Switchbox and Location: A single-gang switchbox (3"
high x 2" wide x 2
dimmers. These dimmers are designed to operate in
ambient temperatures from 0
Allow a minimum space of 4
dimmer for proper heat dissipation.
Short Circuit Check: Check new installation for short
circuits prior to installing dimmer. With POWER OFF,
connect incoming neutral to the white wire, and the hot
wire to both ballast input wires (black wire with brown wire
or yellow/blue wire or orange wire, depending on ballast
used). Turn power ON. If lights do not work, or breaker
trips, a short is present. Correct the wiring and check
circuit again. Install dimmer only when short is no longer
present. This check should be done by a qualified
electrician.
Sockets: Use only with rapid start lamp sockets. Lamp
disconnect sockets may be required for use with certain
manufacturer's ballasts. This is in order to meet U.L. and
NEC regulations and maintains personal safety standards.
Lutron does not require lamp disconnect sockets with their
ballasts. Refer to the manufacturer's ballast label for this
information.
Lamps: Use only rapid start fluorescent lamps. Energy
Saver Lamps may NOT be used with this dimmer.
magnetic ballasts only,
lamps in the same circuit. NOTE: For proper dimming
performance lamps must be operated at full intensity for
100 hours prior to dimming.
Ballasts: Use ONLY dimming ballasts listed on chart in
step 2 of Pre-Installation.
not mix 1 and 2 lamp ballasts in any one dimmer circuit. Do
not mix ballasts manufactured by more than one company.
Using single lamp ballasts will produce the most consistent
low end dimming level.
Multi-phased Applications (120/208-3 Phase): In multiphased applications use a separate neutral for each phase
containing a dimmer. Contact the
Assistance Hotline
"Common Neutral Interaction".
1
/2" deep) will service all individual Nova
o
C (32oF) to 40oC (104oF).
1
/2" above and below the
With
do not mix different wattage
With magnetic ballasts only,
Lutron Technical
toll-free for Application Note #17,
do
NF-10, NF-20, NF-30
120VAC, 60Hz
NF-10-277, NF-20-277277VAC, 60Hz
Pre-Installation
1. Determine the number of dimmers to be ganged in the
same wallbox. If installing a single dimmer in a switchbox,
continue to the "Single Unit Installation" section on page 3.
2. If more than one dimmer is being ganged in the same
wallbox, side sections can be removed to fit in existing
switchboxes. When controlling magnetic ballasts, breaking
side sections off the dimmer will reduce the maximum
number of lamps per dimmer. Use the following charts to
determine the maximum number of lamps per dimmer.
NF-10-277 controls when used
with Lutron electronic dimming
ballasts do not require derating
when side sections are removed.
LAMPS
per control
These products are covered under one or more of the following U.S. patents:
4,663,570; 4,894,587; 5,001,386; 5,041,763; 5,055,742; 5,173,643; 5,224,029 and
corresponding foreign patents. U.S. and foreign patents pending. Lutron, Hi-lume,
and Nova are registered trademarks and Eco-10 is a trademark of Lutron Electronics
Co., Inc.
1997 Lutron Electronics Co., Inc.
1
Multi-gang Installation
In multi-gang installations several dimmers or controls are
grouped horizontally in one ganged switchbox or in a
series of interconnected switchboxes. Multi-gang
faceplates are available to simplify and improve the
appearance of these installations. A multi-gang mounting
frame is provided with each standard multi-gang faceplate
to ensure proper alignment of dimmers, easy application of
the faceplate, and a flat surface for the installation. This
frame is most easily mounted on the wall before dimmer
wires are connected. Refer to multi-gang instruction sheet
supplied with multigang faceplate.
No Side Sections Removed
(No Derating Required)
Installation of dimmers without removing side sections
allows operation at full capacity (i.e., no derating is
required). Follow instructions below. For retrofit
installations, side sections can be removed to fit existing
switchboxes. See Multi-gang Installation, "Side Sections
Removed" at right.
1. Assure safe operation by using Ballast Chart (Figure
A) to determine maximum number of lamps safely used
with specific ballast. Note: Use ONLY dimming ballasts
listed on chart. Do not use any other ballasts.
2. Determine the number of switchboxes necessary by
using Switchbox Requirement Chart in Figure B. When
ganging any combination of "small" (NF-10, NF-10-277)
and "large" (NF-20, NF-30, NF-20-277) dimmers, place all
small dimmers at one end of the gang and all large
dimmers at the other end.
Figure B: Switchbox Requirement Chart
No Side Sections Removed
Number of Small Controls (NF-10)
0123456
Number0011+1*44+1*77+1*
of Large113568911
Controls 24679101213
(NF-20,3681011131416
NF-30)49111214151718
* See Item 3
3. When ganging an EVEN number of SMALL dimmers,
use gangable switchboxes with tapped ears as shown
below. Do not use plaster rings or gangbox covers. Space
an "additional" switchbox
switchbox(es). A 3/4" chase nipple is recommended as a
spacer between the switchboxes. (Example, 4 small
dimmers require 5 switchboxes. See Figure C.)
4. Wire each dimmer according to Steps in "Single Unit
Installation" on page 3.
5. Install dimmers in switchbox(es). When combining
small and large dimmers, place all small dimmers on one
extreme end of the gang, and large dimmers at the other
end of the gang. Use center and offset mounting holes as
required for proper alignment. Allow
for ease in attaching faceplate. See Figure D.
Figure D: Front View - Four-Gang Installation
No Side Sections Removed
Offset Mounting Holes
1
/32" between dimmers
1
/32" Spacing
Center Mounting Holes
6. Replace sliders and snap on multi-gang faceplate (or
multiple single faceplates) and adjust up or down for a
snug fit. Multi-gang faceplates (with mounting frames and
instructions) are available in a variety of colors to beautify
and simplify your installation.
Side Sections Removed
(Derating Required)
1. Derating is necessary when side sections are
removed. Use Derating Ballast Chart in Figure A. Match
the dimmer size, number of side sections removed, and
the ballast type to determine maximum safe load.
2. Determine number of switchboxes necessary by using
the Switchbox Requirement Chart in Figure E. When
ganging any combination of "small" dimmers (NF-10, NF10-277) and "large" (NF-20, NF-30, NF-20-277) dimmers,
place all small dimmers at one end of the gang and all
large dimmers at the other end.
Figure E: Switchbox Requirement Chart
Side Sections Removed
Number of Small Controls (NF-10)
0123456
Number00123456
of Large11345678
Controls235678910
(NF-20,35789101112
NF-30)4791011121314
Four-gang
gangable wallbox
3
/4" space
(use chase
nipple)
Single-gang
gangable
wallbox
2
3. Remove INNER side sections only. Using pliers, bend
side sections down as far as you can and then back to
their original positions. Side sections will break off. See
Figure E.
DO NOT REMOVE OUTER SIDE SECTIONS OF THE
TWO DIMMERS WHICH ARE ON THE ENDS OF THE
GANG.
Single Unit Installation
Figure E: Side Section Removal
Side section break-off points
4. Wire each dimmer according to Steps in "Single Unit
Installation" on page 3.
5. Install dimmers in switchbox(es). Use center mounting
holes as required for first unit, then use offset mounting
holes as required for proper alignment. Remember to keep
all small dimmers grouped together. See Figure F.
Figure F: Front View - Four-Gang Installation
Side Sections Removed
Inner Side Sections
Removed
Offset Mounting Holes
Center Mounting Holes
6. Replace sliders and snap on multi-gang faceplate (or
multiple single faceplates) and adjust up or down for a
snug fit. Multi-gang faceplates (with mounting frames and
instructions) are available in a variety of colors to beautify
and simplify your installation. See Figure G.
Figure G: Multi-Gang Unit With Faceplate
1. TURN POWER OFF at fuse box or circuit breaker.
Wiring with power on can result in personal injury. Damage
caused by wiring with power on will void the warranty.
2. Remove faceplate and slider from dimmer to prevent
surface damage and to access mounting holes. Pull out at
top and bottom edges, plate will snap off.
3. Strip switchbox wires to the following lengths:
5
/8" for No. 16 and 18 gauge
1
/2" for No. 10, 12, and 14 gauge
1/2" or 5/8"
4. Use wire connectors supplied to make the connections
shown in Figure I. Refer to the appropriate wiring diagram
for your application on page 4, when installing dimmer.
Additional wiring information may be found on ballast.
Figure I: Switchbox Wiring
To
Ballasts
To Fuse Box or
Curcuit Breaker
Ground
Control
Switch Hot
Neutral
Hot
Yellow
Red
White
Black
Green or Bare
Cutting Faceplates When Removing Side Sections:
Faceplates will need to be cut if side sections are removed
when not using a multi-gang faceplate. Place faceplate on
a soft cloth face down. Press firmly and score the groove
on the back of faceplate with a razor sharp knife, using
vertical groove to keep knife on a straight course. Bend
section back and forth to break it off. Smooth edges by
placing fine-grained sandpaper on a flat surface and
rubbing edge of faceplate over the sandpaper a few times.
Hold faceplate steady as you rub to keep a straight edge.
See Figure H.
Figure H: Cutting Faceplate
Multigang faceplates, which eliminate the need to cut
individual faceplates, are available from Lutron.
5. Carefully push wires into switchbox allowing room for
the dimmer's backcover.
6. Mount dimmer into the switchbox using center
mounting holes in dimmer base and screws provided. See
Figure K. Unit MUST be mounted vertically.
Figure K: Front View - Single Unit Installation
Trimpot Shaft
Offset Mounting HolesCenter Mounting Holes
7. Turn power ON.
3
Black
Red
Hot
Neutral
120VAC 60Hz
or
277VAC 60Hz
White
Yellow
To Additional Ballasts
Orange
Black
White
Orange
Black
White
Lutron Dimming Ballast
Lutron Dimming Ballast
Dimmer
8. For Lutron electronic ballasts ONLY:
This unit is factory-calibrated and does not require low-end
light adjustment when used with Lutron FDB or ECO-10
electronic ballasts. If lamps flicker or drop out at minimum
dimming level, there may be an installation error.
Continued use of the system in this mode will cause
premature lamp failure. If this condition exists, call the
Lutron Technical Assistance Hotline
at: 1-800-523-
9466.
For magnetic ballasts ONLY:
a) Run lamps at full intensity (slider at top position) for 15
minutes to warm lamps. Note: For proper dimming
performance lamps must be operated at full intensity for
100 hours prior to dimming.
b) After 15 minutes push slider to low intensity position (as
far down as possible without clicking off).
c) Locate trimpot adjustment shaft shown in Figure K.
d) Minimum light intensity is initially set at the factory. Use
the screwdriver provided to turn the trimpot screw
(inside trimpot shaft) clockwise to increase light level
and counterclockwise to lower light level.
9. Replace slider and snap faceplate on dimmer by
pressing firmly at the top, center, and bottom tabs.
NF-10/NF-10-277 with Lutron Ballast
NF-10, NF-20, NF-30, NF-10-277, NF-20-277
with Magnetic Ballast
With one lamp ballast
Dimmer
Hot
120VAC 60Hz
or
277VAC 60Hz
Neutral
Black
Green or
Bare
Ground
Yellow
Red
White
Worldwide Technical and Sales
Assistance
If you have questions concerning the installation or
operation or this product, call the
Assistance Hotline
:
(800) 523-9466 (U.S.A., Canada, and the Caribbean)
Other countries call (610) 282-3800
Fax (610) 282-3090
Warranty
Lutron will, at its option, repair or replace any unit that is defective in materials or
manufacture within one year after purchase. For warranty service, return unit to place
of purchase or mail to LUTRON at 7200 Suter Road, Coopersburg, PA 18036-1299,
postage prepaid.
This warranty is in lieu of all other warranties, express or implied, and the implied
warranty of merchantability is limited to one year from purchase. This warranty
does not cover the cost of installation, removal, or reinstallation, or damage
resulting from misuse, abuse, or damage resulting from improper wiring or
installation.
This warranty gives you specific legal rights, and you may also have other rights which
vary from state to state. Some states do not allow the exclusion or limitation of
incidental or consequential damages or limitations on how long an implied warranty
may last, so the above limitations may not apply to you.
Lutron Technical
Black
White
* Lamp
Disconnect
Socket
Blue
*
With two lamp ballast
Hot
120VAC 60Hz
or
277VAC 60Hz
Neutral
* Lamp
Disconnect
Socket
Green or
Bare
Black
White
Blue/White
Blue
*
*
Black
Ground
Dimmer
White
Ballast
Lamp
Yellow
Red
Ballast
Lamp
Lamp
Yellow/Blue or Brown
Red
Red
Yellow/Blue or Brown
Yellow
Yellow
Red
Red
4
Lutron Electronics Co., Inc.
7200 Suter Road
Coopersburg, PA 18036-1299 U.S.A.
Made and printed in U.S.A. 8/97 P/N 031-176 Rev. A