Fluorescent Dimmers
Installation Instructions
Please Leave for Occupant
Package Contents and Part Identification
Control
Shaft
Slider
Control
Faceplate
Mounting
Screws
5 Wire
Connectors
Screwdriver
Important Notes
Please Read Before Installation
Switchbox and Location: A single-gang switchbox (3"
high x 2" wide x 2
dimmers. These dimmers are designed to operate in
ambient temperatures from 0
Allow a minimum space of 4
dimmer for proper heat dissipation.
Short Circuit Check: Check new installation for short
circuits prior to installing dimmer. With POWER OFF,
connect incoming neutral to the white wire, and the hot
wire to both ballast input wires (black wire with brown wire
or yellow/blue wire or orange wire, depending on ballast
used). Turn power ON. If lights do not work, or breaker
trips, a short is present. Correct the wiring and check
circuit again. Install dimmer only when short is no longer
present. This check should be done by a qualified
electrician.
Sockets: Use only with rapid start lamp sockets. Lamp
disconnect sockets may be required for use with certain
manufacturer's ballasts. This is in order to meet U.L. and
NEC regulations and maintains personal safety standards.
Lutron does not require lamp disconnect sockets with their
ballasts. Refer to the manufacturer's ballast label for this
information.
Lamps: Use only rapid start fluorescent lamps. Energy
Saver Lamps may NOT be used with this dimmer.
magnetic ballasts only,
lamps in the same circuit. NOTE: For proper dimming
performance lamps must be operated at full intensity for
100 hours prior to dimming.
Ballasts: Use ONLY dimming ballasts listed on chart in
step 2 of Pre-Installation.
not mix 1 and 2 lamp ballasts in any one dimmer circuit. Do
not mix ballasts manufactured by more than one company.
Using single lamp ballasts will produce the most consistent
low end dimming level.
Multi-phased Applications (120/208-3 Phase): In multiphased applications use a separate neutral for each phase
containing a dimmer. Contact the
Assistance Hotline
"Common Neutral Interaction".
1
/2" deep) will service all individual Nova
o
C (32oF) to 40oC (104oF).
1
/2" above and below the
With
do not mix different wattage
With magnetic ballasts only,
Lutron Technical
toll-free for Application Note #17,
do
NF-10, NF-20, NF-30
120VAC, 60Hz
NF-10-277, NF-20-277 277VAC, 60Hz
Pre-Installation
1. Determine the number of dimmers to be ganged in the
same wallbox. If installing a single dimmer in a switchbox,
continue to the "Single Unit Installation" section on page 3.
2. If more than one dimmer is being ganged in the same
wallbox, side sections can be removed to fit in existing
switchboxes. When controlling magnetic ballasts, breaking
side sections off the dimmer will reduce the maximum
number of lamps per dimmer. Use the following charts to
determine the maximum number of lamps per dimmer.
Figure A: Derating Ballast Chart
120V Applications
Magnetic
Ballasts
Controls
Ballasts
Universal
550LTCP†12 24 36 9 22 34 6 19 31
502ATCP†* 12 24 36 9 20 32 4 18 28
Advance
DIM 140H 10 20 30 7 18 27 4 15 25
DIM 240H* 10 20 30 6 18 26 4 14 24
Valmont
8G5001W 12 24 36 9 22 34 6 19 31
8G5007W* 12 24 36 9 20 32 4 18 28
†
can be used with 30W lamps
* 2 lamp ballast
Electronic
Ballasts
Lutron
Hi-lume 16 Amps
Eco-10
** Only NF-10 may be used with Lutron Ballasts. Total Amps are determined by
adding all ballast line currents as indicated on ballast label.
Magnetic
Ballasts
Controls
Ballasts
Magnetek
Universal
679LTCP 12 24 11 21 10 20
678LTCP 12 24 10 20 10 20
Electronic
Ballasts
Lutron
Hi-lume 8 Amps
Eco-10
** Only NF-10-277 may be used with Lutron Ballasts. Total Amps are determined by
adding all ballast line currents as indicated on ballast label.
Number of Side Sections Removed
None One Two
NF-10 NF-20 NF-30 NF-10 NF-20 NF-30 NF-10 NF-20 NF-30
Units listed are maximum number of
NF-10**
NF-10 controls when used with
Lutron electronic dimming
ballasts do not require derating
when side sections are removed.
LAMPS
per control
277V Applications
Number of Side Sections Removed
None One Two
NF-10-277 NF-20-277 NF-10-277 NF-20-277 NF-10-277 NF-20-277
Units listed are maximum number of
NF-10-277**
NF-10-277 controls when used
with Lutron electronic dimming
ballasts do not require derating
when side sections are removed.
LAMPS
per control
These products are covered under one or more of the following U.S. patents:
4,663,570; 4,894,587; 5,001,386; 5,041,763; 5,055,742; 5,173,643; 5,224,029 and
corresponding foreign patents. U.S. and foreign patents pending. Lutron, Hi-lume,
and Nova are registered trademarks and Eco-10 is a trademark of Lutron Electronics
Co., Inc.
1997 Lutron Electronics Co., Inc.
1
Multi-gang Installation
In multi-gang installations several dimmers or controls are
grouped horizontally in one ganged switchbox or in a
series of interconnected switchboxes. Multi-gang
faceplates are available to simplify and improve the
appearance of these installations. A multi-gang mounting
frame is provided with each standard multi-gang faceplate
to ensure proper alignment of dimmers, easy application of
the faceplate, and a flat surface for the installation. This
frame is most easily mounted on the wall before dimmer
wires are connected. Refer to multi-gang instruction sheet
supplied with multigang faceplate.
No Side Sections Removed
(No Derating Required)
Installation of dimmers without removing side sections
allows operation at full capacity (i.e., no derating is
required). Follow instructions below. For retrofit
installations, side sections can be removed to fit existing
switchboxes. See Multi-gang Installation, "Side Sections
Removed" at right.
1. Assure safe operation by using Ballast Chart (Figure
A) to determine maximum number of lamps safely used
with specific ballast. Note: Use ONLY dimming ballasts
listed on chart. Do not use any other ballasts.
2. Determine the number of switchboxes necessary by
using Switchbox Requirement Chart in Figure B. When
ganging any combination of "small" (NF-10, NF-10-277)
and "large" (NF-20, NF-30, NF-20-277) dimmers, place all
small dimmers at one end of the gang and all large
dimmers at the other end.
Figure B: Switchbox Requirement Chart
No Side Sections Removed
Number of Small Controls (NF-10)
0123456
Number 0 0 1 1+1* 4 4+1* 7 7+1*
of Large 113568911
Controls 24679101213
(NF-20, 3 6 8 10 11 13 14 16
NF-30) 4 9 11 12 14 15 17 18
* See Item 3
3. When ganging an EVEN number of SMALL dimmers,
use gangable switchboxes with tapped ears as shown
below. Do not use plaster rings or gangbox covers. Space
an "additional" switchbox
switchbox(es). A 3/4" chase nipple is recommended as a
spacer between the switchboxes. (Example, 4 small
dimmers require 5 switchboxes. See Figure C.)
Figure C: Switchbox Positioning Four-Gang Controls
3
/4" apart from the other
4. Wire each dimmer according to Steps in "Single Unit
Installation" on page 3.
5. Install dimmers in switchbox(es). When combining
small and large dimmers, place all small dimmers on one
extreme end of the gang, and large dimmers at the other
end of the gang. Use center and offset mounting holes as
required for proper alignment. Allow
for ease in attaching faceplate. See Figure D.
Figure D: Front View - Four-Gang Installation
No Side Sections Removed
Offset Mounting Holes
1
/32" between dimmers
1
/32" Spacing
Center Mounting Holes
6. Replace sliders and snap on multi-gang faceplate (or
multiple single faceplates) and adjust up or down for a
snug fit. Multi-gang faceplates (with mounting frames and
instructions) are available in a variety of colors to beautify
and simplify your installation.
Side Sections Removed
(Derating Required)
1. Derating is necessary when side sections are
removed. Use Derating Ballast Chart in Figure A. Match
the dimmer size, number of side sections removed, and
the ballast type to determine maximum safe load.
2. Determine number of switchboxes necessary by using
the Switchbox Requirement Chart in Figure E. When
ganging any combination of "small" dimmers (NF-10, NF10-277) and "large" (NF-20, NF-30, NF-20-277) dimmers,
place all small dimmers at one end of the gang and all
large dimmers at the other end.
Figure E: Switchbox Requirement Chart
Side Sections Removed
Number of Small Controls (NF-10)
0123456
Number 0 0123456
of Large 1 1345678
Controls 2 35678910
(NF-20, 3 5789101112
NF-30) 4 7 9 10 11 12 13 14
Four-gang
gangable wallbox
3
/4" space
(use chase
nipple)
Single-gang
gangable
wallbox
2
3. Remove INNER side sections only. Using pliers, bend
side sections down as far as you can and then back to
their original positions. Side sections will break off. See
Figure E.
DO NOT REMOVE OUTER SIDE SECTIONS OF THE
TWO DIMMERS WHICH ARE ON THE ENDS OF THE
GANG.