Lutron Electronics QSGRJ-6P, QSGRJ-3P, QSGRK-3PCE, QSGRK-4PCE, QSGRK-6PCE Programming Addendum

...
Wireless
R
Programming Addendum
LUTRON
This addendum applies to the GRAFIK Eye QS Wireless models listed below, and their associated components.
QSGRJ-3P QSGRJ-4P QSGRJ-6P
QSGRK-3PCE QSGRK-4PCE QSGRK-6PCE
QSGRJ-6E QSGRJ-8E QSGRJ-16E
Contents
Associating GRAFIK Eye QS Wireless Control Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Associating Wireless Occupancy Sensors and GRAFIK Eye QS Wireless Control Units . . . . . . . . . . . . . . . . . . . . 3
Associating Sivoia® QS Wireless Shades/Drapes and GRAFIK Eye QS Wireless Control Units . . . . . . . . . . . . . . . . 4
Associating PicoTM Wireless Controls and GRAFIK Eye QS Wireless Control Units: Zone Control. . . . . . . . . . . . . . 5
Associating PicoTM Wireless Controls and GRAFIK Eye QS Wireless Control Units: Scene Control. . . . . . . . . . . . . 6
Wireless Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Contact Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Wireless System Programming
R
GRAFIK Eye® QS Wireless System Programming 2
OK
1 2 3 4 5 6
OK
1 2 3 4 5 6
GRAFIK Eye QS A “Talks” to GRAFIK Eye QS B; scene activation and master (raise/lower) button presses activated on unit A are replicated on unit B.
GRAFIK Eye QS B “Listens” to GRAFIK Eye QS A; unit B replicates scene activations and master (raise/lower) button presses on unit A.
When there is more than one GRAFIK Eye QS control unit in a wireless system, it is often convenient to associate them so that scene activations and master (raise/lower) button presses carry over to other associated GRAFIK Eye QS control units.
To associate two GRAFIK Eye QS control units:
1. Begin with the GRAFIK Eye QS control unit that will “talk” (button presses will be replicated on the other control unit; in the drawing below this is GRAFIK Eye QS A). Press and hold the top and bottom scene buttons until the LEDs flash (about 3 seconds).
2. Continue with the GRAFIK Eye QS control unit that will “listen” (replicate button presses on the other control unit; in the drawing below this is GRAFIK Eye QS B). Press and hold the top scene button until the LEDs flash (about 3 seconds).
3. Return to the GRAFIK Eye QS control unit that will “talk” (A). Press and hold the top and bottom scene buttons until the LEDs stop flashing (about 3 seconds).
4. It is often desired to repeat the process in reverse so that GRAFIK Eye QS B talks to GRAFIK Eye QS A.
To disassociate two wireless GRAFIK Eye QS control units:
Simply repeat the association steps, in the same order; press and hold the bottom scene button on B to disassociate.
Note: The wireless signal has a range of 30 feet (10 m) through standard construction.
Associating GRAFIK Eye QS Wireless Control Units
OK
9-16 1-8
On the unit that will “talk”, press and hold the top and bottom scene buttons for 3 seconds to begin or end association or disassociation with the unit that will “listen”.
OK
9-16
1-8
On the unit that will “listen”, press and hold the top scene button for 3 seconds to associate, or press and hold the bottom scene button for 3 seconds to disassociate with the unit that will “talk”.
Associate
OR
Disassociate
Wireless System Programming
R
GRAFIK Eye® QS Wireless System Programming 3
OK
1 2 3 4 5 6
Wireless Occupancy Sensor “Talks” to GRAFIK Eye QS control unit, activating scenes on the GRAFIK Eye QS.
Lutron’s wireless Radio Powr SavrTM occupancy and vacancy sensors can be associated with the GRAFIK Eye QS Wireless to activate scenes when occupancy or vacancy is detected.
To associate wireless occupancy sensors and GRAFIK Eye QS control units:
1. Press and hold the “Lights On” and “Lights Off” buttons on the front of the occupancy/vacancy sensor simultaneously until the lens starts flashing (about 3 seconds).
2. Press and hold the top scene button of the GRAFIK Eye QS Wireless control unit until the LEDs flash (about 3 seconds).
3. Return to the occupancy sensor. Press and hold the “Lights On” and “Lights Off” buttons simultaneously until the lens stops flashing (about 3 seconds).
To disassociate wireless occupancy sensors and GRAFIK Eye QS control units:
Simply repeat the association steps, in the same order; press and hold the bottom scene button on the GRAFIK Eye QS to disassociate.
Note: The wireless signal has a range of 30 feet (10 m) through standard construction.
Associating Wireless Occupancy Sensors and GRAFIK Eye QS Wireless Control Units
On the wireless occupancy sensor, press and hold the “Lights On” and “Lights Off” buttons for 3 seconds to begin or end association or disassociation with the GRAFIK Eye QS control unit.
Note: Pressing the “Lights On” button initiates the “occupied” scene programmed on the GRAFIK Eye QS control unit. Pressing the “Lights Off” button initiates the “unoccupied” scene programmed on the GRAFIK Eye QS control unit.
Before the GRAFIK Eye QS is programmed, the “Lights On” button may not produce an action. Refer to the Installation manual for the GRAFIK Eye QS to program desired scenes.
OK
9-16
1-8
On the GRAFIK Eye QS control unit, press and hold the top scene button for 3 seconds to associate, or press and hold the bottom scene button for 3 seconds to disassociate with the occupancy sensor.
Associate
OR
Disassociate
GRAFIK Eye QS Control Unit “Listens” to wireless occupancy sensor, so that the occupancy sensor activates scenes on the GRAFIK Eye QS.
Lens