Lutron Electronics SIVOIA Installation And Operating Instructions Manual

Contents
Installation and Operating Instructions Drapery Installation Kit
A Typical Sivoia Motorized Drapery System
1 Carton Contents pg. 2, 3
2 Tools Required pg. 3
3 Mounting pg. 4, 5
4 Carrier Installation pg. 6, 7
5 Hanging Drapery Fabric pg. 8
7 Configuring the MDU pg. 11, 12
8 Infrared Control pg. 13
9 Troubleshooting pg. 14
10 Warranty pg. 15, 16
1
(Wallstation Control, Transformer, SV-IR Infrared Receiver Module, and Infrared Handheld Transmitter not included)
Wallstation Control
Transformer
SV-IR Infrared Receiver Module
Infrared
Handheld
Transmitter
Drapery System
Sivoia®
ONE WAY DRAW SYSTEM – RIGHT DRAW SHOWN
OR ONE WA
Y DRAW SYSTEM – LEFT DRAW SHOWN
2
OR SPLIT DRA
W SYSTEM
Carton Contents
1
Sivoia® Drapery
#2 Phillips Screwdriver
1/8 in. Straight Blade Screwdriver
Power Drill: Drill Bits, Screwdriver Attachments
Level
Pliers
Tape Measure
Wire Cutter
Wire Stripper
3
Carton Contents
1
Tools Required
2
W ALL MOUNT BRACKETS WITH CAM LOCK ( quantity depends on system width)
ONE HOOK EYE (split draw only)
AUXILIARY CARRIERS (
quantity depends on system width)
CEILING MOUNT C AM LOCKS (
quantity depends on system width)
Sivoia® Drapery
Mount the drapery track to the wall using the wall mount “L” brackets. Mount the brackets using the spacing illustrated below. Mount each end bracket at a maximum dimension of between five (5) and six (6) inches from each end of the track. Space the next bracket on both sides 16 in from the end brackets. Space the remaining brackets 16-24 in apart.
Note: All screws must be securely fastened to stud or structural member.
Top View
BRACKETS MUST BE MOUNTED STRAIGHT AND LEVEL
Each bracket must be mounted along a straight and level line. The drapery track must be straight and level to operate properly. When the wall brackets are securely mounted, install the track to the brackets using the cam locks. (SEE ILLUSTRATIONS BELOW FOR CAM LOCK OPERATION)
Side Elevation View
C
AM LEVER
4
Wall Mounting the Drapery Track
3
Window/Wall Side
Level Line
track
Top View
bracket
3.5-6 in
Adjustability
Push in cam lever until the tab is against the track
2
Cam is fully engaged when the tab on the cam is against the track.
Orient the cam lever in this position to engage the track with the cam lock.
1
16 in 16-24 in
5-6
in
16-24 in 16 in
5-6
in
Sivoia® Drapery
TRACK MOUNTING
Mount the drapery track to the ceiling using ceiling mount cam locks. Mount the cam locks using the spacing guide­lines shown below. Mount each end cam lock at a maximum dimension of between five (5) and six (6) inches and minimum dimension of five (5) inches from each end of system. Space the next bracket on both sides 16 in from the end brackets. Space the remaining brackets 16-24 in apart.
Note: All screws must be securely fastened to stud or
structural member.
Top View
The brackets should be mounted on a straight and level line. If the contour of the ceiling is not straight and level, use shims between the cam lock bracket and the ceiling to compensate for the irregularities.
To mount the track to the brackets, position all the cam lock lever arms to the unlocked position (see unlockeddiagram below). Position the track up against the cam lock brackets and rotate the cam lock arm to the locked position.
C
AM LEVER
Orient each cam lever in the position shown below. This unlocked position allows the track to engage the cam.
1
5
Ceiling Mounting the Drapery Track
3
Top View
16 in 16-24 in
5-6
in
Level Line
Window/Wall Side
Swing cam lock arm to lock track to cam lock bracket. Cam is fully engaged when the tab on the cam is against the track.
2
Track
Unlocked
Locked
16-24 in 16 in
5-6 in
Sivoia® Drapery
LOADING THE CARRIERS
The drapery carriers are installed at the factory, however, the required number of carriers must be verified. Draperies require one carrier per hook. The first two drapery hooks should hook on the master carrier for left, right and split draw systems (see respective diagrams on the next two pages). The number of carriers required is equal to the number of drapery hooks in fabric minus four (4).
LEFT AND RIGHT SINGLE DRAW SY
STEMS
Idle End
TO ADD OR REMOVE CARRIERS: Single Draw: Left or Right
Pry out square plug on the motor side of the track.
Insert or remove auxiliary carriers through the square hole in the track until the proper number of carriers are installed.
Replace plastic square plug by pushing it up into the square home until it snaps into place.
3
2
1
Motor
Housing
hooks for
last two (2)
drapery
hooks
Master Carrier
6
Carrier Installation – Left and Right Draw Systems
4
First two (2) drapery hooks should hook here
3
Pry out here using
flat blade screw driver
1
Auxiliary Carriers Motor End
The number of carriers required is four less than the total number of hooks on the drapery. The first two drapery hooks should hook to the master carrier and the last two drapery hooks should hook to the motor housing.
Sivoia® Drapery
SPLIT DRAW SYSTEMS
The motor side of the drapery track requires four less carriers than the total number of hooks on the drapery track. The first two drapery hooks should hook to the master carrier and the last two drapery hooks should hook to the motor housing. The number of carriers required is different for the idle side. The idle side of the drapery requires three less carriers than the total number of hooks on the drapery. The first two drapery hooks should hook to the master carrier, and the last drapery hooks should hook onto the hook eye on the idle endcap. See diagram below.
Idle end hook eye
Remove idle end cover
2
Carrier Installation – Split Draw Systems
4
7
TO ADD OR REMOVE C
ARRIERS:
Split Drive Systems
Follow the directions on page 6 for motor side plug removal, and installation of the auxiliary carriers.
Remove screw that retains the idle end cover. Remove idle and hook eye.
Insert or remove auxiliary carriers through the square hole in the idler end cap until the proper number of carriers are installed.
Install idle end hook eye and replace the idle end cover using the screw removed in step 2.
4
3
2
1
Remove track plug on the motor side. Follow the directions given on page 6.
1
3
Idle end cover retaining screw
4 2
Number of drapery hooks minus three (3)
Number of drapery hooks minus four (4)
Sivoia® Drapery
DRAPERY HOOK SETTING
For the best system performance, a drapery hook setting of 1/2 in should be used. This allows the system to operate with minimal noise.
DRAPER
Y FABRIC RETURN
Hanging Drapery Fabric
5
8
4.0-6.5 in (depends on wall mount bracket extension)
.50 in
Sivoia® Drapery
Description
2 conductors / #22-24 AWG
3 conductors (2 shielded, 1 common) #24 AWG Belden
® wire model #1883A
3 conductors:
2 / #18-22 AWG (24 VAC power supply) 1 / #18-22 AWG (earth ground)
6 conductors:
2 / #16 AWG (24 VAC power supply) 1 / #18 AWG (earth ground) 3 #22 AWG shielded + 1 #24 AWG
common (comm link)
(
Lutron wire part no. SV-CBL-MDU-250)
3 conductors #22 AWG Lutron model # SV-IR-EXT-10
Maximum Length
Control to MDU: 250 ft.(76 m)
4000 ft. (1333 m) per system 1000 ft. (333 m) from MDU to MDU
Transformer to MDU:
#18 AWG - 150 ft. (46 m) #20 AWG - 100 ft. (31 m) #22 AWG - 60 ft. (18 m)
MDU to
Sivoia power panel:
200 ft. (61 m)
50 ft. (15 m) per system ­total of 5 SV-IR-EXT-10, 10 ft. (3 m) each
Do not connect if there is only one MDU in the system. If there are multiple MDU's in the system,the MDU's must be wired together. Connect the MUX, Common, and MUX terminals of each MDU together in a daisy chain or homerun configuration.
To a Sivoia wall mounted keypad, or a Sivoia interface such as the SV-CCI-GRP or the SV-GRXI. The CNTRL1 and CNTRL2 wires are
polarity sensitive.
Wire to a Sivoia 100VA plug-in transformer, junction box mount transformer, or a
Sivoia power panel. Each MDU must be EARTH grounded. One Sivoia
transformer can power ONLY ONE MDU regardless of drapery size.
Control
Comm
Link
Power
Supply
IR Connector
System Wiring – Single MDU
6
9
CONNECTING WIRES TO THE MDU TERMINAL BLOCK
The terminal block located at the bottom of the MDU is the wire connection point for: power, communication, keypads, and interfaces.
1. Remove terminal block cover by pressing in on the cover and then pulling downward.
2. Grasp terminal block and pull down to separate from connecting block.
3. Connect wires to the terminal block according to the diagram below.
4. Replace the terminal block and the terminal block cover.
Wire Type
Control
A
Comm Link
B
Power Wires
C
Comm & Power
D
B &
C combined
in one cable
SV-IR
E
Extension Cable
A
E
B
C
Sivoia® Drapery
B
1234567
Cntrl 1
Cntrl
2
MUX
Common
MUX
AC
Ground
8
AC
Common MUX
MUX
1234567
8
Cntrl
1
Cntrl
2
Ground
AC
AC
Common
M UX
M UX
1234567
8
Cntrl
1
Cntrl
2
Ground
AC
AC
Common
M UX
M UX
AC
G
N D
AC
Wire to a Sivoia plug-in transformer, junction box mount transformer, or a Sivoia power panel. Each MDU must be EARTH grounded. One Sivoia transformer can power ONLY ONE MDU regardless of system width.
To a Sivoia wall mounted keypad, or a
Sivoia interface
A maximum of 64 MDUs can
be wired together per system
MDU Terminal Blocks
Control
Comm Link
Comm Link
Power Supply
Control
Next
MDU
Next MDU
Comm Link
Power Supply
6
System Wiring – Multiple MDUs
10
Description
2 conductors / #22-24 AWG
3 conductors (2 shielded, 1 common) / #24 AWG Belden
® wire model #1883A
3 conductors:
2 / #18-22 AWG (24 VAC power supply) 1 / #18-22 AWG (earth ground)
6 conductors:
2 / #16 AWG (24 VAC power supply) 1 / #18 AWG (earth ground) 3 #22 AWG shielded + 1 #24 AWG
common (comm link)
(
Lutron wire part no. SV-CBL-MDU-250)
3 conductors #22 AWG Lutron model # SV-IR-EXT-10
Maximum Length
Control to MDU: 250 ft.(76 m)
4000 ft. (1333 m) per system 1000 ft. (333 m) from MDU to MDU
Transformer to MDU:
#18 AWG - 150 ft. (46 m) #20 AWG - 100 ft. (31 m) #22 AWG - 60 ft. (18 m)
MDU to
Sivoia power panel:
200 ft. (61 m)
50 ft. (15 m) per system ­total of 5 SV-IR-EXT-10, 10 ft. (3 m) each
Wire Type
Control
A
Comm Link
B
Power Wires
C
Comm & Power
D
B &
C combined
in one cable
SV-IR
E
Extension Cable
B
B
A
C
B
A
E E
C
Sivoia® Drapery
Open Limit: The position the shade moves to when it opens.
Close Limit: The position the shade moves to when it closes.
Mode Button
Open and Close Buttons
Set Button
Display on bottom of MDU
SINGLE MDU
The motor drive unit should come from the factory with open and close limits set. In order to change the factory limits, follow the steps below. If there is only one MDU in the system, open limit and close limit are the only setups required. Follow the programming steps outlined in the programming table below. If the system has multiple MDU's, follow the single MDU setup directions for each MDU and then continue with the setup codes for multiple MDU systems on the next page.
11
7
Configuring the Motor Drive Unit (MDU)
Steps
Step 1
Step 2
Set
Press the Set button to save the current position as the Open Limit. The display will read and blink for 4 seconds, then go blank.
Press the
Set Button to save the current position as the Close Limit. The display will read and blink for 4 seconds, then go blank.
Mode
Open Limit: Press the Mode button on the
MDU until the display reads
Close Limit: Press the Mode button on the
MDU until the display reads
Adjust
Use the Open and Close buttons on the MDU to adjust the drapery to the Open position desired. When open the auxiliary carriers should not be tightly stacked together.
Use the
Open and Close buttons on the MDU to adjust the drapery to the Closed position desired.
Sivoia® Drapery
MODE
OPEN
CLOSE
SET
All MDU’s with the same room address and the
same address
MUL
TIPLE MDU SET-UP CODES
Program each MDU per instructions on page 11.
Link Address:
Each MDU must be set to a unique Link Address number to allow the MDU's to communicate on the communication
link. There are 64 link addresses available, meaning the maximum number of MDU's in a single system is 64.
Room Address: The room address groups MDU's on the communication link. A group is defined as all MDU's with the same room address number. There are 32 room addresses available in a single system, therefore, a system can have up to 32 groups. Typically, all MDU's in a room will be set to the same room address. Use the room address to help determine how keypads will control the MDU's in the system. Refer to the control station setting table below for information on how the room address setting affects how the system is controlled by keypads or interfaces.
IR Address: Used to set the IR address a MDU will respond to. Some IR hand controls have the ability to control subgroups of draperies within a group, as defined by the room address described above. There are 8 subgroups available. Each IR address (sub­group) is made up of two parts, the IR address number (1,2,3 or 4) and its drapery location (F or r), the FRONT drapery or the REAR drapery. Any number of MDU's can have the same IR address. The IR address can also be used to determine subgroups of the MDU's when a keypad or interface is used to control the system. Refer to the control station setting table below for informa­tion on how the IR address affects how the system is controlled by keypads or interfaces.
Control Station: Determines which MDU's in the system will respond to a "Group" keypad or "Group" interface control that is wired to the MDU being setup. It is not necessary to change the control station setting of an MDU that does not have any keypads or interfaces wired to it.
There are two types of Sivoia keypads and interfaces,
group and individual types. The table to the left describes how a group type controls a system depending on the setting of the MDU it is wired to. An individual type only controls the MDU it is wired to, regardless of the setting of the MDU it is wired to.
Group keypads/interfaces and individual keypads/interfaces can be wired to the same MDU. A maximum of 9 keypads/interfaces can be wired to one MDU.
Any keypad or interface
CANNOT be wired to
more than one MDU.
SPECIAL NOTES:
Control Station Setting Table
MDU
CS
Setting
0
1
2
Which MDU’s in a System Will
Respond
All MDUs with the same room address
All MDUs in the system
All MDUs with the same room address
and the same Front (F) or Rear (r) assignment in the address
4
3
5
All MDUs with the same room address
and the same number (1,
2, 3, or 4) in the address setting
All Front MDUs or all Rear MDU’s in the system
What MDU Address Settings
Determine which MDU in the
System Will Respond
Room address
Room address
IR address Not dependent on and
Room address Front or Rear in the IR address
Room address Same number (1, 2, 3, or 4) in the IR address
Front or Rear in the IR address
12
7
Configuring the MDU
Preset Lockout: Turns off the ability to set or adjust PRESET stop points. To activate, set the scene lockout setting to 1. To deactivate, set the scene lockout setting to 0. Changing this setting on any MDU will adjust all the MDU's in the system. It is not necessary to deactivate the scene lockout setting from the same MDU it was acti­vated it on.
Sivoia® Drapery
MOUNTING THE IR EYE
13
8
Infrared Control
Connect the SV-IR receiver to the wire connector on the MDU
Mount the IR eye to the wall, the ceiling or even a non-moving edge of the drapery fabric using a clip. Make sure the location of the eye is not obstructed by an object.
The SV-IR allows the MDU to be controlled directly with a
Sivoia Infrared Handheld Transmitter (SV-OCIT, SV-3PIT, or SV-4GD-OCIT). The SV-IR receiver connects to the MDU via a 20 in (51cm) cable. This provides the SV-IR receiver ample mounting range to offset any infrared signal restriction caused by a protective/decorative covering for the shade system. To extend the IR receiver mounting range, add up to five (5) SV-IR-EXT-10 extension cables (10 ft [3 m] each).
Note: To control an individual drapery with an IR transmitter, the SV-IR must be connected to that MDU. If there
is a Group/Subgroup of MDUs with the same Room/IR Address (see page 11), the SV-IR need only be con­nected to one of those MDUs to control the entire Group/Subgroup.
The SV-IR receiver must be located to allow line-of-sight reception of infrared signals.
The IR transmitter has a range of 30 ft for the SV-IR to receive its signal.
The SV-IR must
NOT be located near lighting fixtures or in direct sunlight.
The SV-IR must be located within 50 ft (15 m) of the MDU it is connected to. Add up to five SV-IR-EXT-10
extension cables (10 ft [3 m] each).
Sivoia® Drapery
PROBLEM SOLUTION
The draperies will not open or close. 1. Check power to the motor unit by pressing the MODE
button. If the LED display does not show oL check that:
transformer has power
MDU is wired correctly
power wiring terminal is not miswired or
disconnected
2. Try to open and close the drapery using the buttons marked open and close on the motor drive unit. If the drapery does not respond, check for and clear all obstructions.
3. Check that the Open and Close limits are set correctly.
The Drapery does not respond to keypads or IR. 1. Check that power is connected to the drapery.
2. Check that MDU terminal block is connected securely and wired correctly.
3. If using wall keypad, check that wall keypad has been wired correctly.
4. If using IR remote, confirm that SV-IR, infrared receiver is wired to MDU correctly, and is not obstructed.
5. If using IR remote, check transmitter batteries.
Draperies do not move together in a group 1. Confirm that all MDUs are wired correctly, including
power and Comm Link.
2. Confirm that each MDU has a unique link address, and a common room address.
3. Confirm that keypad is a group keypad.
Drapery will not move to full open or full close 1. Confirm that open and close limits are set correctly.
2. Confirm that drapery fabric is not obstructed or caught on something.
3. Confirm that drapery fabric is hanging from only the 1st and 4th holes of the master car.
14
9
Troubleshooting
Sivoia® Drapery
SIVOIA MOTORIZED DRAPERY SYSTEM EIGHT YEAR LIMITED WARRANTY
Vimco warrants, for eight years from shipment, each new
Sivoia Motorized Drapery System to be free from defects in materials or workmanship under conditions of normal use and specified ambient temperature when installed and operated in accordance with Vimco product specifications, applicable local electrical and building codes, applicable National Electrical Code
® provisions,
and the Safety Standards of Underwriter's Laboratories.
WHAT VIMCO WILL DO
Upon the return of a system or system component, subsequently determined by Vimco to be defective, Vimco will, in its sole discretion, repair or replace the defective system or system component, provided that Vimco was promptly notified of the alleged defect within the warranty period, and provided that the system or system component was properly installed, wired, insulated, used, and maintained, as determined solely by Vimco. Vimco shall not be required to remove, install, or re-install any system or system component alleged to be defective.
Vimco will issue a credit for the cost of the repair or the replacement in accordance with the following schedule:
For the first 2 years after the date of shipment 100% For years 3, 4, and 5 after the date of shipment 50% For years 6, 7, and 8 after the date of shipment 25%
WHAT THIS WARRANTY DOES NOT COVER
1. Damage or improper operation determined by Vimco to be due to normal wear and tear, or to abuse, misuse, or accident, such as:
a. Use of incorrect line voltages; b. Use of incorrect fuses or circuit breakers; c. Failure to follow operating instructions provided by
VIMCO; d. Unauthorized repairs or adjustments or alterations; e. Direct exposure to corrosive materials; f. Vandalism; g. Fire, flood, "Acts of God", and other factors beyond
the control of VIMCO.
2. The cost of labor, including any labor required to remove, install, or re-program any replacement item.
3. Components and equipment external to the
Sivoia
Motorized Drapery System, such as:
a. Non-Lutron lighting and automation systems; b. Building wiring; and c. Other manufacturers equipment, including, but not
limited to:
i. Time clocks; ii. Audio-visual equipment; and iii. Photo sensors.
4. The cost of repairing or replacing property or equipment other than the warranted system.
HOW TO GET SERVICE UNDER THIS W
ARRANTY
Should you experience the need for service under this warranty, please contact your
Sivoia Motorized Drapery System service representative immediately; or Contact VIMCO by telephone toll-free at: 1-800-446-1503; or
By mail to: VIMCO Shading Systems
11520 Sun Shade Lane Ashland, VA 23005
or; By E-mail: info@vimco.com
15
10
Limited Warranty
Sivoia® Drapery
LIMITATIONS AND EXCLUSIONS
THIS WARRANTY IS EXCLUSIVE. THERE ARE NO OTHER EXPRESS WARRANTIES.
THE IMPLIED WARRANTY OF MERCHANTABILITY IS LIMITED TO TWO YEARS FROM THE DATE OF SHIPMENT. VIMCO SHALL NOT BE LIABLE FOR ANY REPAIR WORK UNDERTAKEN WITHOUT ITS PROPER WRITTEN CONSENT, OR FOR INCIDENTAL, CONSEQUENTIAL, OR SPECIAL DAMAGES. VIMCOS LIABILITY ON ANY CLAIM FOR DAMAGES ARISING OUT OF OR IN CONNECTION WITH THE MANUFACTURE, SALE, INSTALLATION, DELIVERY, USE, REPAIR, OR REPLACEMENT OF THE SHADING SYSTEM SHALL NEVER EXCEED THE PRICE PAID FOR THE SYSTEM. SOME STATES DO NOT ALLOW LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY LASTS, SO THE ABOVE LIMITATION MAY NOT APPLY TO YOU. SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE ABOVE LIMITATION OR EXCLUSION MAY NOT APPLY TO YOU.
This product may be covered under one or more of the following U.S. Patents: 5,671,387; 6,313,588; 6,346,781; DES. 370,663; DES. 378,814; DES. 437,585; DES. 450,043; and DES 462,332. and corresponding foreign patents. U.S. and foreign patents pending. Lutron, the sunburst logo, and Sivoia are registered trademarks and Shading Solutions by Vimcois a registered trademark of Lutron Electronics Co., Inc. The VIMCO logo is a registered trademark of Virginia Iron & Metal Company, Inc. NEC is a registered trademark of the National Fire Protection Association, Quincy, Massachusetts.
© 2004 Virginia Iron & Metal Company, Inc.
Internet: www.vimco.com, www.lutron.com
16
10
Limited Warranty
Lutron Electronics Co., Inc. 7200 Suter Road Coopersburg, PA 18036 U.S.A. Made and printed in U.S.A. 9/04 P/N 045-014 Rev. B
Sivoia® Drapery
Loading...