
QS Smart
Power Supply
Panel (CE)
Installation
Instructions
QSPS-P2-10-60

QSPS-P2-10-60
230 V~ 50/60 Hz 4 A
Installation Instructions (Please leave for occupant)
Please read before installing.
Tools Required:
Wire Cutter/Stripper Power Drill
Small Flat-Head Screwdriver #2 Phillips® Screwdriver
NOTE: Mounting hardware is not included due to the wide variety of wall materials.
Customer should determine the appropriate mounting hardware for their specific needs.
Box Contents:
QSPS-P2-10-60
Important Notes
1. All wiring must be in accordance with national and local electrical codes.
2. QSPS-P2-10-60 must be installed by a qualified electrician.
3. Ambient operating temperature: 0 to 40 °C (32 to 104 °F), 0 to 90% humidity,
non-condensing.
4. This product is intended for indoor use only.
5. On power-up under unfavorable mains conditions, this device may cause interfering
voltage fluctuations (flicker). To prevent such interference, the system impedance
Zmax shall be 0.21 Ohms or less at the interface point (power service box). If
necessary, the user can ask the public power supply company for the system
impedance at the interface point.
1
1.1
Page 1
Sivoia® QS QSPS-P2-10-60 (CE) Installation instructions

2
2.1
Installation
1. Mount QSPS-P2-10-60 using one of the following methods (mounting hardware is not
provided). Do not mount in any other orientation.
a. Surface Mount - Use the keyholes located on the back of the enclosure to fasten the
QSPS-P2-10-60 to the wall. Use fasteners rated for a 23 kg (50 lb) load. See illustration
of QSPS-P2-10-60 .
b. Recess Mount - Install a 50 mm x 100 mm (2 in x 4 in) board between the studs as
a bottom support. Fasten the QSPS-P2-10-60 to the right stud and bottom support
inserting fasteners through the mounting holes provided.
NOTICE: The equipment
is air-cooled. Mount in a
location where the vented
cover will not be blocked.
A minimum of 300 mm
(1 ft) is necessary.
WARNING: Risk of death
or serious injury. Lock the
supply breaker in the OFF
position before wiring to the
terminal blocks.
406 mm (16 in)
264 mm (10.4 in)
121 mm (4.8 in)
30 mm (1.2 in)
375 mm (14.8 in)
445 mm (17.5 in)
152 mm (6 in)
45 mm (1.8 in)
50 x 100 mm (2 x 4 in)
Bottom Support
2. Connect 230 V~ power wiring
into the QSPS-P2-10-60.
Remove one of the knockout tabs
on the top left side of the enclosure
near the input terminal blocks.
Insert a strain relief into the
knockout hole. Run the power wire
through the strain relief to the input
terminal blocks at the top left side
of the enclosure. Tighten terminal
blocks to 0.4 to 0.6 N•m (3.5 to
5 in-lbs).
Note: Maximum of (1) QSPS-P2-10-60 per
15 A Breaker. Maximum feed breaker size
of 15 Amps. Use only High-Magnetic breakers.
Page 2
Sivoia® QS QSPS-P2-10-60 (CE) Installation instructions

2
2.2
QSPS-P2-10-60 Parts identification
Installation (continued)
Diagnostic Buttons
All Lights On
All Lights Off
All Shades Open
All Shades Close
Power Supply Clear
Reserved for future use
Reserved for future use
Diagnostic LED – Communication Link Traffic
Status LED
FUSE
5X20
FUSE
5X20
10 9 8 7 6 5 4 3 2 110 9 8 7 6 5 4 3 2 1
1 2 3 4 5 6 7 8 9 10
1
2
3
4
5
6
7
8
9
10
FUSE
5X20
COM
MUX
MUX
COM
MUX
MUX
LINK
FUSE
5X20
FUSE
5X20
10 9 8 7 6 5 4 3 2 110 9 8 7 6 5 4 3 2 1
FUSE
FUSE
5X20
FUSE
5X20
10 9 8 7 6 5 4 3 2 110 9 8 7 6 5 4 3 2 1
2
3
4
6
7
8
10
FUSE
5X20
COM
MUX
MUX
COM
MUX
MUX
LINK
10 9 8 7 6 5 4 3 2 110 9 8 7 6 5 4 3 2 1
COM
MUX
MUX
COM
MUX
MUX
LINK
230 V~ input terminal
blocks
Spare fuses 5x20 mm
2.5 A
4-pin connector
power and communication
to Lutron lighting and
shading devices
LED – Output status
(1 per output,
10 outputs)
3-pin connector
communication to
additional power supplies
10 9 8 7 6 5 4 3 2 110 9 8 7 6 5 4 3 2 1
MUX
MUX
Page 3
Sivoia® QS QSPS-P2-10-60 (CE) Installation instructions

QS Link Wiring
3
3.1
Link Rules
The following Link rules must be observed for proper operation.
- Maximum of 100 devices (such as a GRAFIK Eye® QS Unit, QS keypad,
QSPS-P2-10-60, or Sivoia® QS shade)
- Maximum of 100 zones (such as a Sivoia QS shade, or a lighting zone on a
GRAFIK Eye QS Unit)
- Maximum 600 m (2000 ft.) of cable connecting all QSPS-P2-10-60 panels
- Maximum 600 m (2000 ft.) of cable to devices wired to each QSPS-P2-10-60
- Use only cable with at least one twisted/shielded pair for communications (MUX and MUX)
3.2
Wire Length Chart
Maximum devices per one output Maximum distance per one output based on wire guage
Shades + Controls
12 AWG
(4 mm2)
16 AWG
(1.5 mm2)
18 AWG
(1 mm2)
GRX-CBL-346S-500
None
Up to 8
seeTouch QS
keypads
1200 ft (350 m) 500 ft (150 m) 300 ft (75 m)
1 Sivoia QS roller 64TM,
roller 100, roller 200CW,
or roller 225TM
Up to 1
seeTouch QS
keypad
500 ft (150 m) 200 ft (60 m) 125 ft (35 m)
2 Sivoia QS roller 64,
≤ 30 sq ft
(2.75 sq m) each
None
200 ft (60 m) 75 ft (20 m) 50 ft (15 m)
3 Sivoia QS roller 64,
≤ 20 sq ft
(1.8 sq m) each
None
2 Sivoia QS roller 100,
≤ 50 sq ft
(4.6 sq m) each
None
Page 4
Sivoia® QS QSPS-P2-10-60 (CE) Installation instructions