(incandescent, halogen, CFL, LED, ELV, MLV,
electronic fluorescent, magnetic fluorescent)
120-277 V~ 50 / 60 Hz 6 A
Fan
120 V~ 50 / 60 Hz 4.4 A 1/6 HP
Combined lighting and fan load
120 V~ 50 / 60 Hz 4.4 A
P/N 032444 Rev. A 11/2013
Major motion coverage:
30 ft × 30 ft (9 m × 9 m) [900 ft2 (81 m2)]
Minor motion coverage:
20 ft × 20 ft (6 m × 6 m) [400ft
Lutron Electronics Co., Inc.
7200 Suter Road
Coopersburg, PA 18036-1299 U.S.A.
www.lutron.com
MS-PPS6-DDV
Partial-ON only
English
®
Circuit1
Tap Button
Top
programming
button
Bottom
programming
button
Circuit2
Tap Button
2
(36m2)]
Important Notes
®
Please read before installing.
1. Device will not function if it is not
grounded. Both bare and green ground
wires are required to connect to ground.
If no ground is available, consult an
electrician.
2. Device will not function if Black wires
(Circuit 1/Line 1) are not wired.
3. This product is rated to control 6 A per
circuit. Circuits may NOT be wired in
parallel to control loads greater than 6 A.
4.CAUTION:Risk of Electric Shock —
More than one disconnect switch may be
required to de-energize the equipment
before installing the unit, rewiring, or
replacing bulbs.
5. When power is applied, the dualcircuit sensing switch can be manually
turned on or off after 60 seconds and
Wiring
Turn power OFF
1
WARNING! Shock Hazard. May result in serious injury or death. Turn power OFF at circuit
breaker(s) before installing the unit, rewiring, or replacing bulbs.
A
.
O
O
O
Single-Line
* Wiring must comply with NEC code for wiring Multiple Branch Circuits: Where two or more branch circuits
supply devices or equipment on the same yoke, a means to simultaneously disconnect the ungrounded
conductors supplying those devices shall be provided at the point at which the branch circuits originate.
Connect dual-circuit sensing switch
2
A
. Single-Line Wiring
120-277 V~
B
OR
Black-Orange
.
Two-Line*
Black
O
O
O
1
Black
Black-Orange
Load 1
Load 2
will automatically control the load after
2minutes.
6. The dual-circuit sensing switch requires
an unobstructed view of the room and
line-of-sight to detect motion.
7. Hot objects or moving air currents can
affect the performance of the dual-circuit
sensing switch and may cause the sensor
to turn on unexpectedly or maintain its
current state longer than desired.
8.CAUTION: To reduce the risk of
overheating and possible damage to
other equipment, DO NOT use to control
receptacles.
B
. Two-Line Wiring
120-277 V~
120-277 V~
Neutral
Line 1
Line 2
1
Black
Black-Orange
GreenBare
Ground
Black
Black-Orange
2
Load 1
Load 2
9. Install in accordance with all national and
local electrical codes.
10. For indoor use only. Operate between 32°F
and 104°F (0 °C and 40 °C).
Bare
Green
11.DO NOT exceed 20 devices at 120V~ or
7 devices at 277 V~ on a single branch
circuit.
12. Clean with a soft damp cloth only. DONOT
use any chemical cleaners.
Limited Warranty (Valid only in U.S.A., Canada, Puerto Rico, and
the Caribbean). Lutron will, at its option, repair or replace any unit
that is defective in materials or manufacture within five years after
purchase. For warranty service, return unit to place of purchase or
mail to Lutron at 7200 Suter Rd., Coopersburg, PA 18036-1299,
postage pre-paid. This warranty is in lieu of all other express
warranties, and the implied warranty of merchantability is limited
to FIVE years from purchase. This warranty does not cover the cost
of installation, removal or reinstallation, or damage resulting from
misuse, abuse, or damage from improper wiring or installation.
This warranty does not cover incidental or consequential damages.
Lutron’s liability on any claim for damages arising out of or in
connection with the manufacture, sale, installation, delivery,
or use of the unit shall never exceed the purchase price of the
unit. This warranty gives you specific legal rights, and you may
Device will not function if Black wires (Circuit 1/ Line 1) are not wired.
2
Device will not function if it is not grounded.
NOTE: Leave wallplate off if custom settings are desired. See Custom Settings instructions on reverse side.
Turn Power ON
3
A
.
Wait for 60 seconds before manual switching
4
O
O
O
OR
B
.
O
O
O
• The sensing switch will not manually control the load for 60 seconds.
Wait for an additional 60 seconds for automatic switching
5
• Once power has been restored, the sensing switch will not
automatically control the load for the first 2 minutes.
Ground
2
60s
60s
Adjustable Settings
®
Before proceeding, select your preferred settings from the table below; default settings are shown in bold.
Read all instructions before continuing.
Press and hold the
1
buttons indicated in
the pictures.
Timeout
Total
1 Test Mode
number
of
2 1 minute1 minute
flashes
3 5 minutes5 minutes
4 15 minutes15 minutes
5 30 minutes30 minutes
Sensor Mode
Total
number
Auto-ON/Auto-OFF
1
(Occupancy mode)
of
flashes
Manual-ON/Auto-OFF
2
(Vacancy mode)
Advanced Auto-On Modes
Total
1 Ambient Light Detect (ALD)
number
of
2 Off-While-Occupied Enabled
flashes
3 Off-While-Occupied Disabled
Sensitivity
Total
1 Low
number
of
2 High
flashes
3 Restore ALL settings to default
2
The lens will flash once at each setting (always starts at setting 1).
Example: To set the Timeout to 1 minute, press and hold the tap
button. Release the button after the lens flashes for the second time.
15-second) timeout
for testing sensor
coverage. Device
will exit test mode
automatically after
5minutes, or when
any button is pressed.
Default Sensor Mode
settings are locked in
the MS-PPS6-DDV
(Partial-ON model
only) to satisfy the
CEC 2013 Title24
definition for a
“Partial-ON” sensor.
These settings
apply to all circuits
set to “Auto-ON”
(Occupancy) mode.
Lights turn on only if
natural light in room is
low. If switch turns on
when there is enough
natural light, or if
switch does not turn
on when there is not
enough natural light,
press the appropriate
tap button within
5seconds of entering
the room. Over time,
the switch will learn
your preferred setting.
If ALD mode is
selected, fan loads
should be set to
Manual-ON/Auto-OFF.
After manual shutoff,
sensor will keep
lights off for as long
as space is occupied
and timeout has not
expired.
For more information
on Off-While-Occupied
and ALD, please visit
www.lutron.com/
DCSensorInstall
Questions?
For additional instructions, information, and product
application information, please review Application
Note #489 (P/N 048489) at
www.lutron.com/DCSensorInstall
Troubleshooting
SymptomSolution
Sensor modes
can’t be
changed.
Power can’t be
switched ON
or OFF with
newly installed
sensing
switch.
Lights turn
OFF while
space is
occupied.
Lights do
not turn ON
when space is
occupied.
Lights turn
back ON
after they
are manually
turned OFF.
Tap buttons
control the
wrong circuits.
Lights stay ON
after space is
vacated.
• User has the “Partial-ON” version
of this product. Sensor modes
are not adjustable in this model
number (MS-PPS6-DDV).
• Connect green and bare wires to
ground. Ground is required for
sensor to function.
• After power is restored to the
sensor, it will take 2 minutes
before the unit is fully functional.
• Sensor’s timeout is too short
for this application; increase the
timeout.
• Sensor doesn’t have full view of
the room; move objects blocking
its line of sight.
• Sensor’s sensitivity is set too low;
change it to high sensitivity.
• Sensor mode is set to Manual-ON
(Vacancy).
• Ambient Light Detection (ALD)
mode is enabled and the room is
too bright. Continue to turn lights
on within 5 seconds of entering
room to teach the unit your
preferred daylight threshold.
• Sensor does not have full view of
the room. Move objects blocking
sensor’s line of sight.
• Sensor is in Off-While-Occupied
mode and the timeout has not
expired.
• Off-While-Occupied is disabled:
sensor will turn lights back on
25seconds after being turned off;
Enable Off-While-Occupied.
• Switch wiring of product to match
desired zones.
• Find “zone mapping”
programming at
www.lutron.com/DCSensorInstall.
• Check room to ensure that no hot
or moving objects or air currents
are in the sensor’s line of sight.
These can cause false-tripping of
the sensor.
I
I
I
I
I
I
Sensor de ocupación con
I
I
I
I
I
I
interruptor de doble circuito
MS-OPS6-DDV
Ocupación
Sólo polo único
Dos circuitos, cada uno certificado a:
Iluminación
120-277 V~ 50 / 60 Hz 6 A
Ventilador
120 V~ 50 / 60 Hz 4,4 A 1/6 HP
Carga combinada de iluminación y ventilador
120 V~ 50 / 60 Hz 4,4 A
P/N 032444 Rev. A 11/2013
Cobertura mayor de movimiento:
9 m × 9 m (30 pi × 30 pi) [81 m2 (900 pi2)]
Cobertura menor de movimiento:
6 m × 6 m (20 pi × 20 pi) [36 m2 (400 pi2)]
Lutron Electronics Co., Inc.
7200 Suter Road
Coopersburg, PA 18036-1299 E.U.A.
www.lutron.com
MS-PPS6-DDV
Sólo ParcialACTIVADO
Español
Tecla de
circuito 1
Botón
superior de
programación
Botón
inferior de
programación
Tecla de
circuito 2
®
Notas importantes
®
Por favor lea antes de instalar.
1. El dispositivo no funcionará si no está puesto
a tierra. Para la conexión a tierra se requieren
tanto el cable de tierra verde como el pelado. Si
no hay una toma de tierra disponible, consulte
con un electricista.
2. El dispositivo no funcionará si no están
conectados los cables negros (Circuito 1/Línea 1).
3. Este producto está certificado para controlar
6 A por circuito. Los circuitos NO pueden ser
conectados en paralelo para controlar cargas
mayores que 6 A.
4.CUIDADO: Riesgo de descarga eléctrica.
Podría ser necesario más de un interruptor de
desconexión para desenergizar el equipo antes de
reemplazar focos, instalar o recablear la unidad.
5. Cuando se aplica suministro eléctrico, el sensor
con interruptor de doble circuito puede ser
activado o desactivado manualmente luego
de los primeros 60 segundos y controlará
automáticamente la carga luego de 2 minutos.
6. El sensor con interruptor de doble circuito
requiere una visión de la habitación y una línea
de visión sin obstrucciones para detectar los
movimientos.
7. Los objetos calientes o las corrientes de aire
en movimiento pueden afectar al desempeño
del sensor con interruptor de doble circuito
y podrían hacer que el sensor se activara de
manera inesperada o mantuviera su estado
presente más tiempo del deseado.
8.CUIDADO: Para reducir el riesgo de
sobrecalentamiento y posibles daños a
otros equipos, NO lo utilice para controlar
receptáculos.
9. Instálelo de acuerdo con todos los códigos
eléctricos locales y nacionales.
10. Sólo para uso bajo techo. Opérelo entre 0 °C y
40 °C (32 °F y 104 °F).
11.NO exceda de 20 dispositivos a 120 V~ o
7 dispositivos a 277 V~ en un ramal de circuito
individual.
12. Sólo limpie con un paño suave y húmedo. NO
utilice ningún limpiador químico.
Garantía limitada (Válida sólo en E.U.A., Canadá, Puerto Rico y el Caribe).
Lutron reparará o reemplazará, a su entera discreción, cualquier equipo
que exhiba fallas de materiales o fabricación dentro de los cinco años a
partir de la compra. Para obtener el servicio de garantía, retorne el equipo
al lugar donde lo adquirió o envíelo por correo a Lutron, 7200 Suter Rd.,
Coopersburg, PA 18036-1299, con franqueo prepago. Esta garantía se
otorga en lugar de cualquier otra garantía expresa, y la garantía implícita
de comerciabilidad está limitada a CINCO años a partir de la compra. Esta
garantía no cubre el costo de instalación, remoción o reinstalación, ni los
daños resultantes del mal uso, abuso o los daños debidos a un cableado
o instalación incorrectos. Esta garantía no cubre daños incidentales o
consecuentes. La responsabilidad de Lutron ante una reclamación por
daños que surjan de la fabricación, venta, instalación, entrega o uso del
equipo o en relación con los mismos no excederá nunca del precio de
compra del equipo. Esta garantía le otorga derechos legales específicos, y
¡ADVERTENCIA! Peligro de descarga eléctrica. Podría ocasionar lesiones graves o la
muerte. Antes de instalar el equipo DESCONECTE el suministro eléctrico en el disyuntor.
A
.
O
O
O
Línea única
* El cableado debe satisfacer la norma NEC de cableado de circuitos con múltiples ramales: Cuando dos o más
ramales de circuito alimentan dispositivos o equipos ubicados en el mismo yugo, se deberá proporcionar en el
punto en el que se originan los ramales de circuito una manera de desconectar simultáneamente los conductores
no puestos a tierra que alimenten dichos dispositivos.
Conecte el sensor con interruptor de doble circuito
2
A
. Cableado de una sola línea
120-277 V~
Neutro
B
. Cableado de dos líneas
120-277 V~
120-277 V~
Línea 1
Línea 2
Neutro 2
Neutro 1
1
El dispositivo no funcionará si no están conectados los cables negros (Circuito 1/ Línea 1).
2
El dispositivo no funcionará si no está puesto a tierra.
NOTA: Si se desean ajustes personalizados deje la placa de pared desactivada. Consulte al dorso las instrucciones de configuración personalizada.
ENCIENDA el equipo
3
A
.
Espere 60 segundos antes de encender manualmente.
4
O
O
O
• El interruptor de detección no controlará la carga manualmente
durante 60 segundos.
Espere otros 60 segundos para el encendido automático.
5
• Cuando se restablezca la energía, el sensor de detección no controlará
automáticamente la carga durante los primeros dos minutos.
O
O
B
.
Dos líneas*
Negro
Negro-
Anaranjado
Negro
Negro-
Anaranjado
B
.
O
O
O
1
1
Pelado
O
O
O
VerdePelado
Tierra
Verde
Tierra
Negro
Negro-
Anaranjado
2
Negro
Negro-
Anaranjado
2
Carga 1
Carga 2
Carga 1
Carga 2
60 s
60 s
Loading...
+ 5 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.