to alter the control variable ‘Y’, which is generated by the proportional range ‘Kp’ immediately after the step change of the control deviation ‘X-W‘.
You can set a reset time ‘Ki’ of up to 200 minutes.
P controller
A P controller is defined by the proportional range ‘Kp’. The use of a pure P controller means that a control deviation ‘X-W’ always remains. The setpoint ‘W’ will thus never be reached.
PI controller
The PI controller is defined by the proportional range ‘Kp’ and the re­set time ‘Ki’. The use of the PI controller means that the actual value ‘X’
can reach the setpoint ‘W’.
The PI controller is suitable for the majority of applications.
PD-controller
The PD controller is defined by the proportional range ‘Kp’ and the de­rivative time ‘Kd’. The use of a PD controller means that a control devia-
tion ‘X-W’ always remains. The setpoint ‘W’ will thus never be reached.
PID controller
Proportional range Kp
The proportional range ‘Kp’ (p proportion) of a P, PI or PID controller indi­cates the amount by which the actual value ‘X’ must deviate from the setpoint ‘W’ so that the variable Y = 100 %. If the control deviation ‘X-W’ is lower, the control variable is also lower.
The control variable ‘Y’ of a P controller is only affected by the control de­viation ‘X-W’. The Kp value is stated in the unit of the variable to be con­trolled. If for example, during the control of the pH value, an Kp = 2 pH is selected and the actual value is X = 9 pH and setpoint W = 7 pH, the con­trol deviation is X-W = 9 pH – 7 pH = 2 pH.
In this case, the deviation X-W is as large as the Kp value. In this case, the variable Y would be 100 %. With a decreasing deviation X-W, the control variable decreases in a linear fashion to 0 % with an actual value X = set­point W.
Control deviation X-W
The control deviation X-W is the difference between the actual value ‘X’ and the setpoint ‘W’. The control variable ‘Y’ results from the control
deviation.
Setpoint W
The setpoint ‘W’ of a control is the desired value.
Control variable Y
The control variable ‘Y’ is the value with which the controller actuates the actor in accordance with its set parameters and the control deviation
‘X-W’. The value lies between 0 % and 100 %.
Derivative time Kd
With PD or PID controllers, the differential proportion (D proportion) is de­fined with the derivative time ‘Kd’. The D proportion ensures that the
control path already contains a correction factor at the point at which the actual value "X" begins to differ from setpoint "W". The
control variable ‘Y’ depends on the speed with which the control deviation ‘X-W’ takes place. The duration of the correction is determined by the de­rivative time ‘Kd’. If the actual value ‘X’ does not change, i.e. the speed of change is “0”, the correction factor effected by the D proportion with the derivative time ‘Kd’ drops as far as “0” (even if the actual value ‘X’ does not match the setpoint ‘W’, but consistently deviates from it). The fact that the control system causes the actual value ‘X’ to match the setpoint ‘W’ is due mainly to the I proportion of the controller. The D proportion often im­proves the controller behaviour because it acts against the trend to devi­ate.
The derivative time Kd can be set from 0 seconds to a maximum of 1200 seconds.
The PID controller is defined by the proportional range ‘Kp’, the reset time ‘Ki’ and the derivative time ‘Kd’. The integral gain means that the actual value ‘X’ can reach the setpoint ‘W’.
44
Glossary
BA-46020-02-V01
Y alarm
You can activate an alarm which deactivates the controller if the con­trol variable ‘Y’ amounts to over 95 % over a defined period.
© Lutz-Jesco GmbH 2019
Multi-Channel Controller TOPAX
16 Index
®
MC
Operating instructions
A
Adjustment ......................................................................................27
B
Basic load ........................................................................................21
Battery ............................................................................................33
C
Commissioning ................................................................................18
D
Design ...............................................................................................8
Dimensioned drawings ....................................................................11
Dimensions ......................................................................................11
Drillhole dimensions ...................................................................11
Outside dimensions ....................................................................11
DIN contact ......................................................................................22
E
Electrical installation ........................................................................12
Ethernet ...........................................................................................17
EU Declaration of Conformity ...........................................................42
F
Firmware .........................................................................................33
Foreseeable misuse ...........................................................................7
Functional diagram ............................................................................8
G
General warnings ...............................................................................5
N
Notes for the Reader ..........................................................................4
O
Operation .........................................................................................26
P
Personnel qualification .......................................................................5
Personnel tasks .................................................................................6
Product description ............................................................................8
Product warranty ...............................................................................7
R
Rating plate ....................................................................................... 9
S
Safety ................................................................................................5
Scope of delivery ............................................................................... 8
Setpoints .........................................................................................31
Signal words
Explanation ...................................................................................4
Specialist staff ...................................................................................6
T
Technical data .................................................................................10
Terminal connection .........................................................................13
Trained electricians ............................................................................6
Trained persons .................................................................................6
Trend display ...................................................................................27
Troubleshooting ...............................................................................35
H
Handling instructions
Marking ........................................................................................4
Hazards due to non-compliance with the safety instructions ..............5
I
Installation
Connecting the actors .................................................................15
Connecting the sensor ................................................................14
Installation example ...........................................................................8
Installation on the wall .....................................................................12
Intended purpose ...............................................................................7
Intended use ......................................................................................7
Internal fuse ....................................................................................34
L
Limit value control ...........................................................................22
Logbook ..........................................................................................26
M
Maintenance ....................................................................................33
Maintenance intervals ...................................................................... 33
U
Updating software ............................................................................33
W
Warnings
General warnings .........................................................................5
Marking ........................................................................................4
Warning sign
Explanation ...................................................................................4
Warranty claim ................................................................................43
Working in a safety-conscious manner ..............................................5
Y
Y alarm ............................................................................................21
© Lutz-Jesco GmbH 2019 Subject to technical changes. 190729
BA-46020-02-V01
Index
45
Lutz-Jesco GmbH
Am Bostelberge 19 D-30900 Wedemark
Phone: +49 5130 5802-0 info@lutz-jesco.com www.lutz-jesco.com
Multi-Channel Controller TOPAX® MC Operating instructions
Copyright 2019 by Lutz-Jesco GmbH
Loading...