Lutron Electronics Nova NF-10, NovaNF-20, Nova NF-30, Nova NF-10-277, Nova NF-20-277 Installation Instructions Manual

Fluorescent Dimmers
Installation Instructions
Please Leave for Occupant
Package Contents and Part Identification
Control Shaft
Slider
Control
Faceplate
Mounting
Screws
5 Wire
Connectors
Screwdriver
Important Notes Please Read Before Installation
Switchbox and Location: A single-gang switchbox (3"
high x 2" wide x 2 dimmers. These dimmers are designed to operate in ambient temperatures from 0 Allow a minimum space of 4 dimmer for proper heat dissipation.
Short Circuit Check: Check new installation for short circuits prior to installing dimmer. With POWER OFF, connect incoming neutral to the white wire, and the hot wire to both ballast input wires (black wire with brown wire or yellow/blue wire or orange wire, depending on ballast used). Turn power ON. If lights do not work, or breaker trips, a short is present. Correct the wiring and check circuit again. Install dimmer only when short is no longer present. This check should be done by a qualified electrician.
Sockets: Use only with rapid start lamp sockets. Lamp disconnect sockets may be required for use with certain manufacturer's ballasts. This is in order to meet U.L. and NEC regulations and maintains personal safety standards. Lutron does not require lamp disconnect sockets with their ballasts. Refer to the manufacturer's ballast label for this information.
Lamps: Use only rapid start fluorescent lamps. Energy Saver Lamps may NOT be used with this dimmer.
magnetic ballasts only,
lamps in the same circuit. NOTE: For proper dimming performance lamps must be operated at full intensity for 100 hours prior to dimming.
Ballasts: Use ONLY dimming ballasts listed on chart in step 2 of Pre-Installation. not mix 1 and 2 lamp ballasts in any one dimmer circuit. Do not mix ballasts manufactured by more than one company. Using single lamp ballasts will produce the most consistent low end dimming level.
Multi-phased Applications (120/208-3 Phase): In multi­phased applications use a separate neutral for each phase containing a dimmer. Contact the
Assistance Hotline
"Common Neutral Interaction".
1
/2" deep) will service all individual Nova
o
C (32oF) to 40oC (104oF).
1
/2" above and below the
With
do not mix different wattage
With magnetic ballasts only,
Lutron Technical
toll-free for Application Note #17,
do
NF-10, NF-20, NF-30
120VAC, 60Hz
NF-10-277, NF-20-277 277VAC, 60Hz
Pre-Installation
1. Determine the number of dimmers to be ganged in the
same wallbox. If installing a single dimmer in a switchbox, continue to the "Single Unit Installation" section on page 3.
2. If more than one dimmer is being ganged in the same
wallbox, side sections can be removed to fit in existing switchboxes. When controlling magnetic ballasts, breaking side sections off the dimmer will reduce the maximum number of lamps per dimmer. Use the following charts to determine the maximum number of lamps per dimmer.
Figure A: Derating Ballast Chart
120V Applications
Magnetic Ballasts
Controls Ballasts
Universal
550LTCP†12 24 36 9 22 34 6 19 31 502ATCP†* 12 24 36 9 20 32 4 18 28
Advance
DIM 140H 10 20 30 7 18 27 4 15 25 DIM 240H* 10 20 30 6 18 26 4 14 24
Valmont
8G5001W 12 24 36 9 22 34 6 19 31 8G5007W* 12 24 36 9 20 32 4 18 28
can be used with 30W lamps
* 2 lamp ballast
Electronic Ballasts
Lutron
Hi-lume 16 Amps Eco-10
** Only NF-10 may be used with Lutron Ballasts. Total Amps are determined by adding all ballast line currents as indicated on ballast label.
Magnetic Ballasts
Controls Ballasts
Magnetek Universal
679LTCP 12 24 11 21 10 20 678LTCP 12 24 10 20 10 20
Electronic Ballasts
Lutron
Hi-lume 8 Amps Eco-10
** Only NF-10-277 may be used with Lutron Ballasts. Total Amps are determined by adding all ballast line currents as indicated on ballast label.
Number of Side Sections Removed
None One Two
NF-10 NF-20 NF-30 NF-10 NF-20 NF-30 NF-10 NF-20 NF-30
Units listed are maximum number of
NF-10**
NF-10 controls when used with Lutron electronic dimming ballasts do not require derating when side sections are removed.
LAMPS
per control
277V Applications
Number of Side Sections Removed
None One Two
NF-10-277 NF-20-277 NF-10-277 NF-20-277 NF-10-277 NF-20-277
Units listed are maximum number of
NF-10-277**
NF-10-277 controls when used with Lutron electronic dimming ballasts do not require derating when side sections are removed.
LAMPS
per control
These products are covered under one or more of the following U.S. patents: 4,663,570; 4,894,587; 5,001,386; 5,041,763; 5,055,742; 5,173,643; 5,224,029 and corresponding foreign patents. U.S. and foreign patents pending. Lutron, Hi-lume, and Nova are registered trademarks and Eco-10 is a trademark of Lutron Electronics Co., Inc. 1997 Lutron Electronics Co., Inc.
1
Multi-gang Installation
In multi-gang installations several dimmers or controls are grouped horizontally in one ganged switchbox or in a series of interconnected switchboxes. Multi-gang faceplates are available to simplify and improve the appearance of these installations. A multi-gang mounting frame is provided with each standard multi-gang faceplate to ensure proper alignment of dimmers, easy application of the faceplate, and a flat surface for the installation. This frame is most easily mounted on the wall before dimmer wires are connected. Refer to multi-gang instruction sheet supplied with multigang faceplate.
No Side Sections Removed (No Derating Required)
Installation of dimmers without removing side sections allows operation at full capacity (i.e., no derating is required). Follow instructions below. For retrofit installations, side sections can be removed to fit existing switchboxes. See Multi-gang Installation, "Side Sections Removed" at right.
1. Assure safe operation by using Ballast Chart (Figure
A) to determine maximum number of lamps safely used with specific ballast. Note: Use ONLY dimming ballasts listed on chart. Do not use any other ballasts.
2. Determine the number of switchboxes necessary by
using Switchbox Requirement Chart in Figure B. When ganging any combination of "small" (NF-10, NF-10-277) and "large" (NF-20, NF-30, NF-20-277) dimmers, place all small dimmers at one end of the gang and all large dimmers at the other end.
Figure B: Switchbox Requirement Chart
No Side Sections Removed
Number of Small Controls (NF-10)
0123456
Number 0 0 1 1+1* 4 4+1* 7 7+1* of Large 113568911 Controls 24679101213 (NF-20, 3 6 8 10 11 13 14 16 NF-30) 4 9 11 12 14 15 17 18
* See Item 3
3. When ganging an EVEN number of SMALL dimmers,
use gangable switchboxes with tapped ears as shown below. Do not use plaster rings or gangbox covers. Space an "additional" switchbox switchbox(es). A 3/4" chase nipple is recommended as a spacer between the switchboxes. (Example, 4 small dimmers require 5 switchboxes. See Figure C.)
Figure C: Switchbox Positioning Four-Gang Controls
3
/4" apart from the other
4. Wire each dimmer according to Steps in "Single Unit
Installation" on page 3.
5. Install dimmers in switchbox(es). When combining
small and large dimmers, place all small dimmers on one extreme end of the gang, and large dimmers at the other end of the gang. Use center and offset mounting holes as required for proper alignment. Allow for ease in attaching faceplate. See Figure D.
Figure D: Front View - Four-Gang Installation
No Side Sections Removed
Offset Mounting Holes
1
/32" between dimmers
1
/32" Spacing
Center Mounting Holes
6. Replace sliders and snap on multi-gang faceplate (or
multiple single faceplates) and adjust up or down for a snug fit. Multi-gang faceplates (with mounting frames and instructions) are available in a variety of colors to beautify and simplify your installation.
Side Sections Removed (Derating Required)
1. Derating is necessary when side sections are
removed. Use Derating Ballast Chart in Figure A. Match the dimmer size, number of side sections removed, and the ballast type to determine maximum safe load.
2. Determine number of switchboxes necessary by using
the Switchbox Requirement Chart in Figure E. When ganging any combination of "small" dimmers (NF-10, NF­10-277) and "large" (NF-20, NF-30, NF-20-277) dimmers, place all small dimmers at one end of the gang and all large dimmers at the other end.
Figure E: Switchbox Requirement Chart
Side Sections Removed
Number of Small Controls (NF-10)
0123456
Number 0 0123456 of Large 1 1345678 Controls 2 35678910 (NF-20, 3 5789101112 NF-30) 4 7 9 10 11 12 13 14
Four-gang gangable wallbox
3
/4" space (use chase nipple)
Single-gang gangable wallbox
2
3. Remove INNER side sections only. Using pliers, bend
side sections down as far as you can and then back to their original positions. Side sections will break off. See Figure E.
DO NOT REMOVE OUTER SIDE SECTIONS OF THE TWO DIMMERS WHICH ARE ON THE ENDS OF THE GANG.