Lutron SCR-15-TQ, SCR-15-BI Installation Manual

Page 1
CAR-15-DFDU Rated at 125 V~ 60 Hz 15 A CAR-20-DFDU Rated at 125 V~ 60 Hz 20 A NTR-15-DFDU Rated at 125 V~ 60 Hz 15 A NTR-20-DFDU Rated at 125 V~ 60 Hz 20 A SCR-15-DFDU Rated at 125 V~ 60 Hz 15 A SCR-20-DFDU Rated at 125 V~ 60 Hz 20 A CAR-15-HFDU Rated at 125 V~ 60 Hz 15 A CAR-20-HFDU Rated at 125 V~ 60 Hz 20 A NTR-15-HFDU Rated at 125 V~ 60 Hz 15 A NTR-20-HFDU Rated at 125 V~ 60 Hz 20 A SCR-15-HFDU Rated at 125 V~ 60 Hz 15 A SCR-20-HFDU Rated at 125 V~ 60 Hz 20 A RP-FDU-10 Rated at 125 V~ 60 Hz 10 A
Installation Instructions
Please Leave for Occupant
Installation
Note: For installations involving more than one device in a wallbox, refer to Multigang Installation (page 3) before beginning.
2. Refer to Wiring Diagrams (page 2).
3. Connect live (usually black wires) to brass screw terminal(s),
and tighten securely.
Note: The HFDU has no connecting link between brass screw terminals. Therefore, two separate live connections are required.
4. Connect neutral (usually white wires) to silver screw
terminal(s), and tighten securely.
5. Connect ground (green or bare copper wire) to green grounding
screw terminal, and tighten securely.
6. Mount receptacle to wallbox. (See next page.)
Caution: Mounting means not grounded. Receptacle does
not self ground when mounting it to a wallbox. A ground wire connection is required for receptacle grounding. Failure to connect a ground wire to the green grounding screw terminal will result in an ungrounded receptacle.
7. Turn power ON.
Receptacles For Dimming Use
Important Notes
1.
Install in accordance with all national and local electrical codes.
2. Receptacles for dimming use are designed for use in dimming
applications as listed above. DO NOT dim any receptacle not specifically designed for dimming use.
3. Receptacle for dimming use will only accept a special replace-
ment plug for dimming use. DO NOT attempt to insert a stan­dard plug into the receptacle for dimming use.
4. The half for dimming use (HFDU) has an outlet for dimming use on
the top and a standard outlet on the bottom. Both will accept the replacement plug for dimming use. A standard plug can only be
used with the bottom outlet of the half for dimming use (HFDU).
Receptacles for dimming use and replace­ment plugs are UL
® Listed Special Use
Connectors suitable for use with the fol­lowing Lutron products:
GRAFIKTM Lighting Control Systems GRAFIK Eye® Lighting Control Systems Hi-PowerTM 2•4•6 Dimming Modules HomeWorks
® Lighting Control Systems
HomeWorks
® Maestro® Dimmers
HomeWorks® Vareo® Dimmers Nova
® Dimmers
Nova T
® Dimmers
Ariadni® Dimmers Diva
® Dimmers
Faedra
® Dimmers
LyneoTM LX Dimmers Maestro
® Dimmers
Qoto
® Dimmers
RadioRA® Dimmers Skylark
® Dimmers
Spacer System
® Dimmers
Vareo® Dimmers
Please read all instructions completely before installation.
5.
The HFDU requires two separate live feeds. If the live and dimmed live feeds to the HFDU are supplied from different cir­cuits or split-wired, a means to simultaneously disconnect these circuits must be provided at the panelboard where they originate (NEC® 2005, Article 210.7(B)). A 2-pole circuit breaker or two sin­gle-pole circuit breakers with an approved handle tie can be used to accomplish this simultaneous disconnect. When using the HFDU with dimming panels, feed-through panels, which are those without circuit breakers, are recommended.
6. Connect only #10 AWG, #12 AWG or #14 AWG copper or copper-
clad wire to this device. Do not connect aluminum wire to this device. See device for strip length.
7. Multiphase applications: Use a separate neutral for each phase
containing a control circuit. For dimmers requiring a neutral con­nection, the dimmers’ neutral wire should be connected to the neutral connection of its respective load. DO NOT connect dim­mers’ neutral to any other controlled (dimmed or switched) cir­cuit. For more information call the
Lutron Technical Support
Center
and ask for Application Note 17, “Common Neutral
Interaction.”
Page 2
Half For Dimming Use (HFDU)
Mounting
1.
Push wires into wallbox, allowing room for receptacle to be inserted. Do not pinch wires between wallbox and receptacle.
2. Mount receptacle to wallbox using screws provided.
3. Replace wallplate adapter (if removed) and snap on wallplate.
Receptacle for Dimming Use (NTR-15-DFDU shown)
Wallplate Adapter
Wallplate
Wallplate Adapter Mounting Screws
Receptacle Mounting Screws
Cleaning Instructions
Clean receptacles with a
soft damp cloth only
. Do not use any
chemical cleaners.
** NOTE: To control each outlet of the receptacle independently, cut off the con-
necting link between the brass screws with a wire cutter.
Ground (Green or Bare)
Live (Black)
Neutral (White)
125 V~ 60 Hz
Dims lower outlet
** See Note Below
(NTR-15-DFDU shown)
Before
After
Dimmed Live
Dimmed Live
Dims upper outlet
Each outlet will dim independently.
Wiring Diagrams
Wiring Notes:
1. Wire terminals accept #10 AWG, #12 AWG or #14 AWG wire. Solid copper or copper clad wire only.
2. See device for proper strip length of wires.
Ground (Green or Bare)
Live (Black)
Neutral (White)
Lutron
Dimming
Product
Dimmed Live
(NTR-15-DFDU shown)
Loads plugged into these outlets will dim together.
125 V~ 60 Hz
Duplex For Dimming Use (DFDU)
Ground (Green or Bare)
Live (Black)
Neutral (White)
Lutron
Dimming
Product
Dimmed Live
Live
(NTR-15-HFDU shown)
Top outlet will dim and bottom outlet will remain live.
125 V~ 60 Hz
Ground (Green or Bare)
Live (Black)
Neutral (White)
Lutron
Dimming
Product
Switch
Dimmed Live
Switched Live
(NTR-15-HFDU shown)
Top outlet will dim and bottom outlet is controlled by a switch.
125 V~ 60 Hz
Page 3
Wallbox Requirement Chart
Number of Small Controls
01234
0 0 1 1+1 4 4+1 Number 113568 of Large2467810 Controls 3 6 8 10 11 13
4 9 11 12 14 15
Wallbox Requirement Chart
Number of Small Controls
0123456
00123456 Number 11345678 of Large 235678910 Controls 35789101112
4 7 9 10 11 12 13 14
Remove inner side sections (shaded) only.
Do not remove outer side sections.
Single-gang gangable wallbox
3/4 in. space (use chase nipple or Lutron P/N PLUS-ADPTR-3.5)
Four-gang gangable wallbox
Side Sections Removed
Note: When ganging an even number of small controls with side sec­tions intact, use gangable 3 in. x 2 in. wallboxes. Space an additional wallbox 3/4 in. apart from the other wallboxes. A 3/4 in. chase nipple is recommended as a spacer between wallboxes.
Example: Wallbox arrangement required for ganging 4 small controls with no side sections removed:
No Side Sections Removed
Remove inner side sections from controls or receptacles. Using pliers, bend side sections up and down until they break off.
Multigang Installation
Multiple controls and receptacles can be installed in a common gangable wallbox or a series of interconnected wallboxes for a clean, consolidated appearance. Lutron multigang wallplates are available to complete the installation. Refer to instruction sheet supplied with multigang wallplates for installation.
For new installations, controls and receptacles can be ganged without removing side sections, but, to reduce the size of the multigang instal­lation or to fit existing wallboxes, inner side sections must be removed.
Note: When ganging any combination of small and large controls, place all small controls on one end of the gang and all large controls on the other. All receptacles with or without side sections removed are considered small. Use the chart below to determine the number of required gangable wallboxes.
Replacement Plug For Dimming Use
Important Notes
1.
Caution: Plug for lamp loads only. Check that the dimmer load
type matches the load type of the lamp being used (i.e., incan­descent, magnetic low-voltage, electronic low-voltage, fluores­cent, etc.).
2. Check that the load rating does not exceed the rating of the lamp
cord.
3. This plug is intended for use with Lutron receptacles for dimming
use. It can also be used with standard receptacles.
4. Installation of this plug on a lamp cord will permanently change
the lamp cord.
5. Not for use with lamp cords requiring a ground wire connec-
tion.
6. Plug intended for use with SPT-2 18/2 (0.250 in.—0.270 in.
major diameter) wires (6.35 mm—6.86 mm).
7. DO NOT install on extension cords.
8. Plug rated for 125 V~ 60 Hz 10 A.
Installation
1.
Unplug lamp cord.
2. Cut old plug off unplugged lamp cord using a pair of wire cutters.
3. Strip the insulation on the lamp cord as shown below. Do not tin
wires.
4. Wires will be secured between the blade surface and the square
wire clamp. See Plug Wiring Diagram. Using a screwdriver:
•Connect the neutral wire (always the wire with the grooved insulation or a stripe) to the polarized (larger) blade. Tighten screw with a torque of 12 in.-lbs (1.4 N•m).
•Connect the live wire to the non-polarized (smaller) blade. Tighten screw with a torque of 12 in.-lbs (1.4 N•m).
5. Insert the base of the plug into the support side (the part without
the screw assembled in it). The final cord exit direction can be determined by the orientation of the support side with respect to the base (see Plug Assembly Diagram 1 for details).
6. Secure the lamp cord inside the plug by feeding the cord around
the series of walls found on the support side, starting near the screw terminals and working towards the cord opening.
7.
Gently
pull the excess cord through the cord opening once it has
been secured in place.
8. Slide the cover side (the part with the screw assembled in it) of
the plug in place and secure it by tightening the screw until snug.
9. Plug the lamp into the Lutron receptacle for dimming use and
test functionality.
3/8 in. (10 mm)
Page 4
Lutron Electronics Co., Inc. 7200 Suter Road Coopersburg, PA 18036-1299 Made and printed in the U.S.A. 9/07 P/N 030-825 Rev. E
Worldwide Technical and Sales Assistance
If you have questions concerning the installation or operation of these products, call the
Lutron Technical Support Center.
Please
provide exact model number when calling. +1-800-523-9466 (U.S.A., Canada, and the Caribbean)
Other Countries call +1-610-282-3800 Fax +1-610-282-3090 Visit our web site at www.lutron.com
Limited Warranty
(Valid only in U.S.A., Canada, Puerto Rico, and the Caribbean.)
Lutron will, at its option, repair or replace any unit that is defective in materials or manufacture within one year after purchase. For warranty service, return unit to place of purchase or mail to Lutron at 7200 Suter Rd., Coopersburg, PA 18036-1299, postage pre-paid.
THIS WARRANTY IS IN LIEU OF ALL OTHER EXPRESS WARRANTIES, AND THE IMPLIED WARRANTY OF MERCHANTABILITY IS LIMITED TO ONE YEAR FROM PURCHASE. THIS WARRANTY DOES NOT COVER THE COST OF INSTALLATION, REMOVAL OR REIN­STALLATION, OR DAMAGE RESULTING FROM MISUSE, ABUSE, OR DAMAGE FROM IMPROPER WIRING OR INSTALLATION. THIS WARRANTY DOES NOT COVER INCIDEN­TAL OR CONSEQUENTIAL DAMAGES. LUTRON’S LIABILITY ON ANY CLAIM FOR DAM­AGES ARISING OUT OF OR IN CONNECTION WITH THE MANUFACTURE, SALE, INSTAL­LATION, DELIVERY, OR USE OF THE UNIT SHALL NEVER EXCEED THE PURCHASE PRICE OF THE UNIT.
This warranty gives you specific legal rights, and you may have other rights which vary from state to state. Some states do not allow the exclusion or limitation of incidental or conse­quential damages, or limitation on how long an implied warranty may last, so the above limita­tions may not apply to you.
These products may be covered under one or more of the following U.S. patents: 5,180,886; D494,138; 7,198,523; D516,512; and corresponding foreign patents. U.S. patents pending. Lutron, Faedra, Qoto, Spacer System, Ariadni, Diva, GRAFIK Eye, HomeWorks, Maestro, Nova, Nova T , RadioRA, Skylark, and Vareo are registered trademarks and GRAFIK, Lyneo, and Hi-Power are trademarks of Lutron Electronics Co., Inc. NEC is a registered trademark of the National Fire Protection Association, Quincy, Massachusetts. © 2007 Lutron Electronics Co., Inc.
Plug Assembly Diagram 1
Assemble base to support side.
Cord should be carefully fed around these walls.
Wide Blade (Neutral)
Narrow Blade (Live)
Plug Wiring Diagram
Neutral Wire (ribbed or striped wire)
Tip: If you prefer to have the cord exit the plug from the other
direction, remove the base from the support side, flip the base 180° (so that the wide and narrow blades have changed places), and insert back into the support side. When plugged into the Lutron receptacle, the cord will now exit in the other direction.
Plug Assembly Diagram 2
Attach cover side.
Cover side
Secure cover with attached screw
Support Side
Base
Lamp cord (SPT-2 18/2 0.250 in.—0.270 in. major diameter wires) (6.35 mm—6.86 mm)
Live Wire
Base
Loading...