Lutron QSE-IO User Manual

QSE-IO Control Interface Programming Guide
Contents
Overview ........................................... 2
QSE-IO Operating Modes and DIP Switch Settings Overview . . . . 3
Equipment / Functionality Table ........................... 5
Scene Selection Operating Mode ......................... 6
Special Operating Mode: Sequencing...................... 7
Special Operating Mode: Zone Lockout .................... 8
Special Operating Mode: Scene Lockout ................... 9
Special Operating Mode: Panic...........................10
Special Operating Mode: Timeclock .......................11
Special Operating Mode: Afterhours .......................12
Shade Mode: Shade Input Raise, Lower, Stop ...............15
Shade Mode: Shade Input Dual Group .....................16
Shade Mode: Shade Input Dual Group Raise/Lower ...........17
Shade Mode: Shade Input Toggle.........................18
Shade Mode: AC Shade Output ..........................19
Partitioning Mode .....................................20
Occupancy Sensor Mode...............................21
Zone Toggle Mode ................................... 22
Zone Control Mode....................................23
Hotel Mode..........................................28
Integration Mode..................................... 30
page 1
integration conguration
shade stuffs
partitioning occ sensor
345678
345678
345678
Overview
QSE-IO Control Interface Programming Guide
These instructions detail the available functions and the accompanying necessary settings for programming a QSE-IO control interface in a Lutron system. For wiring, installation, system setup, additional operation instructions, and other non-programming information, please refer to the documentation that accompanied this and other devices in your system.
Programming Your System
The programming instructions in this guide are for standalone (GRAFIK Eye QS or QS link only) systems. For Energi Savr Node or Quantum systems, refer to the documentation that came with those products for programming instructions.
Switches and Connections
The DIP switches are numbered from 1 through 8. For operating mode configuration, only switches 3 through 8 are used (with certain noted exceptions; see the specific configuration instructions).
Unit Overview
QS Link
4 3 21
1234567
Contact Closure Outputs
CCO 1 NC
CCO 1 NO
1-2 COM
CCO 2 NC
CCO 2 NO
CCO 3 NC
CCO 3 NO
Program button
3-4 COM
CCO 4 NC
CCO 4 NO
CCO 5 NC
DIP switches
O
1 2 3 4 5 6 7 8
N
Legend:
Up/On
Down/Off
Closure Inputs
CCO 5 NO
5 COM
CCI 1
Contact
CCI 2
CCI 3
CCI 4
CCI 5
COM
The CCI and CCO wiring terminals each accept one 28 to 16 AWG (0.08 to 1.5 mm2) wire. Refer to the specific configuration instructions for details on wiring for your desired operating mode.
Operating Modes
Each QSE-IO can be assigned only one (1) operating mode from those detailed on the following pages. By choosing the correct input (CCI) terminal and accompanying DIP switch settings, you can select the specific action each operating mode will perform.
page 2
QSE-IO Control Interface Programming Guide
integration conguration
shade stuffs
partitioning occ sensor
345678
345678
345678
QSE-IO Operating Modes and DIP Switch Settings Overview
Mode Dip Switch Contact Closures Invoke:
Configuration 3 4 5 6 7 8 Input 1 Input 2 Input 3 Input 4 Input 5 Inputs Outputs
Scene 1 Scene 2 Scene 3 Scene 4 Scene Off
Scene 5 Scene 6 Scene 7 Scene 8 Scene Off
Scene 9 Scene 10 Scene 11 Scene 12 Scene Off
Scene 13 Scene 14 Scene 15 Scene 16 Scene Off
• For AC shades with only 2 inputs (open/close), set DIP switch 1 to the up/on position to enable the feature
• The QSE-IO provides no power, only a control signal, to AC shades. Refer to the instructions that came with your shades
Scene selection
Shade input preset
(“stop if moving”)
Shade input preset
(no “stop if moving”)
(raise, lower, stop)
Shade input dual group
(“stop if moving”)
Shade input dual group
(no “stop if moving”)
Shade input dual group
Shade input toggle
(“stop if moving”:
open/stop/close/stop)
Shade input toggle
(no “stop if moving”:
AC Shade output
(maintained outputs)
AC Shade output
(momentary stop)
AC Shade output
(momentary outputs)
Notes
that mimics “stop” (asserts both “open” and “close” CCOs together when a “stop” command is received).
for more information.
Special
(maintained)
Special
(momentary)
Special 2
(maintained)
Special 2
(momentary)
Shade input
(raise/lower)
open/close)
Scene 1 Scene 2 Scene 3 Scene 4 Scene Off
Scene 5 Scene 6 Scene 7 Scene 8 Scene Off
Scene 9 Scene 10 Scene 11 Scene 12 Scene Off
Scene 13 Scene 14 Scene 15 Scene 16 Scene Off
Sequence 5–16
Sequence 5–16
Sequence 1–4
Sequence 1–4
Shade open
Shade open
Open Group 1
Raise/Stop Group 1
Toggle Group 1
Toggle Group 1
Open Group 1
Open Group 1
Open Group 1
Zone lockout
Zone lockout
Zone lockout
Zone lockout
Shade preset 1
Shade raise
Close Group 1
Lower/Stop Group 1
Toggle Group 2
Toggle Group 2
Stop Group 1Close
Stop Group 1 if moving
Stop Group 1 if moving
Scene lockout
Scene lockout
Scene lockout
Scene lockout
Shade preset 2
Shade lower
Open Group 2
Raise/Stop Group 2
Toggle Group 3
Toggle Group 3
Group 1
Close Group 1
Close Group 1
Panic mode
Panic mode
Panic mode
Panic mode
Shade preset 3
Shade stop
Close Group 2
Lower/Stop Group 2
Toggle Group 4
Toggle Group 4
Open Group 2
Open Group 2
Open Group 2
Timeclock Maintained
Timeclock Momentary
Afterhours mode
Afterhours mode
Shade close
Shade close
Momentary Momentary
Toggle Group 5
Toggle Group 5
Close Group 2
Close Group 2
Close Group 2
Maintained or Momentary
Maintained or Momentary
Maintained
Momentary
Maintained or Momentary
Momentary or Maintained
Maintained or Momentary
Momentary Momentary
Maintained Momentary
Maintained or Momentary
Maintained or Momentary
Maintained or Momentary
Maintained
Momentary
Maintained
Maintained
Maintained
Maintained
Maintained
Maintained
Maintained (except 2, which is Momentary)
Momentary
Legend:
Up/On
Down/Off
page 3
integration conguration
shade stuffs
partitioning occ sensor
345678
345678
345678
QSE-IO Control Interface Programming Guide
QSE-IO Operating Modes and DIP Switch Settings Overview (continued)
Mode Dip Switch Contact Closures Invoke:
Configuration 3 4 5 6 7 8 Input 1 Input 2 Input 3 Input 4 Input 5 Inputs Outputs
Partitioning
(momentary)
Partitioning
(maintained)
Occupancy sensor
(auto on/off)
Occupancy sensor
(manual on/auto off)
Zone toggle with raise/lower
Zone toggle with raise/lower
(maintained output)
(momentary output)
Zone toggle
(maintained)
Zone toggle
(momentary)
(maintained)
(momentary)
Zone control
Zone control
Wall 1 Wall 2 Wall 3 Wall 4 Wall 5 Momentary Maintained
Wall 1 Wall 2 Wall 3 Wall 4 Wall 5 Maintained Maintained
Generates events on occupancy and vacancy Maintained Maintained
Generates events on vacancy only Maintained Maintained
Toggle 1 Toggle 2 Toggle 3 Toggle 4 Toggle 5 Maintained
Toggle 1 Toggle 2 Toggle 3 Toggle 4 Toggle 5 Momentary
Toggle 1 Toggle 2 Toggle 3 Raise Lower Maintained
Toggle 1 Toggle 2 Toggle 3 Raise Lower Momentary
Toggle 1 Toggle 2 Toggle 3 Toggle 4 Toggle 5 Maintained
Toggle 1 Toggle 2 Toggle 3 Toggle 4 Toggle 5 Momentary
Pulse 1 Pulse 2 Pulse 3 Pulse 4 Pulse 5 Maintained
Pulse 1 Pulse 2 Pulse 3 Pulse 4 Pulse 5 Momentary
Maintained
Maintained
Momentary
Zone control
(pulsed output)
Hotel configuration 1
Hotel configuration 2
Integration configuration
Notes
• Occupancy sensor: Each input represents 1 sensor/group of sensors. Response to sensor event is programmable at the assigned lighting control.
• “Momentary” output pulse is of fixed duration (250 ms default). “Pulsed” output duration corresponds to activating button being held/released.
• Hotel: “Service” and “Privacy” are mutually exclusive; “Doorbell” is locked out when “Privacy” is active.
• DIP switch 1 must be up/on to activate the "Start/End Afterhours" feature on CCI4.
• DIP switch 2 must be up/on to activate the "Toggle Scene" or "Scene Blackout" feature on CCI 5.
• Occupancy sensors will not participate in partitioning logic.
Pulse 1 Pulse 2 Pulse 3 Pulse 4 Pulse 5 Maintained
Pulse 1 Pulse 2 Pulse 3 Pulse 4 Pulse 5 Momentary
Service (make up room)
Service (make up room)
Control output 1
Privacy (do not disturb)
Privacy (do not disturb)
Control output 2
Doorbell
Doorbell
Control output 3
Start/end afterhours mode
Start/end afterhours mode
Control output 4
Toggle Scene 1/ Off
Enable/ disable Scene lockout
Control output 5
1-3: Maintained or Momentary 4-5: Maintained
1-3: Maintained or Momentary 4-5: Maintained
Maintained or Momentary
Pulsed
Maintained (except 3)
Maintained (except 3)
Maintained or Momentary
Legend:
Up/On
Down/Off
page 4
QSE-IO Control Interface Programming Guide
Equipment / Functionality Table
Look below for the Equipment / Functionality you have/want,
Look to the right for the Operating Mode you need to refer to for the correct DIP switch setting and programming instructions
Table applies only to standalone systems See next page for notes
Contact Closure Inputs
Contact Closure Outputs
Control Sivoia QS Shades via CCIs
Control AC Shades from QS Shade Controllers (wallstations) via CCOs
Control / M onitor GRAFIK Eye QS and / or Energi Savr Node QS
Implement Partition Logic for 5 Partition Walls via CCIs
Receive Signals from up to 5 Groups of Occupancy Sensors
Integrate a QS System into a Hotel Room √ Control RS232 or Ethernet and/or
Monitor CC Is / CCOs Control CCOs from QS Input Devices
(e.g., wallstations)
Notes
• Table applies only to standalone systems (GRAFIK Eye QS or Energi Savr Node systems). For Quantum systems, refer to the instructions that accompanied that equipment.
• A Momentary output pulse is of fixed duration (250 ms default).
• A Pulsed output pulse's duration corresponds to the activating button being held/released.
• Possible QS input devices include seeTouch QS wallstations, Pico wireless controls (via a QSM), QS keyswitch, QS IR Eye remote, another QSE-IO control interface, or shade keypads on a GRAFIK Eye QS control unit.
then
Special
Scene Selection
Maintained √ √ √ √ √ √ √ √ Momentary √ √ √ √ √ Maintained √ √ √ √ √ √ √ √ Momentary √ Pulsed √ √ Open / Close √ 3 Presets √ Raise/Lower √ Stop if Moving √ 1 Shade Group √ 2 Shade Groups √ 5 Shade Groups
Scene Control via CCIs √ Scene Monitor via CCOs √ Zone Toggle via CCIs √ Zone Monitor via CCOs √ Sequencing √ Scene Lockout √ Zone Lockout √ Panic √ Afterhours Start/Stop √ Timeclock Disable
(GRAFIK Eye QS only)
Shade Input
Raise, Lower, Stop
Shade Input Preset
Raise/Lower
Shade Input Dual Group
Shade Input Toggle
Shade Input Dual Group
Open/Close
Shade Output
Shade Output
Shade Input Toggle
Open/Close (stop if moving)
Momentary Stop
Maintained Outputs
Partitioning
Zone Toggle
Zone Control
Shade Output
Occupancy Sensor
Momentary Outputs
Zone Control
Maintained Outputs
Momentary Outputs
Hotel
Zone Control
Pulsed Outputs
Integration
page 5
QSE-IO Control Interface Programming Guide
scene selection
special and special 2
shade stuffs
345678
345678
345678
345678
345678
345678
345678
345678
345678 345678
345678
345678
345678
345678
integration conguration
shade stuffs
partitioning occ sensor
345678
345678
345678
Scene Selection Operating Mode
• Links to one or more GRAFIK Eye QS control
units and/or Energi Savr Node areas.
• CCIs select between 4 scenes and Off.
• CCOs track currently active scene.
• Inputs: either momentary or maintained.
• Outputs: all maintained or all momentary
(see chart).
• Communicates directly with GRAFIK Eye QS
control units and Energi Savr Node systems.
Programming Instructions
1. Enter programming mode on the QSE-IO control
interface: Press and hold the Program button for 3 seconds. LEDs 1 through 5 will cycle.
2.To assign a GRAFIK Eye QS control unit to the
QSE-IO, press and hold the Scene 1 button on the GRAFIK Eye QS for 3 seconds. Repeat to assign additional GRAFIK Eye QS control units.
3. Exit programming mode on the QSE-IO control
interface: Press and hold the Program button for 3 seconds.
For programming instructions for Energi Savr Node systems, see "Energi Savr Node Handheld Programming Guide" at www.lutron.com
Dip Switch Settings Related Action
345678
345678
345678
345678
345678
Input 1: Scene 1 Input 2: Scene 2 Input 3: Scene 3 Input 4: Scene 4 Input 5: Off Outputs: Maintained
Input 1: Scene 5 Input 2: Scene 6 Input 3: Scene 7 Input 4: Scene 8 Input 5: Off Outputs: Maintained
Input 1: Scene 9 Input 2: Scene 10 Input 3: Scene 11 Input 4: Scene 12 Input 5: Off Outputs: Maintained
Input 1: Scene 13 Input 2: Scene 14 Input 3: Scene 15 Input 4: Scene 16 Input 5: Off Outputs: Maintained
Input 1: Scene 1 Input 2: Scene 2 Input 3: Scene 3 Input 4: Scene 4 Input 5: Off Outputs: Momentary
page 6
345678
345678
345678
Legend:
Up/On
Down/Off
Input 1: Scene 5 Input 2: Scene 6 Input 3: Scene 7 Input 4: Scene 8 Input 5: Off Outputs: Momentary
Input 1: Scene 9 Input 2: Scene 10 Input 3: Scene 11 Input 4: Scene 12 Input 5: Off Outputs: Momentary
Input 1: Scene 13 Input 2: Scene 14 Input 3: Scene 15 Input 4: Scene 16 Input 5: Off Outputs: Momentary
QSE-IO Control Interface Programming Guide
special and special 2
shade stuffs
partitioning occ sensor
345678
345678
345678
345678 345678
345678
345678
345678
integration conguration
shade stuffs
partitioning occ sensor
345678
345678
345678
Special Operating Mode: Sequencing
• Links to one or more GRAFIK Eye QS control
units and / or Energi Savr Node areas.
• Moves sequentially through a group of scenes
(see chart) using Input 1.
• Inputs: momentary only or maintained only
(see chart)
- Maintained: closure enables sequencing; opening disables sequencing.
- Momentary: button press toggles between enable and disable sequencing.
• Outputs: maintained.
• Communicates directly with GRAFIK Eye QS
control units and Energi Savr Node systems.
Programming Instructions
1. Enter programming mode on the QSE-IO control
interface: Press and hold the Program button for 3 seconds. LEDs 1 through 5 will cycle.
2.To assign a GRAFIK Eye QS control unit to the
QSE-IO, press and hold the Scene 1 button on the GRAFIK Eye QS control unit for 3 seconds. Repeat to assign additional GRAFIK Eye QS control units.
3. Exit programming mode on the QSE-IO control
interface: Press and hold the Program button for 3 seconds.
For programming instructions for Energi Savr Node systems, see "Energi Savr Node Handheld Programming Guide" at www.lutron.com
Dip Switch Settings Related Action
345678
345678
345678
345678
Legend:
Up/On
Down/Off
Maintained Inputs: Input 1: closure enables, opening
disables sequencing Scenes 5-16
Output: Maintained
Momentary Inputs: Input 1: button press toggles
enable/disable sequencing Scenes 5-16
Output: Maintained
Maintained Inputs: Input 1: closure enables, opening
disables sequencing Scenes 1-4
Output: Maintained
Momentary Inputs: Input 1: button press toggles
enable/disable sequencing Scenes 1-4
Output: Maintained
page 7
QSE-IO Control Interface Programming Guide
special and special 2
shade stuffs
partitioning occ sensor
345678
345678
345678
345678 345678
345678
345678
345678
integration conguration
shade stuffs
partitioning occ sensor
345678
345678
345678
Special Operating Mode: Zone Lockout
• Links to one or more GRAFIK Eye QS control
units and / or Energi Savr Node areas.
• Prevents modifications to programmed preset
light levels using Input 2.
• Inputs: momentary only or maintained only
(see chart)
- Maintained: closure enables lockout; opening disables lockout.
- Momentary: button presses toggle between enable and disable lockout.
• Outputs: maintained only.
• Communicates directly with GRAFIK Eye QS
control units and Energi Savr Node systems.
Programming Instructions
1. Enter programming mode on the QSE-IO control
interface: Press and hold the Program button for 3 seconds. LEDs 1 through 5 will cycle.
2.To assign a GRAFIK Eye QS control unit to the
QSE-IO, press and hold the Scene 1 button on the GRAFIK Eye QS control unit for 3 seconds. Repeat to assign additional GRAFIK Eye QS control units.
3. Exit programming mode on the QSE-IO control
interface: Press and hold the Program button for 3 seconds.
For programming instructions for Energi Savr Node systems, see "Energi Savr Node Handheld Programming Guide" at www.lutron.com
Dip Switch Settings
345678
345678
345678
345678
Legend:
Up/On
Down/Off
Related Action
Maintained Inputs: Input 2: closure enables,
opening disables zone lockout
Output: Maintained
Momentary Inputs: Input 2: button press toggles
enable/disable zone lockout
Output: Maintained
Maintained Inputs: Input 1: closure enables,
opening disables zone lockout
Output: Maintained
Momentary Inputs: Input 1: button press toggles
enable/disable zone lockout
Output: Maintained
page 8
QSE-IO Control Interface Programming Guide
special and special 2
shade stuffs
partitioning occ sensor
345678
345678
345678
345678 345678
345678
345678
345678
integration conguration
shade stuffs
partitioning occ sensor
345678
345678
345678
Special Operating Mode: Scene Lockout
• Links to one or more GRAFIK Eye QS control units
and / or Energi Savr Node areas.
• Prevents selected scene or programmed preset
levels from changing using Input 3.
• Inputs: momentary only or maintained only
(see chart)
- Maintained: closure enables lockout; opening disables lockout.
- Momentary: button presses toggle between enable and disable lockout.
• Outputs: maintained.
• Communicates directly with GRAFIK Eye QS
control units and Energi Savr Node systems.
Programming Instructions
1. Enter programming mode on the QSE-IO control
interface: Press and hold the Program button for 3 seconds. LEDs 1 through 5 will cycle.
2.To assign a GRAFIK Eye QS control unit to the
QSE-IO, press and hold the Scene 1 button on the GRAFIK Eye QS control unit for 3 seconds. Repeat to assign additional GRAFIK Eye QS control units.
3. Exit programming mode on the QSE-IO control
interface: Press and hold the Program button for 3 seconds.
For programming instructions for Energi Savr Node systems, see "Energi Savr Node Handheld Programming Guide" at www.lutron.com
Dip Switch Settings
345678
345678
345678
345678
Legend:
Up/On
Down/Off
Related Action
Maintained Inputs: Input 3: closure enables,
opening disables scene lockout
Output: Maintained
Momentary Inputs: Input 3: button press toggles
enable/disable scene lockout
Output: Maintained
Maintained Inputs: Input 1: closure enables, opening
disables scene lockout
Output: Maintained
Momentary Inputs: Input 1: button press toggles
enable/disable scene lockout
Output: Maintained
page 9
QSE-IO Control Interface Programming Guide
special and special 2
shade stuffs
partitioning occ sensor
345678
345678
345678
345678 345678
345678
345678
345678
integration conguration
shade stuffs
partitioning occ sensor
345678
345678
345678
Special Operating Mode: Panic
• Links to one or more GRAFIK Eye QS control
units and / or Energi Savr Node areas.
• Activates Scene 16 and enables scene lockout
using Input 4.
• Inputs: momentary only or maintained only
(see chart)
- Maintained: closure enables panic; opening disables panic.
- Momentary: button presses toggle between enable and disable panic.
• Outputs: maintained only.
• Communicates directly with GRAFIK Eye QS
control units and Energi Savr Node systems.
Programming Instructions
1. Enter programming mode on the QSE-IO control
interface: Press and hold the Program button for 3 seconds. LEDs 1 through 5 will cycle.
2.To assign a GRAFIK Eye QS control unit to the
QSE-IO, press and hold the Scene 1 button on the GRAFIK Eye QS control unit for 3 seconds. Repeat to assign additional GRAFIK Eye QS control units.
3. Exit programming mode on the QSE-IO control
interface: Press and hold the Program button for 3 seconds.
For programming instructions for Energi Savr Node systems, see "Energi Savr Node Handheld Programming Guide" at www.lutron.com
Dip Switch Settings
345678
345678
345678
345678
Legend:
Up/On
Down/Off
Related Action
Maintained Inputs: Input 4: closure enables,
opening disables panic
Output: Maintained
Momentary Inputs: Input 4: button press toggles
enable/disable panic
Output: Maintained
Maintained Inputs: Input 1: closure enables, opening
disables panic
Output: Maintained
Momentary Inputs: Input 1: button press toggles
enable/disable panic
Output: Maintained