Lutron Electronics Switch User Manual

R
Installation Guide
Softswitch128TM (XPS) and
GRAFIK SystemsTM (XP)
Switching Panels
Please Read
Contents
Softswitch128 (XPS) 2 GRAFIK Systems (XP) 3
PPaanneell DDiimmeennssiioonnss Mini Panel 4 Standard Panel 5 Large Panel 6 Extra-Large Panel 7
PPaanneell MMoouunnttiinngg Panel and TUB Mounting 8 Rough-In Panel Interior Mounting 9
WWiirriinngg Feed-Through Panel: Feed and Load Wiring 10 Dual-Voltage Panel: Feed and Load Wiring 10 Panel with Branch Circuit Breakers:
Feed and Load Wiring 11
Panel with Isolation Switch:
Feed and Load Wiring 12
System Wiring Overview 13
RRaattiinnggss
Softswitch128 (XPS) 14 GRAFIK Systems (XP) 15
Temporary Lighting 16 Activate Loads in Bypass 16 Complete Installation 17 Remove Bypass Jumpers 17
Warranty 19 Contact Information 20
Overview
Use this guide to successfully install a switching panel. This guide describes panel installation, wiring, and load activation. For systems using rough-in panels, special instructions are included for keepout areas, panel mounting, and installing the panel interior.
XPS48-1204ML-20 shown
CChhiinneessee
EEnngglliisshh
EEssppaaññooll FFrraannççaaiiss
PPoorrttuugguuêêss
NNeeddeerrllaannddss
DDeeuuttsscchh
IIttaalliiaannoo
R
XPS24-1204ML-20-CGP____
R
2 Installation Guide for Switching Panels
Panel Model Number Guide
Softswitch128TM (XPS)
XPS24-120FT-CGP____
Feed-Through Model Numbers
Example
Number of Circuits in Panel
Feed Voltage
Feed­Through Type
Custom Panel Suffix
Custom Panel Suffix
Number of Circuits in Panel
Indicates number of switching circuits in the panel: 8, 12, 16, 20, 24, 28, 32, 36, 40, 44, or 48
Feed Voltage
1, 2
Omit for dual voltage 120 for 120 V 230 for 230 V (CE) 240 for 220-240 V (non-CE) 277 for 277 V
Load Cir
cuit Rating
16 A per circuit
Custom Panel Suf
fix
Contact Lutron for options
Number of Circuits in Panel
Indicates number of switching circuits in the panel: 8, 12, 16, 20, 24 (all voltages) 28, 32, 36, 40, or 42 (120/277/347 V only)
Feed Voltage 120 for 120 V
230 for 230 V (CE) 240 for 220-240 V (non-CE) 277 for 277 V 347 for 347 V
Feed Type Input Ratings 4ML for 3 phase 4 wire main lugs 120/208 V
or 277/480 V or 230/400 V or 220/380-240/415 V
3ML for 1 phase 3 wire main lugs 120/240 V 4IS for 3 phase 4 wire isolation switch
Branch Circuit Rating 20 for 20 A branch circuit breakers (120/277/347 V ; 16 A
continuous load rating)
16 for 16 A branch circuit breakers (230/220-240 V )
Custom Panel Suffix
Contact Lutron for options
Number of Circuits in Panel
Indicates number of switching circuits in the panel: 8, 12, 16, 20, 24, 28, 32, 36, 40, 44, or 48
Feed Voltage
1, 2
Omit for dual voltage 120 for 120 V 277 for 277 V
Load Circuit Rating
16 A per circuit
Branch Circuit Breaker Model Numbers
Example
Number of Circuits in Panel
Feed Voltage
Feed Type
Branch Circuit Rating
SINT8-120FT
Rough-In Model Numbers
120/277 V only
Example
Number of Circuits in Panel
Feed Voltage
Feed­Through Type
1
Multiple voltages (120 V and 277 V ) may be switched in the same panel. At least one feed of the specified voltage is required for the low voltage control transformer in the panel.
2
If voltage is not specified in the model number (e.g., XPS24-FT) product is rated 120 V or 277 V . Refer to Wiring section.
Frequency - All Model Numbers and Voltages
50/60 Hz
Output Voltages
120 V , 230 V , 240 V , 277 V , or 347 V
Number of Circuits in Panel
Indicates number of switching circuits in the panel: 4, 8, 12, 16, 20, 24, 28, 32, 36, 40, 44, or 48
Feed V
oltage
1, 2
Omit for dual voltage 120 for 120 V 230 for 230 V (CE) 240 for 220-240 V (non-CE) 277 for 277 V 347 for 347 V
Load Circuit Rating
16 A per circuit
Custom Panel Suffix
Contact Lutron for options
Number of Circuits in Panel
Indicates number of switching circuits in the panel: 4, 8, 12, 16, 20, 24 (all voltages) 28, 32, 36, 40, or 42 (120/277/347 V only)
Feed V
oltage
120 for 120 V 230 for 230 V (CE) 240 for 220-240 V (non-CE) 277 for 277 V 347 for 347 V
Feed Type Input Ratings 4ML for 3 phase 4 wire main lugs 120/208 V
or 277/480 V or 230/400 V or 220/380-240/415 V
3ML for 1 phase 3 wire main lugs 120/240 V IS for 3 phase 4 wire isolation switch
Branch Circuit Rating 20 for 20 A branch circuit breakers (120/277/347 V ; 16 A
continuous load rating)
16 for 16 A branch circuit breakers (230/220-240 V )
Custom Panel Suf
fix
Contact Lutron for options
Number of Circuits in Panel
Indicates number of switching circuits in the panel: 4, 8, 12, 16, 20, 24, 28, 32, 36, 40, 44, or 48
Feed Voltage
1, 2
Omit for dual voltage 120 for 120 V 277 for 277 V
Load Circuit Rating
16 A per circuit
1
Multiple voltages (120 V and 277 V ) may be switched in the same panel. At least one feed of the specified voltage is required for the low voltage control transformer in the panel.
2
If voltage is not specified in the model number (e.g., XPS24-FT) product is rated 120 V or 277 V . Refer to Wiring section.
Frequency - All Model Numbers and Voltages
50/60 Hz
Output V
oltages
120 V , 230 V , 240 V , 277 V , or 347 V
R
Installation Guide for Switching Panels 3
Panel Model Number Guide (continued)
GRAFIK SystemsTM (XP)
XP24-120FTML-CGP____
Feed-Through Model Numbers
Example
Number of Circuits in Panel
Feed Voltage
Feed­Through Type
XP24-1204ML-20-CGP____
Branch Circuit Breaker Model Numbers
Example
Number of Circuits in Panel
Feed Voltage
Feed Type
Branch Circuit Rating
XINT8-120FT
Rough-In Model Numbers
120/277 V only
Example
Number of Circuits in Panel
Feed Voltage
Feed­Through Type
Custom Panel Suffix
Custom Panel Suffix
Panel Dimensions
Mini Panel
Bottom View
Top View
Right Side
Left Side
Dimensions are in inches (mm).
Front View
14.38 (365)
15.875 (403)
8.00
(203)
2.2
(56)
4.2 (107)
0.15 (4)
1.34 (34)
21.50 (546)
24.50 (622)
24.00 (610)
2.21 (56)
15.13 (384)
10.75 (273)
4.09 (104)
Cover
R
4 Installation Guide for Switching Panels
NNoottee ffoorr RRoouugghh--IInn TTuubb ((mmooddeellss
XINT4 to XINT16,
or SINT8 to SINT16)
:: KKeeeepp cclleeaarr!! Inside of solid black line indicates keep-out area for interior.
R
Installation Guide for Switching Panels 5
Dimensions are in inches (mm).
Panel Dimensions (continued)
Bottom View
Top View
Right Side
Standard Panel
Left Side
Front View
14.375 (365)
15.875 (403)
2.43 (62)
8.00
(203)
4.21
(107)
0.15 (4)
2.69 (68)
41.75
(1060)
59.50
(1511)
59.00
(1499)
2.43 (62)
11.00 (279)
15.125 (394)
4.15 (105)
Cover
NNoottee ffoorr RRoouugghh--IInn TTuubb ((mmooddeellss
XINT20 to XINT48,
or SINT20 to SINT48)
:: KKeeeepp cclleeaarr!! Inside of solid black line indicates keep-out area for interior.
R
6 Installation Guide for Switching Panels
Panel Dimensions (continued)
Large Panel (120/277/347 V only)
Dimensions are in inches (mm).
Bottom View
Top View
Right Side
Left Side
Front View
22.0 (559)
23.50 (597)
2.50 (64)
3.34 (85)
6.30
(160)
0.15 (4)
45.00
(1143)
63.50
(1613)
63.00
(1600)
18.50 (470)
22.75 (578)
6.1 (155)
Cover