PROGRAMMINGLEDs and BUTTON PRESSES
Lutron Electronics Co., Inc. | 7200 Suter Road
Coopersburg, PA 18036-1299, U.S.A.
Help 1.800.523.9466 U.S.A., Canada and the Caribbean +1.888.235.2910 México +1.610.282.3800 Others
1. Enter Load Setup. Simultaneously press and hold the Program and Input buttons for 3 seconds. LEDs for Group 1 Inputs and
‘Default’ will blink once per second.
2. Select options. Press the Option button to select the option and then use the and buttons for each zone to select the choice
for each option.
LED
Option Setting Choices
Opt 2 Load Type High LED 0-10 V Dimming (default)
1
Med LED 10-0 V Dimming
1
Low LED Switched
High LED and
Low LED
Receptacle
Opt 3
(not available on
QSN-4S16-S or
QSN-4S16-S-347)
High End Trim High-Med LEDs 100% maximum (default)
down to
55% minimum
Default + Opt 1
(not available on
QSN-4S16-S or
QSN-4S16-S-347)
Low End Trim Low-Med LEDs 0% minimum
up to
45% maximum
Default + Opt 2
Absolute
Minimum Light
Level
2
High-Med-Low LEDs 100% maximum
down to
0% minimum (default)
1
Not available on QSN-4S16-S or QSN-4S16-S-347
2
This setting is required in certain cities (i.e. Chicago). Check local electrical codes to verify if required.
3. Exit Load Setup. Simultaneously press and hold the Program and Input buttons for 3 seconds to exit.
Set zone level. Use the
and buttons to adjust zone preset light level.
Assign zone. Simultaneously press then release the
and buttons to save the zone level and assign the zone to the selected
input.
To unassign a zone, simultaneously press then release the
and buttons of the desired zone. The zone LED will turn off to indicate
an unassigned zone.
Repeat setting zone level and zone assignment for each zone to be assigned to the selected input.
e. CCI input:
The LED for the currently saved option will be steady on.
Press the Option button to select the desired option. The LED for the selected option will flash.
CCI—Contact Closure Input
Option
LED
Switch
Action Feature Function
Default Momentary Sweep to
Off*
Contact closure will turn assigned zones Off
Opt 1
Maintained Enable /
Disable
Afterhours
Mode
† ‡
Contact closure will enable Afterhours Mode
Contact open will disable Afterhours Mode
Opt 2
Maintained Zones
Preset/
Off
Contact closure will set assigned zones to
preset level (preset level cannot be set to off)
Contact open will set assigned zones off
* By default, all zones are assigned and set to off, but zones can be unassigned and zone levels are adjustable to any level.
† The zone must be set to Afterhours Mode to function properly. Please refer to Occupancy Setup.
‡ Default Afterhours Mode setting: 5 minute warning (assigned zones ash 3 times) before zones turn off; pressing any button activates a 45 minute delay, after
which the 5 minute warning will activate again. Receptacle loads will not blink-warn in Afterhours Mode.
Save the selected option. Press and hold the Option button for 3 seconds. The LED for the selected option will remain steady
on.
Set zone levels. Use the
and buttons to adjust zone preset light levels.
Assign/Unassign zones. Simultaneously press the
and buttons of any zone to save the zone level and assign or unassign the
zone to/from the selected input. A flashing ‘Zone’ LED indicates an assigned zone. A ‘Zone’ LED that is off indicates an unassigned
zone.
Repeat setting zone level and zone assignment for each zone to be assigned to the selected input.
f. Emerg input:
Set zone levels. Use the
and buttons to adjust zone preset light levels.
Assign zone. Simultaneously press then release the
and buttons to save the zone level and assign the zone to the selected
input.
To unassign a zone, simultaneously press then release the
and buttons of the desired zone. The zone LED will turn off to indicate
an unassigned zone.
Repeat steps 2 and 3 for each desired input.
4. Exit Input Setup. Press and hold the Program button for 3 seconds to exit.
Associating Wired Input Devices to a QSM
Once wired inputs are connected to the QSM, upon power up, the QSM will automatically detect and configure the wired inputs
after a valid signal is received. For example: occupied room, IR signal, etc.
If any wired inputs are moved to a different connection on the QSM, the inputs will need to be re-detected. To force the QSM to redetect all wired inputs, press and hold the Program button on the QSM for 10 seconds.
Associating Wireless Input Devices to a QSM
Wireless input devices must be associated to only one QSM before they are assigned to control system devices.
1. Enter Input Setup. Press and hold the Program button on the QSM for 3 seconds. You will hear a long 1-second beep upon
entering, and the ‘Status’ LED will blink.
2. Associate devices. For each wireless device you wish to associate, press and hold the appropriate button on the device
according to the following table:
Input
Device Button
Press
For
Device
Feedback
Maximum
Per QSM
Radio Powr SavrTM
Occupancy Sensor or Lights Off
6 seconds Dome ashes
briey
10
Radio Powr Savr
Daylight Sensor
Link 6 seconds Dome ashes
briey
10
Pico
® Wireless
Controller
or Off
(bottom button)
6 seconds N/A 10
After each successful input association, QSM will respond with 3 long beeps (2 seconds each).
Note: If QSM responds in any other way, consult the Troubleshooting section on the first page of this guide.
3. Exit Input Setup. Press and hold the Program button on the QSM for 3 seconds to exit.
QSM Association to an ESN Unit
1.
Press and hold the Program button on the QSM for 3 seconds. You will hear a long 1-second beep upon entering, and the ‘Status’
LED will blink. The input LEDs on Energi Savr Node
TM unit(s) on the QS link will sequence through each input group.
2. Associate QSM. On the Energi Savr NodeTM unit to which the QSM will be associated, press and hold the Input button for 3
seconds until the ‘QSM’ LED on the Energi Savr Node
TM unit begins to flash.
3. Exit QSM Association. Press and hold the Program button on the QSM for 3 seconds to exit.
1. Enter ESN Wired Input Setup. Press and hold the Program button for 3 seconds. LEDs for Group 1 ‘Occ’ and ‘Wired’ will blink
once per second.
2. Select input. Tap the Program button to select an input. Corresponding LED (located above input terminal) will blink. Also, LEDs
of sensors wired to the Energi Savr NodeTM unit will flash to help with identification.
3. Setup options. Follow the appropriate section for each input below.
a. Occupancy sensor:
Assign zone(s). Simultaneously press then release the
and buttons of any zone to assign the zone to the selected input. A
flashing zone LED indicates an assigned zone.
To unassign a zone, simultaneously press then release the
and buttons of the desired zone. The zone LED will turn off to indicate
an unassigned zone.
b. Daylight sensor:
Assign zone(s). Simultaneously press then release the
and buttons of any zone to assign the zone to the selected input. A
flashing zone LED indicates an assigned zone.
Note: Each zone can only be assigned to a single daylight sensor input. The zone must be unassigned from the input
before assigning to a different daylight sensor input.
Note: Any zone set to “Receptacle” load type cannot be assigned to a daylight sensor.
To unassign a zone, simultaneously press then release the
and buttons of the desired zone. The zone LED will turn off to indicate
an unassigned zone.
c. IR receiver / IR Wallstation:
The LED for the currently saved option will be steady on. Press the Option button to select the desired option. The LED for the
selected option will flash.
LED
Option
Opt 1
Scene Mode Allows IR remote to select scenes (see Scene Setup
for more information)
Note: CC-4BRL wallstation will only recall scenes
1-4, and CC-1BRL will only recall scene 1.
Opt 2
Zone mode (default) Allows setting of preset light levels for each zone
Save the selected option. Press and hold the Option button for 3 seconds. The LED for the saved option will remain steady on.
Set zone level (Zone Mode only). Use the and buttons to adjust zone preset light level.
Assign zone. Simultaneously press then release the
and buttons to save zone level (Zone Mode only) and assign the zone to
the selected input (Zone Mode and Scene Mode).
To unassign a zone, simultaneously press then release the
and buttons of the desired zone. The zone LED will turn off to indicate
an unassigned zone.
Note: For any keypad assigned to control a receptacle zone, Raise/Lower will not control that zone.
Repeat setting zone level (Zone Mode only) and zone assignment for each zone to be assigned to the selected input.
d. Switch input:
The LED for the currently saved option will be steady on. Press the Option button to select the desired option. The LED for the
selected option will flash.
Switch—NEC® Class 2 / PELV dry contact switch
Option
LED
Switch
Action Feature Function
Default
Maintained Zone toggle
Preset / Off
(default)
Contact closure or open will toggle the state of assigned zones
between a preset and off* (preset level cannot be set to off)
Opt 1
Momentary Zone toggle
Preset / Off
Contact closure will toggle the state of assigned zones between
a preset and off* (preset level cannot be set to off)
Opt 2 Maintained
(dual action)
Zones
Preset / Off
Contact closure will turn assigned zones on to preset level
(preset level cannot be set to off)
Contact open will turn assigned zones off
Opt 3
Momentary
(single action)
Zones On Contact closure will turn assigned zones on to preset level
(preset level can be set to off)
* If one or more assigned zones are on at time of contact closure/open, all assigned zones will turn off.
Save the selected option. Press and hold the Option button for 3 seconds. The LED for the selected option will remain steady
on.
Continued next column...
Load Setup
Energi Savr Node
TM (ESN) Unit Wired Input Setup - continued
QS Sensor Module (QSM) Input Setup
Energi Savr Node
TM (ESN) Unit Wired Input Setup
1.
1.
1. 3.
1. 3.
ESN Wired Input Setup
QS Sensor Module (QSM) Input Setup
3.2.
2.
2.
Enter Load Setup
Press and hold
3 seconds
Press and hold
3 seconds
Press and hold
3 seconds
Press and hold
3 seconds
Press and hold
3 seconds
Press and hold
3 seconds
Press and hold
3 seconds
Press and hold
3 seconds
Press and hold
3 seconds
Press and hold
6 seconds
Press and hold
6 seconds
Press and hold
6 seconds
Press and hold
3 seconds
Press
Press
Press
Press simultaneously
Press
Press simultaneouslyPress
Press
Enter ESN Wired Input Setup
Enter QSM Wireless Input Setup Exit Setup
Enter QSM-ESN Association Exit QSM-ESN Association
Associate QSM
Select Option
Select Input
Associate Devices
Select Option
Save Option
Change Setting
Selected Input Blinks
Exit Load Setup
3.
a.
b.
f.
c.
d.
e.
Assign Zones
Exit ESN Wired Input Setup
Set Zone Levels
Assign Zone
Set Zone Level
(IR receiver: Zone Mode Only)