Lutron Electronics GRAFIK Eye QSG-3PCE, GRAFIK Eye QSG-4PCE, GRAFIK Eye QSG-6PCE Installation And Operation Manual

LUTRON
System
Installation and
Operation Guide
R
Chinese
Please Read
Installation
Features and Functions of the GRAFIK Eye QS System . 2
Wiring the GRAFIK Eye QS System . . . . . . . . . . . . . . . . . 3
Wiring the GRAFIK Eye QS System
Class 2 / PELV Cable . . . . . . . . . . . . . . . . . . . . . . . . . 4
QS System Low-Voltage Control Wiring . . . . . . . . . . . . . .5
QS System Low-Voltage Terminal Connections . . . . . . . 6
Installing the GRAFIK Eye QS System . . . . . . . . . . . . . . . 7
Zone Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Operation
Preprogrammed Button Functionality . . . . . . . . . . . . . . 10
General Functionality . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
General Functionality: Programming Mode . . . . . . . . . .12
Zone Button Operation . . . . . . . . . . . . . . . . . . . . . . . . . .13
Quick Scene Programming . . . . . . . . . . . . . . . . . . . . . . 15
Scene Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
LED Displays for Lighting Levels . . . . . . . . . . . . . . . . . . 18
Adjusting Window Treatment Settings . . . . . . . . . . . . . .19
Timeclock Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Set Save Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Set Up Occupant Sensor . . . . . . . . . . . . . . . . . . . . . . . .29
Activate System Accessories . . . . . . . . . . . . . . . . . . . . .30
Faceplate Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Menu Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Contact Information . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
The GRAFIK Eye QS System allows for control of both lights and shades or window treatments using a single control unit. Features include pushbutton scene recall, info screen that displays energy savings and status, IR receiver, astronomic timeclock, occupant sensor connection, and backlit buttons that are easy to find and operate.
Model Number Unit Capacity Zone Capacity
(watts) (watts) QSG - 3PCE 1 500 500 QSG - 4PCE 2 000 500 QSG - 6PCE 2 300 500 (see page 8 for additional ratings)
All units: 230 V 50/60 Hz
R
GRAFIK Eye® QS System Installation and Operation Guide 2
OK
1 2 3 4 5 6
Info screen
Displays status; programming functions
Lighting column
Scene buttons with integral scene indicator LEDs
Shade column
Preset and raise/lower
buttons with integral LEDs
(maximum of 3 columns)
Space for future shade columns
Zone numbers
Zone raise/lower buttons
Zone LEDs display current
lighting zone levels
Timeclock status button
Displays current
timeclock info
OK button
Used for programming
fade time
Infrared receiver
For handheld remote use
Master buttons
Temporarily raise and lower lighting levels on unit
USB type mini B input
{
Hinged faceplate
Hinged faceplate
Features and Functions of the GRAFIK Eye® QS System
R
GRAFIK Eye® QS System Installation and Operation Guide 3
Wiring the GRAFIK Eye® QS System
Important Wiring Information
• Use properly certified cable for all line voltage/mains cables.
• Proper short-circuit and overload protection must be provided at the distribution panel.
• Install in accordance with all local and national electrical codes.
• Class 2 / PELV terminals may be unplugged for ease of IR, occupant sensor, and control wiring.
Caution! Before connecting the loads to the control unit, test the loads for short-circuits.
1.Turn power OFF at the circuit breaker or fuse box.
2.Connect a standard light switch between the live lead and load wire to test the circuit.
3.Turn power ON and check for short or open circuits. If load does not operate, the circuit is open. If the breaker/MCB trips (fuse blows or opens), a load short may exist. Correct short or open circuits and test again.
Caution! Do not connect line voltage/mains cable to Class 2 / PELV terminals.
• Earth/ground terminal connection must be made as shown in wiring diagrams.
• Do not mix different load types on the same zone.
• Follow all local and national electrical codes when installing Class 2 / PELV wiring with line voltage/mains wiring.
• Test for short-circuits on loads before wiring QS control unit.
To connect the line voltage/mains cables to the control unit:
1.Strip 8 mm (5/16 in.) of insulation off the line voltage/mains cables in the wallbox.
2.Connect the line voltage/mains, ground, and load wires to the appropriate terminals on the back of the control unit.
The recommended installation torque is 0,6 N•m (5,0 in.-lbs.) for line voltage/mains connections and 0,6 N•m (5,0 in.-lbs.) for the earth/ground connection.
3/8 in. (10 mm)
8 mm
(5/16 in.)
Danger! GRAFIK Eye QS control units must be installed by a qualified electrician in accordance with all applicable regulations and building codes. Improper wiring can result in personal injury or damage to control units or other equipment. Always turn off circuit breaker or remove main fuse from power line before doing any work. To avoid overheating and possible damage to equipment, do not install dimming devices to dim receptacles, motor-operated appliances, or fluorescent lighting not equipped with Lutron Hi-lume®, Eco-10TM, or Tu-Wire® electronic dimming ballasts, or devices approved for your location. In dimmed magnetic low-voltage circuits, you can prevent transformer overheating and failure by avoiding excessively high current flow: Do not operate control units with any lamps removed or burned out; replace any burned out lamps immediately; use only transformers that incorporate thermal protection or fused primary windings. Control units are designed for residential and commercial use, for indoor use only.
Neutral
Hot/Live
Switch
Load
Occupant Sensor Wiring
R
GRAFIK Eye® QS System Installation and Operation Guide 4
1234
1: COM 2: 24 V 3: MUX 4: MUX
12
ABC
Note: Use appropriate wire connecting devices as specified by local codes.
Occupant sensor
123456LN
Distribution Panel
LN
To Load 1
To Load 2
To Load 3
To Load 4
To Load 5
To Load 6
Control Wiring
Wiring the GRAFIK Eye® QS System Class 2 / PELV USA Cable
IR Wiring
From external IR connection (by others)
Common and power (terminals 1 and 2):
Two 1,0 mm
2
(#18 AWG) each terminal
1,0 mm
2
(#18 AWG)
each terminal
2,5 mm
2
(#12 AWG)
each terminal
1234
12
ABC
123456LN
1,0 mm2(#18 AWG) each terminal
230 V
1: IR DATA 2: IR COM
A: OCC SIG B: 24 V C: OCC COM
To control stations, window treatments, or other GRAFIK Eye QS control units
Line Voltage/Mains Cables and Load Wiring
Data (terminals 3 and 4):
Twisted, shielded pair 1,0 mm2(#22 AWG) each terminal
R
GRAFIK Eye® QS System Installation and Operation Guide 5
• System communication uses Class 2 / PELV low-voltage wiring.
• Follow all local and national electrical codes when installing Class 2 / PELV wiring with line voltage/mains wiring.
• Each terminal accepts up to two 1,0 mm
2
(#18 AWG) wires.
• Total length of control link must not exceed 610 m (2 000 ft.).
• Make all connections in the control unit’s wallbox.
• A QS system can have up to 100 zones and 100 devices (see table below).
• Wiring can be T-tapped or daisy-chained.
• Wire sizes:
- Two 1,0 mm2(#18 AWG) conductors for
control power.
- One twisted, shielded pair of 1,0 mm
2
(#22 AWG) for data link.
- Cable is available from Lutron:
GRX-CBL-S-500 (non-plenum) GRX-CBLP-S-500 (plenum rated). Check compatibility in your area.
LUTRON
LUTRON
LUTRON
LUTRONLUTRON
LUTRON
LUTRON
GRAFIK Eye QS
Sivoia QS
seeTouch QS
LUTRON
LUTRON
LUTRON
LUTRON LUTRON LUTRON
LUTRON
Daisy-Chain Wiring Example
T-Tap Wiring Example
GRAFIK Eye QS
Sivoia QS
QS smart
power
supply panel
QS smart power supply panel
seeTouch QS
QS System Low-Voltage Control Wiring
System Limits
QS Device Zone Count Device Count
3-zone QS 3 1
4-zone QS 4 1
6-zone QS 6 1
seeTouch
QS 0 1
Sivoia
QS 1 1
QS smart power supply panel 0 1
LUTRON
LUTRON
LUTRON
LUTRON
QS System Low-Voltage Terminal Connections
R
GRAFIK Eye® QS System Installation and Operation Guide 6
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
1234
12
ABC
123456HN
1234
12
ABC
123456HN
1234
12
ABC
123456HN
1234
12
ABC
123456HN
A1
2
3
4
1
A2
A3
A1 powers wallstation 1 only; terminal 2 terminates at wallstation 1
A2 and A3 have their own power supply; no terminal 2 connection
A3 powers wallstations 2, 3, and 4
A4
P1
S1
A4 powers wallstations 5, 6, and 7
P1 powers shade S1 only
Sivoia QS
shade
QS smart
power supply
panel
Control units shown in rear view
5
6
7
• Connect the terminal 1, 3, and 4 connections to all control units, wallstations, and control interfaces.
• Each control unit has its own power supply. Terminate the terminal 2 connection (24 V power) so that each control unit supplies power to a maximum of three wallstations. Each wallstation should receive power from only one control unit.
No terminal 2 connection between wallstations 4 and 5; they are powered by different control units
R
GRAFIK Eye® QS System Installation and Operation Guide 7
Installing the GRAFIK Eye® QS System
1.Mount a 89 mm (3 1/2-in.) deep 4-gang wallbox on a dry, flat indoor surface that is accessible and allows for system programming and operation. Allow at least 110 mm (4 1/2 in.) clearance above and below the faceplate to ensure proper heat dissipation. Allow 25 mm (1 in.) for faceplate overhang on all sides.
Note: 4-gang wallbox available from Lutron; P/N 241400.
2.Mount the control unit in the wallbox as shown using the four screws provided.
Note: Follow all local and national electrical codes when installing Class 2 PELV wiring with line voltage/mains wiring.
3.Apply the protective overlay to the control unit. See page 14 for instructions for naming zones.
Test the Wiring
1.Restore power.
2.Press the top button on the lighting keypad. The LED will light.
3.Press the zone raise or lower button. Make sure the control unit is dimming all connected loads.
Protective overlay (apply after installation)
Note: When tightening mounting screws, make sure that the hinged cover and faceplate will open fully, as shown.
Wall
200 mm
(7.9 in.)
87 mm (3.5 in.)
95 mm
(3.75 in.)
LUTRON
LUTRON
Faceplate overhangs wallbox on all sides; allow 25 mm (1 in.)
110 mm (4.5 in.)
Zone Setup
Assign Load Type
1. Enter programming mode (see page 12).
2. Use the master buttons to highlight “Zone setup” and press the OK button to accept.
3. Use the master buttons to highlight “Load type”. Press the OK button to accept.
4. Use the zone raise/lower buttons to
choose the load type for that zone. See the list below for supported load types. Press the OK button to accept.
5. The info screen will display a
confirmation screen that your load type has been saved.
6. Exit programming mode (see page 12).
R
GRAFIK Eye® QS System Installation and Operation Guide 8
Main menu
Occ sensor
Zone setup
Zone setup
High end
Load type
Set type using zone controls
Load type
OK
1 2 3 4 5 6
Use the zone raise/lower buttons to choose the load type for that zone.
Master buttons
OK button
Load Type Notes
• All electronic low-voltage (ELV) lighting used with an interface must be rated for reverse phase control dimming. Before installing an ELV light source, verify with the manufacturer that their transformer can be dimmed. When dimming, an ELV interface must be used with the control unit.
• Not all zones must be connected; however, connected zones must have a minimum load of 40 W.
• No zone may be loaded with more than 500 W.
• Maximum total lighting load per unit is 10 A.
• Maximum total lighting load for a magnetic low-voltage (MLV) load is 2 300 VA or 1 800 W after transformer. Maximum load per MLV zone is 500 VA or 400 W.
Setting Load Types
Fixture load type
Incandescent MLV (magnetic low-voltage) ELV (electronic low-voltage)
Hi-Lume/Eco-10
Non-dim Neon/Cold cathode
Tu-Wire
Direct control via GRAFIK Eye QS
Incandescent MLV
--
-­Non-dim LOFO or Non-dim FOFO Neon, CC
Tu-Wire
Control via power module
Power module Power module Power module Fluorescent module Non-dim LOFO or Non-dim FOFO Neon, CC
Tu-Wire
LUTRON
LUTRON
Choose this load type from the menu
on the GRAFIK Eye® QS:
Saved
Saved
Set Minimum Level (optional)
Some local regulations specify a minimum lighting level for dimming zones in occupied buildings. If this pertains to you, follow these steps to set up your minimum lighting level.
1. Enter programming mode (see page 12) and select “Zone setup,” then “Min level”. Press the OK button to accept.
2. Use the master buttons to highlight “OFF” if you want your lights to go all the way off at their minimum light level, or “10%” if you want that to be the minimum light level. Press the OK button to accept. Note: Non-dim loads will turn off regardless of the minimum level setting.
3. The info screen will display a confirmation screen that your minimum level has been saved.
4. Exit programming mode (see page 12).
R
GRAFIK Eye® QS System Installation and Operation Guide 9
Zone Setup
Set High End or Low End
High and low end trim settings limit the maximum and minimum output of a dimming zone. Trim levels are set automatically when the load type is programmed. Change the high or low end trim for a zone only if the default setting needs to be adjusted.
1. Enter programming mode (see page 12).
2. Use the master buttons to highlight “Zone setup” and press the OK button to accept.
3. Use the master buttons to highlight “High end” or “Low end” (this example shows low end). Press the OK button to accept.
4. Use the zone raise/lower buttons to set
the high end or low end trim for that zone. The info screen will display each zone number and percentage as you adjust it. Press the OK button to accept.
5. The info screen will display a
confirmation screen that your setting has been saved.
6. Exit programming mode (see page 12).
Main menu
Occ sensor
Zone setup
Zone setup
High end
Low end
Set trim using zone controls
Zone 2
Low end
OK
1 2 3 4 5 6
Use the zone raise/lower buttons to set the high end or low end trim for that zone.
Master buttons
OK button
10%
Min level
OFF
Zone setup
Low end
Min level
Saved
Saved
Saved
Saved
Preprogrammed Button Functionality
R
GRAFIK Eye® QS System Installation and Operation Guide 10
Lighting Column Button Preprogramming (Factory Default: Dimmable Loads)
Scene 1: All lights to 100% Scene 2: All lights to 75% Scene 3: All lights to 50% Scene 4: All lights to 25% Scene OFF: All lights to 0%
Lighting Column Button Preprogramming (Factory Default: Non-Dim Loads)
Scene 1: All lights On Scene 2: All lights On Scene 3: All lights On Scene 4: All lights On Scene OFF: All lights Off
Shade Column Button Preprogramming (Factory Default: Sivoia® QS shades)
All shades fully open All shades to 50% All shades fully closed Lower/Raise all shades
The GRAFIK Eye® QS System controls lights without special programming. The factory defaults for the lighting column buttons are shown below for both dimmable and non­dim zones. See pages 15 through 17 for methods for changing scene settings.
The info screen goes blank after 20 seconds if there is no button press or fading.
The master buttons also activate the info screen. These buttons temporarily raise or lower all dimmable lights (except those programmed as unaffected in the current scene). Adjustments are temporary and do not affect scene programming.
The OK button activates the info screen, which then shows the current scene and its fade time.
The timeclock button activates the info screen and displays the current time, the next event scheduled to occur, and what that next event is. Pressing a second time displays the location and the sunrise/sunset times.
R
GRAFIK Eye® QS System Installation and Operation Guide 11
OK
Info screen: see example screens below
Timeclock button displays the current time and the next scheduled event. Pressing when in Program mode functions as a “back” button.
OK button activates the info screen, which shows the current scene’s fade time. In Save Always mode, allows fade time adjustment. In Save by OK mode, pressing a second time allows zone adjustment; pressing a third time allows fade adjustment.
Master buttons temporarily raise or lower all lights (except unaffected, shades, and non-dim zones) on this GRAFIK Eye QS unit
Scene 1
Master raise Master lower
General Functionality
OK
Scene: 1
Adjust fade
03 seconds
11:23 AM Fri
Next: 5:00 PM
Scene 1
Loading...