Lutron Electronics Maestro MS-OPS6-DDV, Maestro MS-PPS6-DDV User Manual

I
I
I
I
I
I
Dual-Circuit Occupancy
I
I
I
I
I
I
Sensing Switch
MS-OPS6-DDV
Occupancy
Single-pole only
Two circuits, each rated at: Lighting
(incandescent, halogen, CFL, LED, ELV, MLV, electronic fluorescent, magnetic fluorescent)
120-277 V~ 50 / 60 Hz 6 A Fan 120 V~ 50 / 60 Hz 4.4 A 1/6 HP Combined lighting and fan load 120 V~ 50 / 60 Hz 4.4 A
P/N 032444 Rev. A 11/2013
Major motion coverage: 30 ft × 30 ft (9 m × 9 m) [900 ft2 (81 m2)]
Minor motion coverage: 20 ft × 20 ft (6 m × 6 m) [400ft
Lutron Electronics Co., Inc. 7200 Suter Road Coopersburg, PA 18036-1299 U.S.A.
www.lutron.com
MS-PPS6-DDV
Partial-ON only
English
®
Circuit1 Tap Button
Top programming button
Bottom programming button
Circuit2 Tap Button
2
(36m2)]
Important Notes
®
Please read before installing.
1. Device will not function if it is not grounded. Both bare and green ground
wires are required to connect to ground. If no ground is available, consult an electrician.
2. Device will not function if Black wires (Circuit 1/Line 1) are not wired.
3. This product is rated to control 6 A per circuit. Circuits may NOT be wired in
parallel to control loads greater than 6 A.
4. CAUTION: Risk of Electric Shock — More than one disconnect switch may be required to de-energize the equipment before installing the unit, rewiring, or replacing bulbs.
5. When power is applied, the dual­circuit sensing switch can be manually turned on or off after 60 seconds and
Wiring
Turn power OFF
1
WARNING! Shock Hazard. May result in serious injury or death. Turn power OFF at circuit breaker(s) before installing the unit, rewiring, or replacing bulbs.
A
.
O
O
O
Single-Line
* Wiring must comply with NEC code for wiring Multiple Branch Circuits: Where two or more branch circuits
supply devices or equipment on the same yoke, a means to simultaneously disconnect the ungrounded conductors supplying those devices shall be provided at the point at which the branch circuits originate.
Connect dual-circuit sensing switch
2
A
. Single-Line Wiring
120-277 V~
B
OR
Black-Orange
.
Two-Line*
Black
O
O
O
1
Black
Black-Orange
Load 1
Load 2
will automatically control the load after 2minutes.
6. The dual-circuit sensing switch requires an unobstructed view of the room and line-of-sight to detect motion.
7. Hot objects or moving air currents can affect the performance of the dual-circuit sensing switch and may cause the sensor to turn on unexpectedly or maintain its current state longer than desired.
8. CAUTION: To reduce the risk of overheating and possible damage to other equipment, DO NOT use to control receptacles.
B
. Two-Line Wiring
120-277 V~
120-277 V~
Neutral
Line 1
Line 2
1
Black
Black-Orange
GreenBare
Ground
Black
Black-Orange
2
Load 1
Load 2
9. Install in accordance with all national and local electrical codes.
10. For indoor use only. Operate between 32°F and 104°F (0 °C and 40 °C).
Bare
Green
11. DO NOT exceed 20 devices at 120V~ or 7 devices at 277 V~ on a single branch circuit.
12. Clean with a soft damp cloth only. DONOT
use any chemical cleaners.
Limited Warranty (Valid only in U.S.A., Canada, Puerto Rico, and the Caribbean). Lutron will, at its option, repair or replace any unit that is defective in materials or manufacture within five years after purchase. For warranty service, return unit to place of purchase or mail to Lutron at 7200 Suter Rd., Coopersburg, PA 18036-1299, postage pre-paid. This warranty is in lieu of all other express warranties, and the implied warranty of merchantability is limited to FIVE years from purchase. This warranty does not cover the cost of installation, removal or reinstallation, or damage resulting from misuse, abuse, or damage from improper wiring or installation. This warranty does not cover incidental or consequential damages.
Lutron’s liability on any claim for damages arising out of or in connection with the manufacture, sale, installation, delivery, or use of the unit shall never exceed the purchase price of the unit. This warranty gives you specific legal rights, and you may
have other rights which vary from state to state. Some states do not allow the exclusion or limitation of incidental or consequential damages, or limitation on how long an implied warranty may last, so the above limitations may not apply to you. Lutron and Maestro are registered trademarks of Lutron Electronics Co., Inc. © 2013 Lutron Electronics Co., Inc.
Neutral 2
Neutral 1
1
Device will not function if Black wires (Circuit 1/ Line 1) are not wired.
2
Device will not function if it is not grounded.
NOTE: Leave wallplate off if custom settings are desired. See Custom Settings instructions on reverse side.
Turn Power ON
3
A
.
Wait for 60 seconds before manual switching
4
O
O
O
OR
B
.
O
O
O
• The sensing switch will not manually control the load for 60 seconds.
Wait for an additional 60 seconds for automatic switching
5
• Once power has been restored, the sensing switch will not automatically control the load for the first 2 minutes.
Ground
2
60 s
60 s
Adjustable Settings
®
Before proceeding, select your preferred settings from the table below; default settings are shown in bold. Read all instructions before continuing.
Press and hold the
1
buttons indicated in the pictures.
Timeout
Total
1 Test Mode
number of
2 1 minute 1 minute
flashes
3 5 minutes 5 minutes
4 15 minutes 15 minutes
5 30 minutes 30 minutes
Sensor Mode
Total number
Auto-ON/Auto-OFF
1
(Occupancy mode)
of flashes
Manual-ON/Auto-OFF
2
(Vacancy mode)
Advanced Auto-On Modes
Total
1 Ambient Light Detect (ALD)
number of
2 Off-While-Occupied Enabled
flashes
3 Off-While-Occupied Disabled
Sensitivity
Total
1 Low
number of
2 High
flashes
3 Restore ALL settings to default
2
The lens will flash once at each setting (always starts at setting 1). Example: To set the Timeout to 1 minute, press and hold the tap button. Release the button after the lens flashes for the second time.
Circuit 1
1
2
Circuit 1
Test Mode
1
Circuit 2
Circuit 2
Auto-ON/Auto-OFF (Occupancy mode)
Manual-ON/Auto-OFF (Vacancy mode)
3
4,5,7
6,7
Technical Assistance: www.lutron.com | U.S.A., Canada, Caribbean: 1.800.523.9466 | Mexico: +1.888.235.2910 | Others: +1.610.282.3800
The setting is saved
3
after the button(s) is (are) released.
1
2
3
4
5
6
7
NOTES
Short (less than
15-second) timeout for testing sensor coverage. Device will exit test mode automatically after 5minutes, or when any button is pressed.
Default Sensor Mode
settings are locked in the MS-PPS6-DDV (Partial-ON model only) to satisfy the CEC 2013 Title24 definition for a “Partial-ON” sensor.
These settings
apply to all circuits set to “Auto-ON” (Occupancy) mode.
Lights turn on only if
natural light in room is low. If switch turns on when there is enough natural light, or if switch does not turn on when there is not enough natural light, press the appropriate tap button within 5seconds of entering the room. Over time, the switch will learn your preferred setting.
If ALD mode is
selected, fan loads should be set to Manual-ON/Auto-OFF.
After manual shutoff,
sensor will keep lights off for as long as space is occupied and timeout has not expired.
For more information
on Off-While-Occupied and ALD, please visit
www.lutron.com/ DCSensorInstall
Questions?
For additional instructions, information, and product application information, please review Application Note #489 (P/N 048489) at www.lutron.com/DCSensorInstall
Troubleshooting
Symptom Solution
Sensor modes can’t be changed.
Power can’t be switched ON or OFF with newly installed sensing switch.
Lights turn OFF while space is occupied.
Lights do not turn ON when space is occupied.
Lights turn back ON after they are manually turned OFF.
Tap buttons control the wrong circuits.
Lights stay ON after space is vacated.
• User has the “Partial-ON” version of this product. Sensor modes are not adjustable in this model number (MS-PPS6-DDV).
• Connect green and bare wires to ground. Ground is required for sensor to function.
• After power is restored to the sensor, it will take 2 minutes before the unit is fully functional.
• Sensor’s timeout is too short for this application; increase the timeout.
• Sensor doesn’t have full view of the room; move objects blocking its line of sight.
• Sensor’s sensitivity is set too low; change it to high sensitivity.
• Sensor mode is set to Manual-ON (Vacancy).
• Ambient Light Detection (ALD) mode is enabled and the room is too bright. Continue to turn lights on within 5 seconds of entering room to teach the unit your preferred daylight threshold.
• Sensor does not have full view of the room. Move objects blocking sensor’s line of sight.
• Sensor is in Off-While-Occupied mode and the timeout has not expired.
• Off-While-Occupied is disabled: sensor will turn lights back on 25seconds after being turned off; Enable Off-While-Occupied.
• Switch wiring of product to match desired zones.
• Find “zone mapping” programming at www.lutron.com/DCSensorInstall.
• Check room to ensure that no hot or moving objects or air currents are in the sensor’s line of sight. These can cause false-tripping of the sensor.
I
I
I
I
I
I
Sensor de ocupación con
I
I
I
I
I
I
interruptor de doble circuito
MS-OPS6-DDV
Ocupación
Sólo polo único
Dos circuitos, cada uno certificado a: Iluminación
(incandescente, halógeno, LFCA, LED, BVE, BVM, fluorescente electrónica, fluorescente magnética)
120-277 V~ 50 / 60 Hz 6 A Ventilador 120 V~ 50 / 60 Hz 4,4 A 1/6 HP Carga combinada de iluminación y ventilador 120 V~ 50 / 60 Hz 4,4 A
P/N 032444 Rev. A 11/2013
Cobertura mayor de movimiento: 9 m × 9 m (30 pi × 30 pi) [81 m2 (900 pi2)]
Cobertura menor de movimiento: 6 m × 6 m (20 pi × 20 pi) [36 m2 (400 pi2)]
Lutron Electronics Co., Inc. 7200 Suter Road Coopersburg, PA 18036-1299 E.U.A.
www.lutron.com
MS-PPS6-DDV
Sólo Parcial­ACTIVADO
Español
Tecla de circuito 1
Botón superior de programación
Botón inferior de programación
Tecla de circuito 2
®
Notas importantes
®
Por favor lea antes de instalar.
1. El dispositivo no funcionará si no está puesto a tierra. Para la conexión a tierra se requieren
tanto el cable de tierra verde como el pelado. Si no hay una toma de tierra disponible, consulte con un electricista.
2. El dispositivo no funcionará si no están conectados los cables negros (Circuito 1/Línea 1).
3. Este producto está certificado para controlar 6 A por circuito. Los circuitos NO pueden ser conectados en paralelo para controlar cargas mayores que 6 A.
4. CUIDADO: Riesgo de descarga eléctrica. Podría ser necesario más de un interruptor de desconexión para desenergizar el equipo antes de reemplazar focos, instalar o recablear la unidad.
5. Cuando se aplica suministro eléctrico, el sensor con interruptor de doble circuito puede ser activado o desactivado manualmente luego de los primeros 60 segundos y controlará automáticamente la carga luego de 2 minutos.
6. El sensor con interruptor de doble circuito requiere una visión de la habitación y una línea de visión sin obstrucciones para detectar los movimientos.
7. Los objetos calientes o las corrientes de aire en movimiento pueden afectar al desempeño del sensor con interruptor de doble circuito y podrían hacer que el sensor se activara de manera inesperada o mantuviera su estado presente más tiempo del deseado.
8. CUIDADO: Para reducir el riesgo de sobrecalentamiento y posibles daños a otros equipos, NO lo utilice para controlar receptáculos.
9. Instálelo de acuerdo con todos los códigos eléctricos locales y nacionales.
10. Sólo para uso bajo techo. Opérelo entre 0 °C y 40 °C (32 °F y 104 °F).
11. NO exceda de 20 dispositivos a 120 V~ o 7 dispositivos a 277 V~ en un ramal de circuito individual.
12. Sólo limpie con un paño suave y húmedo. NO utilice ningún limpiador químico.
Garantía limitada (Válida sólo en E.U.A., Canadá, Puerto Rico y el Caribe). Lutron reparará o reemplazará, a su entera discreción, cualquier equipo que exhiba fallas de materiales o fabricación dentro de los cinco años a partir de la compra. Para obtener el servicio de garantía, retorne el equipo al lugar donde lo adquirió o envíelo por correo a Lutron, 7200 Suter Rd., Coopersburg, PA 18036-1299, con franqueo prepago. Esta garantía se otorga en lugar de cualquier otra garantía expresa, y la garantía implícita de comerciabilidad está limitada a CINCO años a partir de la compra. Esta garantía no cubre el costo de instalación, remoción o reinstalación, ni los daños resultantes del mal uso, abuso o los daños debidos a un cableado o instalación incorrectos. Esta garantía no cubre daños incidentales o consecuentes. La responsabilidad de Lutron ante una reclamación por
daños que surjan de la fabricación, venta, instalación, entrega o uso del equipo o en relación con los mismos no excederá nunca del precio de compra del equipo. Esta garantía le otorga derechos legales específicos, y
usted podría tener otros derechos que varían de estado en estado. Algunos estados no permiten la exclusión o limitación de los daños incidentales o consecuentes, ni la limitación sobre la duración de una garantía implícita, por lo que las limitaciones anteriores podrían no regir en su caso. Lutron y Maestro son marcas comerciales registradas de Lutron Electronics Co., Inc. © 2013 Lutron Electronics Co., Inc.
Cableado
DESCONECTE la alimentación eléctrica
1
¡ADVERTENCIA! Peligro de descarga eléctrica. Podría ocasionar lesiones graves o la muerte. Antes de instalar el equipo DESCONECTE el suministro eléctrico en el disyuntor.
A
.
O
O
O
Línea única
* El cableado debe satisfacer la norma NEC de cableado de circuitos con múltiples ramales: Cuando dos o más
ramales de circuito alimentan dispositivos o equipos ubicados en el mismo yugo, se deberá proporcionar en el punto en el que se originan los ramales de circuito una manera de desconectar simultáneamente los conductores no puestos a tierra que alimenten dichos dispositivos.
Conecte el sensor con interruptor de doble circuito
2
A
. Cableado de una sola línea
120-277 V~
Neutro
B
. Cableado de dos líneas
120-277 V~
120-277 V~
Línea 1
Línea 2
Neutro 2
Neutro 1
1
El dispositivo no funcionará si no están conectados los cables negros (Circuito 1/ Línea 1).
2
El dispositivo no funcionará si no está puesto a tierra.
NOTA: Si se desean ajustes personalizados deje la placa de pared desactivada. Consulte al dorso las instrucciones de configuración personalizada.
ENCIENDA el equipo
3
A
.
Espere 60 segundos antes de encender manualmente.
4
O
O
O
• El interruptor de detección no controlará la carga manualmente durante 60 segundos.
Espere otros 60 segundos para el encendido automático.
5
• Cuando se restablezca la energía, el sensor de detección no controlará automáticamente la carga durante los primeros dos minutos.
O
O
B
.
Dos líneas*
Negro
Negro-
Anaranjado
Negro
Negro-
Anaranjado
B
.
O
O
O
1
1
Pelado
O
O
O
VerdePelado
Tierra
Verde
Tierra
Negro
Negro-
Anaranjado
2
Negro
Negro-
Anaranjado
2
Carga 1
Carga 2
Carga 1
Carga 2
60 s
60 s
Loading...
+ 5 hidden pages