Lutron Electronics QSGRJ-3P, QSGR-4P, QSGRJ-6P, QSGR-3P, QSGR-6P Installation And Operation Manual

...
LUTRON
Control Unit
Installation and Operation Guide
®
Please Read
The GRAFIK Eye® QS control unit allows for control of both lights and shades, without interfaces, using a single control unit. Features include pushbutton scene recall, info screen that displays energy savings and status, IR receiver, astronomic timeclock, contact closure input, and engravable backlit buttons that are easy to find and operate.
Model Numbers: QSGRJ-3P, QSGRJ-4P, QSGRJ-6P
QSGR-3P, QSGR-4P, QSGR-6P
120 V~ 50/60 Hz 220 - 240 V~ 50/60 Hz
Unit Capacity (watts) 2000 W 3000 W
MLV 2000 VA / 1600 W 3000 VA / 2400 W
Zone Capacity (watts) 25 – 800 W 40 – 1200 W
MLV 25 – 800 VA / 25 – 600 W 40 – 1200 VA / 40 – 960 W
See page 7 for IEC PELV/NEC® Class 2 ratings.
For California residents only: The batteries in these devices contain Perchlorate Material – special handling may apply. For more information visit www.dtsc.ca.gov/hazardouswaste/perchlorate
English
Español
Français
®
GRAFIK Eye® QS Control Unit Installation and Operation Guide 2
Contents
Features and Functions of the
GRAFIK Eye® QS Control Unit .................3
Wiring the GRAFIK Eye® QS Control Unit
Overview of Line Voltage/Mains Wiring .........4
Line Voltage Wiring Details...................5
Overview of IEC PELV/NEC® Class 2 Wiring .....7
QS Link Control Wiring Details................8
Powering More Than 3 Wallstations Example....9
Completing Installation of the
GRAFIK Eye® QS Control Unit ............10
General Functionality ...................11
Pre-Programmed Button Functionality .....12
Zone Button Operation
Zone LED Displays for % of Lighting Levels....13
Programming Mode
Entering and Exiting Programming Mode ......14
Navigating Menus in Programming Mode ......14
Wireless Mode......................... 15
FCC Information ..........................15
Zone Setup
Assigning Load Types......................16
Assigning Non-Dim Load Types..............16
Setting Load Types ........................17
Setting High End or Low End Trim............18
Setting Minimum Level (optional).............18
Labeling a Zone (optional) ..................19
Scene Setup
Setting Zone Levels, Fade Rates,
and Shade Group Actions ..................20
Labeling a Scene (optional) .................21
Enabling/Disabling Daylighting in a Scene .....21
Setting Save Mode
Save Mode Settings .......................22
Quick Scene Programming:
Save by OK Mode .........................22
Contact Closure Input (CCI) Setup.........23
Occupancy Sensor Setup................25
Associating Wireless Occupancy Sensors .....26
Selecting the Mode ........................27
Scene Mode .............................28
Zone Mode ..............................29
Labeling an Occupancy Sensor (optional)......30
Configuring Occupancy Sensor Settings
(optional) ................................31
Daylight Sensor Setup ..................32
Associating Wireless Daylight Sensors ........33
Assigning Sensors.........................34
Calibrating Sensors........................34
Labeling a Daylight Sensor (optional) .........35
Pico® Wireless Control Setup .............36
Associating with a GRAFIK Eye® QS
Wireless Control Unit ......................37
Associating through a QS Sensor Module .....38
IR Setup ..............................39
Enabling/Disabling the IR Receiver ...........40
Associating the QS IR Eye with a
GRAFIK Eye® QS Control Unit ...............41
Associating through a QS Sensor Module .....43
Associating Sivoia® QS Shades/Drapes
and GRAFIK Eye® QS Control Units........44
Adjusting Shade Settings
Setting Limits.............................45
Preset Adjustment: Simple Method ...........46
Preset Adjustment: Advanced Method ........46
Naming a Group of Shades .................47
Enable/Disable “Stop If Moving” Functionality . . 48
Associating Sivoia® QS Triathlon® Shades with
GRAFIK Eye® QS Control Unit . . . . . . . . . 49
Setting Upper and Lower Limits of a Sivoia® QS Triathlon® Shade with
GRAFIK Eye® QS Control Unit . . . . . . . . . 50
Associating Multiple GRAFIK Eye® QS
Control Units ..........................51
Timeclock Operation
Setting Time and Date .....................52
Setting Location ..........................53
Setting Daylight Saving Time ................53
Adding an Event ..........................54
Deleting an Event .........................55
Viewing an Event..........................55
Setting a Holiday ..........................56
Viewing a Holiday .........................56
Deleting a Holiday .........................56
Copying a Schedule .......................57
Deleting a Schedule .......................57
Afterhours ............................58
Afterhours Examples.......................59
Setting Up Afterhours ......................60
Ending Afterhours .........................60
Diagnostics and Special Settings
Enabling/Disabling the Timeclock ............61
Enabling/Disabling the Backlighting ..........61
Diagnostics ..............................61
Setting the Security Password ...............62
Language Selection ....................63
Faceplate Removal . . . . . . . . . . . . . . . . . . . . . 63
Troubleshooting .......................64
Troubleshooting: Wireless Functions.......65
Troubleshooting: Shade Functions ........66
Warranty .............................67
Contact Information ....................67
OK
®
GRAFIK Eye® QS Control Unit Installation and Operation Guide 3
Optional Shade
button groups
Preset and raise/lower
buttons with integral LEDs
(maximum of 3 button
groups)
Zone numbers
Zone raise/lower buttons
Zone LEDs display current
lighting zone levels
Hinged faceplate
Hinged faceplate
Features and Functions of the GRAFIK Eye® QS Control Unit
Info screen
Displays status or programming functions
Scene buttons
With integral scene indicator LEDs
Timeclock button
Displays current timeclock info
“OK” button
Used for programming
Infrared receiver
For handheld remote use
Master buttons
Temporarily raise and lower lighting levels on unit
USB Receptacle for PC programming: Micro or Mini B
(To access micro USB receptacle, pull down to remove lower hinged faceplate)
®
GRAFIK Eye® QS Control Unit Installation and Operation Guide 4
Wiring the GRAFIK Eye® QS Control Unit
Overview of Line Voltage/Mains Wiring
1234
12
ABC
123456LN
12 AWG (4.0 mm2) each terminal
120 - 127 V~ or 220 - 240 V~ Distribution Panel
Line Voltage/Mains Cables and Load Wiring
123456LN
Incandescent load
Load controlled by power module or interface
Terminal labels:
L: Hot/Live N: Neutral : Ground
1-6: Dimmed/Switched
line voltage outputs
Power module or interface
®
GRAFIK Eye® QS Control Unit Installation and Operation Guide 5
Wiring the GRAFIK Eye® QS Control Unit (continued)
Line Voltage Wiring Details
• Use properly certified cable for all line voltage/mains cables.
• Proper short-circuit and overload protection must be provided at the distribution panel. You can use up to a 20 A circuit breaker for your installation.
• Install in accordance with all local and national electrical codes.
• IEC PELV/NEC
® Class 2 terminals may
be temporarily unplugged for ease of IR, occupancy sensor, and control wiring.
Notice: Risk of damage to unit. Do not connect line voltage/mains cable to IEC PELV/NEC
® Class 2 terminals.
Step 1: Install wallbox. Mount a 3½ in (89 mm) deep 4-gang U.S. wallbox on a dry, flat indoor surface that is accessible and allows for system programming and operation. Allow at least 4½ in (110 mm) clearance above and below the faceplate to ensure proper heat dissipation. Allow 1 in (25 mm) for faceplate overhang on all sides.
Note: 4-gang wallbox available from Lutron; P/N 241400.
Step 2: Test load wiring.
• Turn power OFF at the circuit breaker or fuse box.
• Connect a standard light switch between the live lead and load wire to test the circuit.
• Turn power ON and check for short or open circuits. If load does not operate, the circuit is open. If the circuit breaker trips (fuse blows or opens), a load short may exist. Correct short or open circuits and test again.
`
Step 3: Check control unit wiring.
Earth/ground terminal connection must
be made as shown in line voltage wiring diagrams.
Do not mix different load types on the
same zone.
• Follow all local and national electrical codes when installing IEC PELV/ NEC
® Class 2 wiring with line voltage/
mains wiring.
WARNING! Shock hazard. May result in serious injury or death. Always turn off circuit breaker or remove main fuse from power line before doing any work. Before connecting the loads to the GRAFIK Eye® QS control unit, test the loads for short-circuits.
Neutral
Hot/Live
Switch
Load
LUTRON
LUTRON
Faceplate overhangs wallbox on all sides; allow 1 in (25 mm)
4` in (110 mm)
®
GRAFIK Eye® QS Control Unit Installation and Operation Guide 6
Wiring the GRAFIK Eye® QS Control Unit (continued)
Line Voltage Wiring Details
Step 4: Connect line voltage and loads to control unit.
• Strip 9 in (8 mm) of insulation off the line voltage/mains cables in the wallbox.
• Connect the line voltage/mains, ground, and load wires to the appropriate terminals on the back of the control unit.
L: Hot/Live N: Neutral : Ground Terminals 1-6: Dimmed/Switched
line voltage outputs
9 in
(8 mm)
The recommended installation torque is
5.0 in∙lb (0.6 N∙m) for line voltage/mains connections and 5.0 in∙lb (0.6 N∙m) for the earth/ground connection.
Note: See the zone setup section for a
list of compatible load types and instructions for programming the GRAFIK Eye
® QS control unit to
properly recognize them.
Notice: Risk of damage to unit. GRAFIK Eye
® QS control units must be in stalled by a
qual i fied electrician in accordance with all applica ble reg u la tions and building codes. Im prop er wiring can result in dam age to control units or oth er equipment.
Note: To avoid over heat ing and pos si ble damage to equipment, do not install control units to dim re cep ta cles, mo tor-op erated ap pli ances, or flu o res cent lighting not equipped with LutronR Hi-lume
®, Eco-10®, Tu-Wire®, electron ic dim ming ballasts, or
other devices approved for your location. In dimmed mag net ic low-voltage cir cuits, you can pre vent trans former overheating and failure by avoid ing excessively high current flow. Do not op erate control units with any lamps re moved or burned out; re place any burned out lamps imme di ate ly; use only transform ers that in cor po rate thermal pro tection or fused pri ma ry wind ings. Control units are de signed for res i den tial and commercial use, for indoor use only.
1234
12
ABC
123456LN
Contact Closure Input Wiring
24 V- 50 mA For settings, see CCI Mode Setup.
®
GRAFIK Eye® QS Control Unit Installation and Operation Guide 7
1234
12
ABC
Example:
Occupancy sensor (maximum 1)
1: COM 2: 24 V-* 3: MUX 4: MUX
Wiring the GRAFIK Eye® QS Control Unit (continued)
Overview of IEC PELV/NEC® Class 2 Wiring
IR Wiring
From external IR connection (by others)
18 AWG (1.0 mm2) each terminal
18 AWG (1.0 mm2) each terminal
1: IR DATA 2: IR COM
A: CCI SIG B: 24 V­C: CCI COM
To control stations, shades, or other GRAFIK Eye
® QS
control units
Data (terminals 3 and 4):
Twisted, shielded pair 22 AWG (0.5 mm2) each terminal
* Do not connect terminal 2
between any GRAFIK Eye
®
QS control unit and any other power supply, including another GRAFIK Eye
® QS control unit.
Refer to the QS Link Power Draw Units specification submittal (LutronR P/N 369405) for more information concerning PDUs.
ABC
Example:
Emergency lighting interface (maximum 1)
Note: The GRAFIK Eye
® QS control unit
must be powered by a Normal/Emergency distribution panel for proper ELI operation. Refer to the LUT-ELI-3PH Installation Guide for the complete wiring diagram.
A: CCI SIG B: 24 V­C: CCI COM
LUT-ELI-3PH
Signal +V Input Circuit Common
Note: Use appropriate wire connecting devices as specified by local codes.
QS Link Control Wiring
24 V- 100 mA
Common and power (terminals 1 and 2):
Two 18 AWG (1.0 mm2) each terminal (for link <500 ft/153 m) Two 12 AWG (4.0 mm2) each terminal (for link 500-2000 ft/153-610 m)
• System communication uses IEC PELV/NEC® Class 2 wiring.
• Follow all local and national electrical codes when installing IEC PELV/NEC® Class 2 wiring with line voltage/mains wiring.
• Each terminal accepts up to two 18 AWG (1.0 mm
2
)
wires.
• Total length of control link must not exceed 2000 ft (610 m).
• Make all connections in the control unit’s wallbox.
• Wiring can be T-tapped or daisy-chained.
• IEC PELV/NEC® Class 2 24 V- 150 mA.
System Limits
The QS wired communication link is limited
to 100 devices or 100 zones. The GRAFIK Eye® QS control unit supplies 3 Power Draw Units (PDUs) on the QS link. Refer to the QS Link Power Draw Units specification submittal (LutronR P/N 369405) for more information concerning Power Draw Units.
®
GRAFIK Eye® QS Control Unit Installation and Operation Guide 8
Wiring the GRAFIK Eye® QS Control Unit (continued)
QS Link Control Wiring Details
QS smart
power
panel
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
T-Tap Wiring Example
GRAFIK Eye® QS
control unit
Sivoia
® QS
shade/drape
seeTouch
® QS
wallstation
LUTRON
LUTRON
LUTRON
LUTRONLUTRON
LUTRON
LUTRON
GRAFIK Eye® QS
control unit
Sivoia
®
QS
shade/
drape
seeTouch
® QS
wallstations
Daisy-Chain Wiring Example
QS smart power panel
GRAFIK Eye
® QS
control unit
Wire Sizes (check compatibility in your area)
QS Link Wiring Length Wire Gauge LutronR Cable Part Number
Less than 500 ft (153 m) Power (terminals 1 and 2); 1 pair 18 AWG (1.0 mm
2
) GRX-CBL-346S (non-plenum)
GRX-PCBL-346S (plenum)
Data (terminals 3 and 4); 1 twisted, shielded pair 22 AWG (0.5 mm2)
Up to 2000 ft (610 m) Power (terminals 1 and 2); 1 pair 12 AWG (4.0 mm2) GRX-CBL-46L (non-plenum)
GRX-PCBL-46L (plenum)
Data (terminals 3 and 4); 1 twisted, shielded pair 22 AWG (0.5 mm2)
Notes:
• For more information regarding LutronR cable specifications, please see LutronR P/N 369596 and P/N 369597 at www.lutron.com
• For wire runs over 2000 ft (610 m), please contact LutronR Technical Support
®
GRAFIK Eye® QS Control Unit Installation and Operation Guide 9
1234
12
ABC
4 3 2 1
4 3 2 1
4 3 2 1
4 3 2 1
123456LN
Wiring the GRAFIK Eye® QS Control Unit (continued)
Powering More Than 3 Wallstations Example
• The +24 VDC wire from the power supply connects to QS link terminal 2 on all of the wallstations it is powering. This wire does not connect to terminal 2 on the GRAFIK Eye
® QS control unit.
The GRAFIK Eye
® QS control unit can power up to 3 seeTouch® wallstations. An external 24 V- power supply is required to power
more than 3 wallstations.
To power source
QSPS-P1-1-50 (powers up to 8 seeTouch
® QS
wallstations)
• The Common wire from the power supply connects to QS link terminal 1 on all of the wallstations it is powering and terminal 1 on the GRAFIK Eye
® QS
control unit.
GRAFIK Eye® QS control unit
(rear view)
1 twisted pair 22 AWG (0.5 mm
2
)
LutronR cable GRX-CBL-346S-500 (non-plenum) or GRX-PCBL-346S-500 (plenum)
seeTouch
® QS wallstations
(1) 18 AWG (1.0 mm
2
)
Common
• The communication signals on the QS link (terminals 3 and 4) connect from the wallstations to the GRAFIK Eye
® QS
control unit on twisted, shielded cable just as when an additional power supply is not being used. Control unit shown in rear view.
®
GRAFIK Eye® QS Control Unit Installation and Operation Guide 10
Completing Installation of the GRAFIK Eye® QS Control Unit
1. Mount the control unit in the wallbox as shown using the four screws pro vid ed.
Note: Follow all local and national electrical codes when installing IEC PELV/NEC
® Class 2 wiring with line
voltage/mains wiring.
2. Verify installation:
• Restore power.
• Press the top scene button. The LED will light.
• Press the zone raise and lower buttons. Make sure the control unit is dimming all connected loads.
3. Apply the protective overlay to the control unit.
Note: When tightening mounting screws, make sure that the hinged cover and faceplate will open fully, as shown.
Wall
7.9 in
(200 mm)
3.5 in (87 mm)
3.75 in
(95 mm)
Protective overlay (apply after installation)
Note: To access micro USB receptacle, pull down to remove lower hinged faceplate.
OK
The info screen turns off 30 seconds after the last button press or completion of the last scene change. See example screens below.
The Master buttons activate the info screen. These buttons temporarily raise or lower all dimmable lights (except those programmed as unaffected in the current scene). Adjustments are temporary and do not affect scene programming.
Note: Master buttons affect all zones.
The “OK” button activates the info screen (when off), which then shows the current scene and its fade time.
In “Save Always” mode, it allows fade time adjustment. In “Save by OK” mode, pressing a second time allows zone adjustment; pressing a third time allows fade adjustment.
The Timeclock button activates the info screen and displays the current time and the next event scheduled to occur. Pressing a second time displays the time, date, and afterhours status. Pressing a third time displays location and sunrise/sunset times. Pressing a fourth time displays the language selection screen. Pressing once more returns to the first screen.
®
GRAFIK Eye® QS Control Unit Installation and Operation Guide 11
Scene 1
Master raise Master lower
General Functionality
OK
Scene 1
Adjust fade
3 seconds
11:23 AM Fri
Next: 5:00 PM
Scene 1
Master buttons
“OK” button
Timeclock (back) button
Pre-Programmed Button Functionality
®
GRAFIK Eye® QS Control Unit Installation and Operation Guide 12
Scene Button Pre-Programming for Dimmable Loads
Scene 1: All zones to 100% Scene 2: All zones to 75% Scene 3: All zones to 50% Scene 4: All zones to 25% All zones Off
Shade Button Pre-Programming for Sivoia® QS shades
All shades fully open All shades to 50% All shades fully closed Lower/Raise all shades (Applies only to units with shade keypads)
The GRAFIK Eye® QS control unit controls most lighting loads without special programming. Each unit ships with pre-programmed default settings for the scene and shade buttons. For load types other than those shown below (dimmable or non-dim), assign the load type before proceeding. See the scene setup section for instructions on changing scene settings.
Zone Button Operation
Each zone column (LEDs and buttons) represents one zone of lights. Pressing any button on a column turns on the info screen and displays the zone’s current light level and current energy savings.
Pressing the raise and lower buttons on a zone causes different actions depending on zone type (see below).
Dimmable zones:
• Press and hold to raise/lower all lights in a zone; release to stop
• Press raise or lower to stop a zone that is fading
• Raising lights from off to full on or lowering from full on to off takes 5 seconds
• Press raise and lower simultaneously to toggle between full on and off
• Press and hold lower for 6 seconds after the zone has gone to 0% light level to set the zone as unaffected in the current scene. The zone will not change when this scene is initiated, and the Master buttons will not raise/lower the zone in this scene.
Non-dim zones:
• Press raise to turn zone on
• Press lower to turn zone off
Note: To set zone types, see the zone
setup section.
®
GRAFIK Eye® QS Control Unit Installation and Operation Guide 13
Zone Raise
Zone Lower
Legend:
UA = Unaffected (lights are not affected by
scene button or Master buttons)
LED on LED off
Zone LEDs LEDs indicate light level (see below)
Zone LED Displays for % of Lighting Levels
Light Level (%)
Off 1–17 18-33 34-49 50-66 67-82 83-99 On/
100
UA
Dimmable Load Types
Non-Dim Load Types
Entering and Exiting Programming Mode
Entering programming mode: Press and hold the top and bottom scene buttons simultaneously for 3 seconds. The LEDs in the scene buttons will scroll from top to bottom, confirming that you are in programming mode, and the info screen will display the main menu.
Exiting programming mode: Press and hold the top and bottom scene buttons simultaneously for 3 seconds. The info screen will go to Scene 1.
Navigating Menus in Programming Mode
Master Buttons The Master buttons allow you to move through the menu choices. The current choice is highlighted on the info screen.
OK Button The “OK” button chooses the current highlighted menu choice. This will either take you to the next menu or accept a setting you have selected. When the screen displays a Yes/No question, the “OK” button is “Yes.”
Timeclock Button The Timeclock button functions as a “back” button during programming mode. Pressing the Timeclock button takes you back one step in the current menu. Pressing it repeatedly will eventually return you to the main menu, but will not exit programming mode. When the screen displays a Yes/No question, the Timeclock button is “No.”
®
GRAFIK Eye® QS Control Unit Installation and Operation Guide 14
Programming Mode
OK
Press and hold the top and bottom buttons for 3 seconds to enter or exit programming mode
Master buttons
“OK” button
Timeclock (back) button
Main menu
Scene setup
Timeclock
Scene 1
Fade time 3 seconds
®
GRAFIK Eye® QS Control Unit Installation and Operation Guide 15
Wireless Mode
Many models of the GRAFIK Eye® QS control unit support wireless communication with
other Lutron® products. This feature allows for easy integration of wireless sensors, keypads, remotes, and shades for single-room wireless applications, as well as compatibility with other LutronR wireless systems such as RadioRA® 2. (See the RadioRA® 2 Setup Guide; LutronR P/N 044254.)
Units supporting wireless communication are labeled “GRAFIK Eye
® QS Wireless” on
the front label of the unit.
The wireless feature of the GRAFIK Eye
® QS Wireless control unit has 3 modes of
operation.
Ignore Programming (default): The GRAFIK Eye
® QS Wireless control unit will only
respond to normal operation commands from wireless devices associated while in “Enabled” mode.
Disabled: Use for wired-only systems.
Enabled (30 minutes): The GRAFIK Eye
® QS Wireless control unit will respond to any
programming commands from nearby LutronR QS wireless (and compatible) products. The GRAFIK Eye® will automatically revert to “Ignore Programming” mode if there is no activity for 30 minutes.
Changing the wireless mode of the GRAFIK Eye
® QS Wireless control unit:
1. Enter programming mode.
2. Use the Master buttons to highlight “Wireless Mode” and press the “OK” button to accept.
3. Use the Master buttons to highlight the desired wireless mode, and press the “OK” button to accept.
4. The info screen will display a confirming “Saved” message.
5. Exit programming mode.
Notes
• The wireless signal has a range of 30 ft (9 m) through standard
construction or 60 ft (18 m) line of sight.
• When used within a RadioRA
® 2 system, the wired QS link on the
GRAFIK Eye® QS control unit is disabled, and certain features that do not pertain to RadioRA® 2 are not accessible.
Wireless Mode
Enabled (30 minutes)
Saved
Saved
Main menu
Shade labels
Wireless Mode
FCC Information
Changes or modifications not expressly approved by Lutron Electronics Co. could void the user’s authority to operate this equipment. Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC rules. Operation is subject to the following: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. These limits are designed to provide reasonable protection against harmful interference in a residential and commercial installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio or television reception. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
OK
Master buttons
“OK” button
Timeclock (back) button
®
GRAFIK Eye® QS Control Unit Installation and Operation Guide 16
Assigning Load Types
1. Enter programming mode.
2. Use the Master buttons to highlight “Zone setup” and press the “OK” button to accept.
3. Use the Master buttons to highlight “Load type.” Press the “OK” button to accept. See “Setting Load Types” table on the next page.
4. Use the zone raise/lower buttons to choose the load type for that zone. See the list on the next page for supported load types. Press the “OK” button to accept.
5. The info screen will confirm that your load type has been saved.
6. Exit programming mode.
Zone Setup
OK
Master buttons
“OK” button
Main menu
CCI Setup
Zone setup
1 2 3 4 5 6
Use the zone raise/lower buttons to choose the load type for that zone.
Zone Setup
Non-Dim Load Type
Load Type
Set zones
Saved
Load Type
Assigning Non-Dim Load Types
Zones assigned to non-dim loads have five available configurations:
• LOFO: Last On, First Off
• FOFO: First On, First Off
• FOLO: First On, Last Off
• LOLO: Last On, Last Off
• 60/40: On at 60%, off at 40% Scenes made up of both dim and non-dim
load types will toggle the non-dim loads before the dim loads in a “First” on/off configuration, and after the dim loads in a “Last” on/off configuration.
1. Enter programming mode.
2. Use the Master buttons to highlight “Zone setup” and press the “OK” button to accept.
3. Use the Master buttons to highlight “Non-Dim Load type.” Press the “OK” button to accept. See “Setting Load Types” table on the next page.
4. Use the zone raise/lower buttons to choose
the non-dim load type for that zone. (Zones not programmed as non-dim will be displayed as Unaffected.) Press the “OK” button to accept.
5. The info screen will confirm that your load type
has been saved.
6. Exit programming mode.
Main menu
CCI Setup
Zone setup
Zone Setup
Load Type
Load Type
Set zones
Saved
Non-Dim Load Type
®
GRAFIK Eye® QS Control Unit Installation and Operation Guide 17
Zone Setup (continued)
Load Type Notes
• All electronic low-voltage (ELV) lighting used with an interface must be rated for reverse phase control dimming. Before installing an ELV light source, verify with the manufacturer that their transformer can be dimmed. When dimming, an ELV interface (such as the PHPM-PA-DV-WH) must be used with the control unit.
• For all DMX or RGB/CMY DMX lighting, an external DMX interface (such as the QSE-CI-DMX) must be used with the control unit.
• Maximum total lighting load for Lutron
® Tu-Wire® and Advance
Mark X® electronic dimming ballasts (120 to 127 V~ only) must not exceed 6 A per zone or 16 A per unit.
Zone ratings:
• Not all zones must be connected; however, connected zones must have a minimum load:
120 - 127 V~: 25 W
220 - 240 V~: 40 W
• Maximum zone loads:
120 - 127 V~: 800 W
220 - 240 V~: 1200 W
• Maximum total lighting load for magnetic low-voltage (MLV) varies by input voltage: 120 - 127 V~: 800 VA / 600 W 220 - 240 V~: 1200 VA / 960 W
LUTRON
LUTRON
Setting Load Types
Direct control via GRAFIK Eye
® QS
control unit
Control via power module or interface
Fixture load type Choose this load type from the menu
on the GRAFIK Eye
® QS control unit:
Zones
1 – 6
Incandescent Incandescent Power module
MLV (magnetic low-voltage) MLV Power module
ELV (electronic low-voltage) Power module
Hi-Lume
®/Eco-10® Fluorescent module
0-10 V Fluorescent module
Non-dim lighting loads Non-dim Non-dim
Neon/Cold cathode Neon, CC Neon, CC
Tu-Wire® Tu-Wire Tu-Wire
Advance Mark X® Tu-Wire Tu-Wire
DMX DMX
RGB/CMY DMX RGB/CMY DMX
Cree LR4/LR6 LED Cree LR4/LR6 LED Fluorescent module
LED Incandescent* Power module
* Use incandescent load type unless otherwise specified in the LED product selection tool available at www.lutron.com/ledtool.
Power module or interface
Setting Minimum Level (optional)
Some local regulations specify a minimum lighting level for dimming zones in occupied buildings. If this pertains to you, follow these steps to set up your minimum lighting level.
1. Enter programming mode and select “Zone setup,” then “Min level.” Press the “OK” button to accept.
2. Use the Master buttons to highlight “Off” if you want your lights to go all the way off at their minimum light level, or “10%” if you want that to be the minimum light level. Press the “OK” button to accept. Note: Non-dim loads will turn off
regardless of the minimum level setting.
3. The info screen will confirm that your minimum level has been saved.
4. Exit programming mode.
®
GRAFIK Eye® QS Control Unit Installation and Operation Guide 18
Zone Setup (continued)
Setting High End or Low End Trim
• If you are unsure about appropriate high and low end settings, please contact LutronR Technical Support for assistance.
• High and low end trim settings limit the maximum and minimum output of a dimming zone. Trim levels are set automatically when the load type is programmed.
1. Enter programming mode.
2. Use the Master buttons to highlight “Zone setup” and press the “OK” button to accept.
3. Use the Master buttons to highlight “High end” or “Low end” (this example shows low end). Press the “OK” button to accept.
4. Use the zone raise/lower buttons to set the high end or low end trim for that zone. The info screen will display each zone number and percentage as you adjust it. Press the “OK” button to accept.
5. The info screen will confirm that your setting has been saved.
6. Exit programming mode.
Main menu
CCI Setup
Zone setup
High end
Zone 2
Low end
Set zones
Low end
OK
Master buttons
1 2 3 4 5 6
Use the zone raise/lower buttons to set the high end or low end trim for that zone.
“OK” button
10%
Min level
Off
Zone setup
Low end
Min level
Zone setup
Saved
Saved
®
GRAFIK Eye® QS Control Unit Installation and Operation Guide 19
Zone Setup (continued)
Labeling a Zone (optional)
1. Enter programming mode.
2. Use the Master buttons to highlight “Zone setup” and press the “OK” button to accept.
3. Use the Master buttons to highlight “Label” and press the “OK” button to accept.
4. Use the Master buttons to change the zone number to your desired zone. Custom zone labels will appear if previously set. Press the “OK” button to accept.
5. Use the Master buttons to highlight “Custom” and press the “OK” button to accept. Or, highlight “Default” to return the zone label to the default (e.g., Zone 1).
6. Use the Master buttons to scroll through the characters (lowercase and uppercase letters, plus numbers 0 through 9). The character you are currently changing will be underlined on the screen. Press OK to select the character you want, then repeat for all available characters. Choose a space (no character) and press OK for any remaining characters. Press the “OK” button to accept.
Note: Custom zone labels will always begin with the zone
number and a colon (e.g., 1: Uplights).
7. The info screen will confirm that your name has been saved.
8. Exit programming mode.
Main menu
CCI Setup
Zone setup
Min level
Label zone
Label
Label zone 2
Custom
Label zone 2
1: A
A
1 / 11
OK
Master buttons
“OK” button
Zone setup
Zone 2
Saved
®
GRAFIK Eye® QS Control Unit Installation and Operation Guide 20
Scene Setup
Setting Zone Levels, Fade Rates, and Shade Group Actions
1. Enter programming mode.
2. Use the Master buttons to highlight “Scene setup” and press the “OK” button to accept.
3. Use the Master buttons to highlight “Levels” to adjust lighting and/or shade levels. Press the “OK” button to accept. Use the Master buttons to highlight the scene number of your desired scene. Press the “OK” button to accept.
4. Set each zone to the desired light level for this scene using the zone raise/lower buttons. The info screen will display the zone and percentage as you adjust it.
To set a zone as unaffected, lower the light levels all the way
to off, then hold the zone lower button for 3 seconds. The screen will display “---” and the three middle LEDs for the zone will be lit to indicate this zone is unaffected by the scene (the zone will not change when this scene is initiated).
When all zones are at the desired level, press the “OK” button
to accept.
5. Use the Master buttons to set the fade time for this scene. Press the “OK” button to accept.
6. Note: This step is applicable only if you have shades on your
system. If you do not have or do not wish to set shade groups for this scene, press the “OK” button to skip this step.
Set each shade group to the desired level for this scene. When all shade groups are at the desired level, press the “OK” button to accept. For shade programming, see the section on adjusting shade settings.
7. The info screen will confirm that your scene has been saved.
8. Exit programming mode.
Main menu
Timeclock
Scene setup
Scene setup
Labels
Levels
Scene 1
Adjust fade seconds
Scene 1
Set shade
Groups
3 seconds
Scene 1
Set zones
Scene setup
Scene 1
Saved
3
Shade button group
Zone raise
Zone lower
OK
Master buttons
“OK” button
Timeclock (back) button
®
GRAFIK Eye® QS Control Unit Installation and Operation Guide 21
Scene Setup (continued)
Labeling a Scene (optional)
1. Enter programming mode.
2. Use the Master buttons to highlight “Scene setup” and press the “OK” button to accept.
3. Use the Master buttons to highlight “Labels” and press the “OK” button to accept.
4. Use the Master buttons to highlight your desired scene. Press the “OK” button to accept.
5. Use the Master buttons to highlight “Custom” and press the “OK” button to accept.
6. Use the Master buttons to scroll through the characters (lowercase and uppercase letters, plus numbers 0 through 9). The character you are currently changing will be underlined on the screen. Press OK to select the character you want, then repeat for all available characters. Choose a space (no character) and press OK for any remaining characters. Press the “OK” button to accept.
7. The info screen will confirm that your name has been saved.
8. Exit programming mode.
Main menu
Timeclock
Scene setup
Labels
Select scene:
Scene 1
Label scene 1
Custom
Label scene 1
1: A
A
1 / 10
OK
Master buttons
“OK” button
Scene setup
Levels
Labels
Saved
Enabling/Disabling Daylighting in a Scene
1. Enter programming mode.
2. Use the Master buttons to highlight “Scene setup” and press the “OK” button to accept.
3. Use the Master buttons to highlight “Daylighting” and press the “OK” button to accept.
4. Use the Master buttons to highlight your desired scene. Press the “OK” button to accept.
5. Use the Master buttons to select “Enable” or “Disable.” When daylighting is disabled in a scene, the GRAFIK Eye
® QS control unit will
not respond to daylight sensors information when that scene is active. Press OK to save.
6. Exit programming mode.
Labels
Daylighting
Scene 1
Scene 1
Daylighting
Enable
Scene setup
Labels
Daylighting
Saved
Loading...
+ 46 hidden pages