Lutron Electronics QSN-4S16-S-347, QSN-4T16-S, QSN-4T20-S, QSN-4T16-S-347, QSN-4S20-S Programming Manual

...
BUTTON AND LED LOCATIONS
TROUBLESHOOTING
WIRED INPUTS
USING THIS GUIDE
OTHER QS LINK DEVICES
QS SENSOR MODULE (QSM) WITH WIRED OR WIRELESS INPUT DEVICES
Lutron Electronics Co., Inc. | 7200 Suter Road Coopersburg, PA 18036-1299, U.S.A.
Help 1.800.523.9466 U.S.A., Canada and the Caribbean +1.888.235.2910 México +1.610.282.3800 Others
This guide is divided into sections. Each section deals with a particular feature or set of features of the Energi Savr NodeTM unit and the equipment connected to it. Depending on the connected equipment and the intended use of your Energi Savr NodeTM unit, some sections may not apply. See below to determine which sections should be read.
0-10 V Outputs l Salidas l Sorties
4 X 50 mA
(Sinking O
nl
y l Rece
pcion
solam
en
te l Réc
epteur de
co
urant seulem
e
nt)
QSN-4T16-S-347
120-277 V~ 50/60 Hz 500 mA
0-10 V / Softswitch
®
24/7 Help | Ayuda | Aide www.lutron.com U.S.A. Canadá Caribbean | E.U.A. Caribe | É.-U., Caraïbes 1.800.523.9466 México +1.888.235.2910 Others | Otros | Autres +1.610.282.3800
Coopersburg, PA 18036, U.S.A.
500-14444 Rev. A
saving energy since 1961
Energi Savr Node
TM
Type 1
Enclosure
243C
LISTED
Ind. Cont. Eq.
4 Softswit
ch
®
Circuits l Circuitos
Capacity l Capacidad l Capacité :
IE
C PELV / NEC
®
C
lass 2
Input Groups | Grupos de
entrada
Groupes d’entreés :
20
V
-
4
X 65 mA
QS Link | Elance | L
iaison :
24
V
-
4
62 mA
WARNING
Risk of Electric Shock. May Result in serious injury or death. More than one disconnect may be required to de-energize this device. Disconnect all power sources before servicing unit.
ADVERTENCIA
Riesgo choque eléctrico. Puede resultar en lesiones graves o muerte. Puede necesitarse más de una desconexión para desenergizar este dispositivo. Desconecte todas las fuentes de alimentación antes de prestar servicio a la unidad.
AVERTISSEMENT
Risque d'électrocution. Peut causer le décès de la personne ou de graves lésions. Plus d’un débranchement peut être Débrancher toutes les sources d’énergie avant de procéder à l’entretien de cette unité.
®
4 x 16 A 120-277 V~ 4 x 0,5 HP 120 V~ 4 x 1,5 HP 277 V~
4 x 16 A 347 V~
All Energi Savr NodeTM units
Read:
»
Load Setup
Energi Savr NodeTM with Softswitch® unit
(QSN-4S16-S, QSN-4S16-S-347, QSN-4S20-S)
Energi Savr NodeTM for 0-10 V unit
(QSN-4T16-S, QSN-4T16-S-347, QSN-4T20-S)
Type 1 Enclosure
4 Softswitch
®
Circuits l C
irc
uit
os
Capacity l Capacidad l Capacité :
QSN-4S16-S-347
120-277 V 50/60 Hz 500 mA
Softswitch
®
Coopersburg, PA 18036, U.S.A.
500-14445 Rev. A
saving energy since 1961
Energi Savr Node
TM
WARNING
Risk of Electric Shock. May Result in serious injury or death. More than one disconnect may be required to de-energize this device. Disconnect all power sources before servicing unit.
ADVERTENCIA
Riesgo choque eléctrico. Puede resultar en lesiones graves o muerte. Puede necesitarse más de una desconexión para desenergizar este dispositivo. Desconecte todas las fuentes de alimentación antes de prestar servicio a la unidad.
AVERTISSEMENT
Risque d'électrocution. Peut causer le décès de la personne ou de graves lésions. Plus d’un débranchement peut être Débrancher toutes les sources d’énergie avant de procéder à l’entretien de cette unité.
®
24/7 Help | Ayuda | Aide www.lutron.com U.S.A. Canadá Caribbean | E.U.A. Caribe | É.-U., Caraïbes 1.800.523.9466 México +1.888.235.2910 Others | Otros | Autres +1.610.282.3800
243C
LISTED
Ind. Cont. Eq.
IE
C PE
L
V / NEC
®
Class 2
Input Groups | Gru
pos de entrada
Groupes d’entreés :
20
V
-
4
X 65 mA
QS Link | Elance | Liaison
:
24
V -
462 mA
4 x 16 A 120-277 V~ 4 x 0,5 HP 120 V~ 4 x 1,5 HP 277 V~
4 x 16 A 347 V~
LED Feedback
LED LED Behavior Description
Occ
(Occupancy Sensor)
Continuous On
Sensor detects Vacancy
1 flash per second
Sensor detects Occupancy
Off
Sensor never detected
Daylight
(Daylight Sensor )
Continuous On
Sensor is detected
Flashing
Sensor information transmitting on the QS link
Off
Sensor never detected/sensor not seeing light
IR
(Infrared Receiver)
Continuous On Receiver is detected
Flashing
IR button press detected
Off
Receiver never detected
Switch
(NEC
® Class2 Switch)
Continuous On
Switch detected/open
Flashing
Switch button press detected
Off
Switch never detected
CCI
(Contact Closure Input)
Continuous On
Contact detected/open
Flashing
Contact closed
Off
Contact never detected
Emerg
(Emergency Contact Closure Input)
Continuous On
Normal operation/Contact Closed/ Jumpered
Rapid flash
Emergency Mode/Contact Open/ Jumper missing
QS Link
On/Flashing
/
Device transmitting/receiving on the QS link
3 quick flashes every 4 seconds
Communication error
Off
Device not transmitting/receiving on the QS link
Wired Continuous On
Wired sensor
Zone
Continuous On
Load is on
Off
Load is off
Troubleshooting using Symptoms
Symptom Cause Solution
Unable to add daylight sensor to a zone
Existing daylight sensor already assigned to the zone
Unassign the existing daylight sensor and try again.
Unable to add an occupancy sensor to a zone
16 sensors have already been assigned
No more than 16 sensors can be assigned to one ESN unit. Unassign sensors until below 16 sensor limit.
Daylight sensor fails to turn on a zone
Occupancy sensor is overriding the zone
Daylight sensors will not turn a zone on if an occupancy sensor assigned to that zone detects that the room is vacant.
Switched zone daylighting: incorrect light level set during Daylighting Setup
Reset the daylighting set point. See
Daylighting Setup.
When associating a QSM to the Energi Savr NodeTM unit, the ‘QSM’ LED flutters for 1 second, then turns off
A QSM has already been associated to the Energi Savr NodeTM unit.
To clear the QSM association and any Energi Savr Node
TM unit zone assignments
to any QSM inputs, press and hold the Input button on the Energi Savr NodeTM unit for 10 seconds. The ‘Input’ LED will flutter for 1 second, then turn off.
When associating a wireless input device to a QSM, the QSM responds with 10 short beeps
Maximum number of associations to the QSM has been exceeded for that wireless input device type.
Unassign any unnecessary wireless inputs of that device type and try again.
When associating a wireless input device to a QSM, the QSM responds with 5 short beeps
Input device is already associated to another QSM on the QS link.
If you choose to ignore the warning and try to associate the same input device to the QSM a second time, the input device will be removed from association with the previous QSM and will now be associated with the new QSM. Note: This will also remove any Energi Savr Node
TM
programming that the wireless device may have had through the previous QSM.
QS Link LED quickly flashes 3 times every 4 seconds
QS Link communication error.
Check QS Link wiring
Technical Assistance
U.S.A. / Canada: 1.800.523.9466 Mexico: +1.888.235.2910 Other Countries: +1.610.282.3800
IMPORTANT NOTES
Energi Savr NodeTM with Softswitch® unit
(QSN-4S16-S, QSN-4S16-S-347, QSN-4S20-S)
Energi Savr NodeTM for 0-10 V unit
(QSN-4T16-S, QSN-4T16-S-347, QSN-4T20-S)
Energi Savr NodeT
manual programming guide
English
1. Manual Programming: This document describes manual
programming via the buttons on the front of the Energi Savr NodeTM unit. For programming using the Apple iPod touch or iPhone mobile digital devices, please see the Energi Savr NodeTM app available from the Apple AppStore online store.
2. Use only compatible Lutron® sensors and controls.
032449 | Rev. C | 05/2014
24/7 Help
U.S.A., Canada and the Caribbean
1.800.523.9466
México
+1.888.235.2910
Others
+1.610.282.3800
Fax
+1.610.282.6311
w
w
w
.
l
u
t
r
o
n
.
c
o
m
If you have wired sensor inputs wired directly to the Energi Savr NodeTM unit input group terminal blocks, see below to determine which additional sections to read.
www.lutron.com
© 2014 Lutron Electronics Co., Inc.
P/N 032449 Rev. C 05/2014
Apple, iPhone, and iPod touch are trademarks of Apple Inc., registered in the U.S. and other countries. AppStore is a service mark of Apple Inc.
Lutron, GRAFIK Eye, Pico, seeTouch, Softswitch and ) are registered trademarks, and Energi Savr Node and Radio Powr Savr are trademarks of Lutron Electronics Co., Inc.
All Wired Inputs
Read:
»
Energi Savr NodeTM (ESN) Unit Wired Input Setup
OR
Energi Savr Node
TM
Unit
LUTRON
Dry Contact Closure Switch
Wires to “Switch”, “CCI”, or “EMERG” Input
»
Energi Savr
Node
TM (ESN)
Unit Wired Input Setup
Wired Occupancy Sensor
Wires to “Occ” Input
Additional Sections:
»
Energi Savr NodeTM (ESN)
Unit Wired Input Setup
»
Occupancy Setup
Wired Wallstation or Infrared (IR) Sensor
Wires to “IR” Input
»
Energi Savr
NodeTM (ESN) Unit Wired Input Setup
Wired Daylight Sensor
Wires to “Daylight” Input
Additional Sections:
»
Energi Savr NodeTM (ESN)
Unit Wired Input Setup
»
Daylighting Setup
If you have a QSM wired to the Energi Savr NodeTM unit QS Link terminal block, read sections QS Sensor Module (QSM) Input Setup and
QS Sensor Module (QSM) Zone Assignment. Some parts of the section
may not apply, depending on the devices connected to the QSM. See below to determine which additional sub­sections to read for each type of connected device.
QSM Wireless Input Devices
Communicates with QSM via Radio Frequency (RF)
Read:
»
Subsection: Associating Wireless Input
Devices to a QSM
QS Sensor Module (QSM)
Wires to “QS Link” Terminal Block on
Energi Savr Node
TM unit
Wireless Occupancy Sensor
Additional Sections:
»
Occupancy Setup
»
Subsection: Assign Zones to
QSM Inputs
Wireless Daylight Sensor
Additional Sections:
»
Daylighting Setup
»
Subsection: Assign Zones to
QSM Inputs
Wired Occupancy Sensor
Additional Sections:
»
Occupancy Setup
»
Subsection: Assign Zones to
QSM Inputs
Wired Daylight Sensor
Additional Sections:
»
Daylighting Setup
»
Subsection: Assign Zones to
QSM Inputs
LUTRON
Pico® Wireless Controller
Additional Sections:
»
Subsection: Assign Zones to Pico®
Wireless Controller (through QSM)
QS Link
Wired Wallstation or Infrared (IR) Sensor
Additional Sections:
»
Subsection: Assign Zones
to QSM Inputs
OR
Energi Savr NodeTM Unit
QS Sensor Module
Read:
»
QS Sensor Module (QSM)
Input Setup
»
QS Sensor Module (QSM)
Zone Assignment
QSM Wired Input Devices
Wires to Input Terminal Blocks on QSM
Read:
» Subsection: Associating Wired
Input Devices to a QSM
QS Link
If you have other devices wired to the Energi Savr NodeTM unit QS Link terminal block, see below to determine which additional sections to read.
Energi Savr NodeTM Unit
Wired seeTouch® QS Wallstation
Additional Sections:
» Wired seeTouch® QS Wallstations Programming
QSE-IO Input/Output Interface
Additional Sections:
» QSE-IO Input/Output Interface Programming
CCI1 CCI 2
CCI 3
CCI 4
COM CCI 5
V
0-24 V 1 A 0-24 V ½ A
R
O N
CCO 1 NC
CCO 1 NO
CCO 2 NC CCO 2 NO
1-2 COM
CCO 3 NC
CCO 4 NO
CCO 3 NO
CCO 4 NC
3-4 COM
CCO 5 NC
5 COM
CCO 5 NO
V
R
MUX
COM V+
MUX
500-13491 Rev. B
CCO 1
CCO 2
CCO 3
CCO 4
CCO 5
STAT
QS
800.523.9466
+1.610.282.3800
www.lutron.com/qs
QSE-IO
24 V 100 mA
®
243C IND. CONT. EQ.
02755761323 1
8 7 6 5 4 3 2 1
4 3 2 1
GRAFIK Eye® QS Control Unit or QS Timeclock
Additional Sections:
» GRAFIK Eye® QS Control Unit or QS Time clock Programming
LUTRON
Zones
Inputs
PROGRAMMINGLEDs and BUTTON PRESSES
Lutron Electronics Co., Inc. | 7200 Suter Road Coopersburg, PA 18036-1299, U.S.A.
Help 1.800.523.9466 U.S.A., Canada and the Caribbean +1.888.235.2910 México +1.610.282.3800 Others
1. Enter Load Setup. Simultaneously press and hold the Program and Input buttons for 3 seconds. LEDs for Group 1 Inputs and
‘Default’ will blink once per second.
2. Select options. Press the Option button to select the option and then use the and buttons for each zone to select the choice
for each option.
LED
Option Setting Choices
Opt 2 Load Type High LED 0-10 V Dimming (default)
1
Med LED 10-0 V Dimming
1
Low LED Switched
High LED and Low LED
Receptacle
Opt 3
(not available on QSN-4S16-S or QSN-4S16-S-347)
High End Trim High-Med LEDs 100% maximum (default)
down to 55% minimum
Default + Opt 1
(not available on QSN-4S16-S or QSN-4S16-S-347)
Low End Trim Low-Med LEDs 0% minimum
up to 45% maximum
Default + Opt 2
Absolute Minimum Light Level
2
High-Med-Low LEDs 100% maximum
down to 0% minimum (default)
1
Not available on QSN-4S16-S or QSN-4S16-S-347
2
This setting is required in certain cities (i.e. Chicago). Check local electrical codes to verify if required.
3. Exit Load Setup. Simultaneously press and hold the Program and Input buttons for 3 seconds to exit.
Set zone level. Use the
and buttons to adjust zone preset light level.
Assign zone. Simultaneously press then release the
and buttons to save the zone level and assign the zone to the selected
input.
To unassign a zone, simultaneously press then release the
and buttons of the desired zone. The zone LED will turn off to indicate
an unassigned zone.
Repeat setting zone level and zone assignment for each zone to be assigned to the selected input.
e. CCI input:
The LED for the currently saved option will be steady on. Press the Option button to select the desired option. The LED for the selected option will flash.
CCI—Contact Closure Input
Option LED
Switch Action Feature Function
Default Momentary Sweep to
Off*
Contact closure will turn assigned zones Off
Opt 1
Maintained Enable /
Disable Afterhours Mode
† ‡
Contact closure will enable Afterhours Mode Contact open will disable Afterhours Mode
Opt 2
Maintained Zones
Preset/ Off
Contact closure will set assigned zones to preset level (preset level cannot be set to off)
Contact open will set assigned zones off
* By default, all zones are assigned and set to off, but zones can be unassigned and zone levels are adjustable to any level. † The zone must be set to Afterhours Mode to function properly. Please refer to Occupancy Setup. ‡ Default Afterhours Mode setting: 5 minute warning (assigned zones ash 3 times) before zones turn off; pressing any button activates a 45 minute delay, after
which the 5 minute warning will activate again. Receptacle loads will not blink-warn in Afterhours Mode.
Save the selected option. Press and hold the Option button for 3 seconds. The LED for the selected option will remain steady on.
Set zone levels. Use the
and buttons to adjust zone preset light levels.
Assign/Unassign zones. Simultaneously press the
and buttons of any zone to save the zone level and assign or unassign the zone to/from the selected input. A flashing ‘Zone’ LED indicates an assigned zone. A ‘Zone’ LED that is off indicates an unassigned zone.
Repeat setting zone level and zone assignment for each zone to be assigned to the selected input.
f. Emerg input:
Set zone levels. Use the
and buttons to adjust zone preset light levels.
Assign zone. Simultaneously press then release the
and buttons to save the zone level and assign the zone to the selected input.
To unassign a zone, simultaneously press then release the
and buttons of the desired zone. The zone LED will turn off to indicate
an unassigned zone.
Repeat steps 2 and 3 for each desired input.
4. Exit Input Setup. Press and hold the Program button for 3 seconds to exit.
Associating Wired Input Devices to a QSM
Once wired inputs are connected to the QSM, upon power up, the QSM will automatically detect and configure the wired inputs after a valid signal is received. For example: occupied room, IR signal, etc.
If any wired inputs are moved to a different connection on the QSM, the inputs will need to be re-detected. To force the QSM to re­detect all wired inputs, press and hold the Program button on the QSM for 10 seconds.
Associating Wireless Input Devices to a QSM
Wireless input devices must be associated to only one QSM before they are assigned to control system devices.
1. Enter Input Setup. Press and hold the Program button on the QSM for 3 seconds. You will hear a long 1-second beep upon
entering, and the ‘Status’ LED will blink.
2. Associate devices. For each wireless device you wish to associate, press and hold the appropriate button on the device
according to the following table:
Input Device Button
Press For
Device
Feedback
Maximum Per QSM
Radio Powr SavrTM Occupancy Sensor or Lights Off
6 seconds Dome ashes
briey
10
Radio Powr Savr Daylight Sensor
Link 6 seconds Dome ashes
briey
10
Pico
® Wireless
Controller
or Off
(bottom button)
6 seconds N/A 10
After each successful input association, QSM will respond with 3 long beeps (2 seconds each).
Note: If QSM responds in any other way, consult the Troubleshooting section on the first page of this guide.
3. Exit Input Setup. Press and hold the Program button on the QSM for 3 seconds to exit.
QSM Association to an ESN Unit
1.
Press and hold the Program button on the QSM for 3 seconds. You will hear a long 1-second beep upon entering, and the ‘Status’ LED will blink. The input LEDs on Energi Savr Node
TM unit(s) on the QS link will sequence through each input group.
2. Associate QSM. On the Energi Savr NodeTM unit to which the QSM will be associated, press and hold the Input button for 3
seconds until the ‘QSM’ LED on the Energi Savr Node
TM unit begins to flash.
3. Exit QSM Association. Press and hold the Program button on the QSM for 3 seconds to exit.
1. Enter ESN Wired Input Setup. Press and hold the Program button for 3 seconds. LEDs for Group 1 ‘Occ’ and ‘Wired’ will blink
once per second.
2. Select input. Tap the Program button to select an input. Corresponding LED (located above input terminal) will blink. Also, LEDs
of sensors wired to the Energi Savr NodeTM unit will flash to help with identification.
3. Setup options. Follow the appropriate section for each input below.
a. Occupancy sensor:
Assign zone(s). Simultaneously press then release the
and buttons of any zone to assign the zone to the selected input. A
flashing zone LED indicates an assigned zone.
To unassign a zone, simultaneously press then release the
and buttons of the desired zone. The zone LED will turn off to indicate
an unassigned zone.
b. Daylight sensor:
Assign zone(s). Simultaneously press then release the
and buttons of any zone to assign the zone to the selected input. A
flashing zone LED indicates an assigned zone.
Note: Each zone can only be assigned to a single daylight sensor input. The zone must be unassigned from the input before assigning to a different daylight sensor input.
Note: Any zone set to “Receptacle” load type cannot be assigned to a daylight sensor.
To unassign a zone, simultaneously press then release the
and buttons of the desired zone. The zone LED will turn off to indicate
an unassigned zone.
c. IR receiver / IR Wallstation:
The LED for the currently saved option will be steady on. Press the Option button to select the desired option. The LED for the selected option will flash.
LED
Option
Opt 1
Scene Mode Allows IR remote to select scenes (see Scene Setup
for more information) Note: CC-4BRL wallstation will only recall scenes 1-4, and CC-1BRL will only recall scene 1.
Opt 2
Zone mode (default) Allows setting of preset light levels for each zone
Save the selected option. Press and hold the Option button for 3 seconds. The LED for the saved option will remain steady on.
Set zone level (Zone Mode only). Use the and buttons to adjust zone preset light level.
Assign zone. Simultaneously press then release the
and buttons to save zone level (Zone Mode only) and assign the zone to
the selected input (Zone Mode and Scene Mode).
To unassign a zone, simultaneously press then release the
and buttons of the desired zone. The zone LED will turn off to indicate
an unassigned zone.
Note: For any keypad assigned to control a receptacle zone, Raise/Lower will not control that zone.
Repeat setting zone level (Zone Mode only) and zone assignment for each zone to be assigned to the selected input.
d. Switch input:
The LED for the currently saved option will be steady on. Press the Option button to select the desired option. The LED for the selected option will flash.
Switch—NEC® Class 2 / PELV dry contact switch
Option LED
Switch Action Feature Function
Default
Maintained Zone toggle
Preset / Off (default)
Contact closure or open will toggle the state of assigned zones between a preset and off* (preset level cannot be set to off)
Opt 1
Momentary Zone toggle
Preset / Off
Contact closure will toggle the state of assigned zones between a preset and off* (preset level cannot be set to off)
Opt 2 Maintained
(dual action)
Zones Preset / Off
Contact closure will turn assigned zones on to preset level (preset level cannot be set to off)
Contact open will turn assigned zones off
Opt 3
Momentary (single action)
Zones On Contact closure will turn assigned zones on to preset level
(preset level can be set to off)
* If one or more assigned zones are on at time of contact closure/open, all assigned zones will turn off.
Save the selected option. Press and hold the Option button for 3 seconds. The LED for the selected option will remain steady on.
Continued next column...
Load Setup
Energi Savr Node
TM (ESN) Unit Wired Input Setup - continued
QS Sensor Module (QSM) Input Setup
Energi Savr Node
TM (ESN) Unit Wired Input Setup
1.
1.
1. 3.
1. 3.
ESN Wired Input Setup
QS Sensor Module (QSM) Input Setup
3.2.
2.
2.
Enter Load Setup
Press and hold 3 seconds
Press and hold
3 seconds
Press and hold 3 seconds
Press and hold
3 seconds
Press and hold 3 seconds
Press and hold 3 seconds
Press and hold 3 seconds
Press and hold 3 seconds
Press and hold 3 seconds
Press and hold
6 seconds
Press and hold 6 seconds
Press and hold 6 seconds
Press and hold 3 seconds
Press
Press
Press
Press simultaneously
Press
Press simultaneouslyPress
Press
Enter ESN Wired Input Setup
Enter QSM Wireless Input Setup Exit Setup
Enter QSM-ESN Association Exit QSM-ESN Association
Associate QSM
Select Option
Select Input
Associate Devices
Select Option
Save Option
Change Setting
Selected Input Blinks
Exit Load Setup
3. a. b.
f.
c. d. e.
Assign Zones
Exit ESN Wired Input Setup
Set Zone Levels
Assign Zone
Set Zone Level
(IR receiver: Zone Mode Only)
P
ress and ho
ld
3 secon
ds
4.
Press
Associating Wireless Input Devices to a QSM
QSM Association to an ESN Unit
Pr
ess and ho
ld
2.
Button and LED Locations
LED states:
OFF ON Blink/Flash
See written instructions at right.
Load Setup
Zones
Inputs
Figure B
Figure A
Figure C
Loading...
+ 2 hidden pages