Caution - Wire in a daisy-chain
arrangement as shown - no variations.
Do not substitute cables!
Notes:
• All control wiring is Class 2 (Extra Low Voltage).
Do not place any of these wires in with line voltage
(mains voltage) wiring.
• Panel may be placed in the middle of the wiring as
opposed to on the end as shown, but panel to
panel wiring may be more difficult.
• 2 #12 AWG (2.5mm2) wires will not fit in the
Accessory Control terminal blocks. Use the
diagram shown at right to make the connections
in the wallbox. #12 AWG (2.5mm2) is necessary
due to voltage drop on the wire.
• Shielding must be connected as shown, but do not
connect to Ground (Earth) or Accessory Control. It
is easiest to connect the bare drain wires and cut
off the outside shield.
• Make wire connections inside the wallbox, GP and
XP panel or in a junction box (provided by others)
within 8ft. (2.4m) from the terminals.
LUTRON
LUTRON
CLASS 2 WIRING
SSA CONTROLS
(10 MAX.)
NTGRX-1S
GRAFIK Eye GP, LP, or XP SERIES LIGHTING CONTROL PANELS
(Number of panels max = 33 - Number of Control Units -
4
3
2
1
Number of Accessory Controls)
-SHIELD/DRAIN
2 #12 AWG (2.5mm2)
1 #18 AWG
(1mm2)
2 #12 AWG (2.5mm
2
)
• Maximum number of lighting control panels may
be increased using a repeater—contact Lutron.
• The following cables: Liberty #LUCOM-12/22-RBL,
Belden #9461, and Alpha #2211 are made with #22
AWG wire, and have been tested and approved.
Not all #22 AWG cable will work. Any #18 AWG
twisted, shielded pair will work.
For More Information...
?
Accessory Control to Control UnitPanel to Panel Wiring.................................22
to Panel Wiring.................................21
4
Step by Step instructions for GRAFIK Eye Switching Panel
Wire System
STEP 3: Wire System (cont.)
Suggested wiring when panels are close together
Suggested wiring when panels are far apart
Neutral Wire (N)
Hot/Live
Wire (H)
Distribution Panel
Module wiring
Hot/Live In
Switched Hot
Load 16 A max
Neutral
Large
Distance
H
SH
H
SH
H
SH
H
SH
H
SH
H
SH
H
SH
H
SH
SH
Small
Load 16A Max.
SH
H
Splice Neutrals
in Trough
SH
H
Switched Hot/Live
Wire (SH)
XP Panel
N
N
SH
XP Panel
Load 16A Max.
H
Switched Hot/Live
Wire (SH)
Neutral
Wire (N)
Hot/Live
Wire (H)
Distribution Panel
N
N
H
H
Distance
Notes:
• Terminal blocks accept one #14 AWG (2.5mm2)
through #10 AWG (4.0mm2) or two AWG #18 AWG
through #16 AWG wire.
• Two modules and the control feed are shown to the
left. The module terminal blocks are typical of the
rest of the possible 12 modules
• Lutron recommends that the Control Feed be a
dedicated circuit even though the control wiring
will draw 0.5 Amps max.
Danger - An XP Series panel is fed by
multiple circuits. Locate and lock each
feed in the OFF position.
Caution - XP Series panels require entry
of wires as specified. Improper entry will
block serviceable parts or violate NEC codes.
Warning - Do not remove bypass jumpers
at this step.
Neutral
Ground
Dedicated Hot/Live
N
N
H
H
Reference Sheets for GRAFIK Eye Switching Panel
Caution - Lutron recommends the use of
a trough for ease of wiring (where space
permits).
Caution - Follow all local wiring codes.
5
Set Address Switches
STEP 4: Set Address Switches
Control
LUTRON
LUTRON
NTGRX-1S GRX-4000 Series
No switches for addressing.
Go to Step 6 if no other types of
Accessory Controls.
Action
Address
Control 1
N/A
1 2 3 4 5 6
Function
Factory Set
N/A
1 2 3 4
1
2
3
4
LUTRON
PARTITION STATUS
OPEN
CLOSED
NTGRX-RL NTGRX-4PS
SEQUENCE
ZONE LOCK
SCENE LOCK
FADE OVERRIDE
LUTRON
LUTRON
LUTRON
1 2 3 4 5 6
LUTRON
1 2 3 4 5 6
LUTRON
GRX-AV
Must set switches BEFORE
installing these controls.
Set Switches 1-4 on each
Accessory Control to a unique
address.
Must set switches BEFORE
installing these controls.
Set Switches 1-4 on each
Accessory Control to a unique
address.
Set Switches 5-6 to define the
function of control.
Control 2
Control 3
Control 4
Control 5
Control 6
Control 7
Control 8
Control 9
Control 10
Control 11
Control 12
Control 13
Control 14
5 6
Leave switches as factory
set.
Go to Step 6 if no other
types of Accessory controls.
Setting Switches 5 and 6
requires system knowledge.
See Step 5 for function
options.
ALL OTHERS
Notes:
• GRX-AV has 8 switch positions. Positions 7 and 8
also set the function.
• GRX-AV-RS232’s do not have an address—
follow instructions packaged with each control
and skip to step 6.
For More Information...
?
6
Step by Step instructions for GRAFIK Eye Switching Panel
See also One-Line Diagram from submittals.
Control 15
Control 16
Back of Accessory Control
Switch
location
4
3
2
1
Caution - Do not install controls in
wallbox without setting the Address and
Function Switches.
LUTRON
R
LUTRON
R
Set Function Switches
STEP 5: Set Function Switches
Accessory Control
NTGRX-4S,
GRX-4S-DW
NTGRX-4S-IR
w/GRX-IT,
GRX-CIR
w/GRX-IT
NTGRX-RL
NTGRX-4Q
LUTRON
LUTRON
1 2 3 4 5 6
LUTRON
SEQUENCE
ZONE LOCK
SCENE LOCK
FADE OVERRIDE
1 2 3 4 5 6
Function Set by Switches
on Back of Control
Factory Set
5 6 5 6 5 6 5 6
Factory Set
Activate Scenes 1-4
Not Applicable
Sequence Scenes 1-4
Activate Scenes 5-8
Not Applicable
Not Applicable
Activate Scenes 9-12
Not Applicable
Not Applicable
Activate Scenes 13-16
Not Applicable
Sequence Scenes 5-16
Function Set
with Front
Buttons
(See Step 17)
Activate Scenes on
specified GRX-4000
Series Control Units
Raise/Lower specified
Zones on specified
GRX-4000 Series
Control Units
Affect specified GRX4000 Series Control
Units
NTGRX-4PS
NTGRX-4M
GRX-AV
GRX-AV
7 8
Factory Settings
NTGRX-1S
GRX-IT
GRX-8IT
NTGRX-2B
1
2
3
4
PARTITION STATUS
OPEN
CLOSED
Not Applicable
Fifth button turns
LUTRON
Control Units On only.
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Fifth button turns
Control Units Off only.
Parallel specified GRX4000 Series Control
Units
Toggle 4 specified
groups of GRX-4000
Series Control Units On
and Off.