Lutron NT-600, NT-1000, NT-1500, NT-2000, NT-603P Installation Manual

...
Page 1
Incandescent Dimmers NT-Series Magnetic Low-Voltage Dimmers NTLV-Series Electronic Low-Voltage Dimmers NTELV-Series Fan-Speed Controls NTFS-Series Quiet Fan-Speed Controls NTFSQ-Series Fluorescent Dimmers NTF-Series
Quiet Fan-Speed Controls NTFSQ-Series
NTFSQ 120 V~ 60 Hz These controls are for use with a single ceiling paddle fan only, rated at 1.5 A maximum. (The current rating of your fan motor may be determined from the motor nameplate, packaging, or by contacting the manufacturer.) Do not wire into a circuit with a GFCI breaker or receptacle. Set multi-speed fans to their highest setting before installing controls. Do not use these controls for light fixtures. Not recommended for use with Hunter Original®Series fan; contact Lutron's Customer Service department for suitable controls.
Fluorescent Dimmers NTF-Series
NTF-10, NTFTU-5A 120 V~ 60 Hz NTF-10-277 277 V~ 60 Hz
These dimmers are for use with Lutron's FDB, ECO, HL3, or CB3 Series Electronic Fluorescent Dimming Ballasts only. Refer to indi­vidual series specification sheets for maximum capacity. Do not use with other ballasts.
Important Notes
Please read before installing.
1. Install in accordance with national and local electrical codes.
2. When no "grounding means" exist within the wallbox then the
NEC©2008, Article 404-9 allows a dimmer without a ground connections to be installed as a replacement, as long as a plastic, noncombustible wallplate is used. For this type of installation, cap or remove the green ground wire on the dimmer and use an appropriate wallplate such as Lutron’s Nova T*
®
series wallplates.
3. These controls are designed to operate in ambient temperatures
from 32 °F to 104 °F (0 °C to 40 °C)
4. Strip wallbox wires. Important: When making wire connections,
follow the recommended strip lengths and combinations for the supplied wire connectors. Twist wire connector tight making sure that no bare wire is exposed. Note: Wire connectors provid­ed are suitable for copper wire only. For aluminum wire, consult an electrician.
5. Check for short circuits in new installations before wiring con-
trols. With power OFF, use standard switch and connect to lamp and voltage line. Turn power ON. If breaker trips, a short is present. Correct wiring and check circuit again. Install control only when short is no longer present.
6. Multiphase applications: Use a separate neutral for each phase
containing a control circuit. For more information, call the
Lutron Technical Support Center
and ask for Application Note
17, "Common Neutral Interaction."
7. To ensure proper dimming performance and full lamp life, fluo-
rescent lamps must be operated at full intensity for 100 hours prior to dimming.
Cleaning Instructions
To clean, wipe with a clean damp cloth. DO NOT use any chemical cleaning solutions.
Installation Instructions
Please Leave for Occupant
Description
Incandescent Dimmers NT-Series
NT-600, NT-1000, NT-1500, NT-2000, NT-603P, NT-1003P, NT-1503P 120 V~ 60 Hz These dimmers are for use with incandescent and halogen lamps only, 120 V~ 60 Hz. DO NOT use to control receptacles, fluorescent lighting fixtures, compact flourescent (Energy Saver) lamps, motor­operated or transformer-supplied appliances, or electronic low-volt­age lighting fixtures.
Magnetic Low-Voltage Dimmers NTLV-Series
NTLV-600, NTLV-1000, NTLV-1500, NTLV-603P, NTLV-1003P, NTLV-1503P 120 V~ 60 Hz NTLV-600-277, NTLV-1000-277 277 V~ 60 Hz These dimmers are for use with magnetic low-voltage incandescent and halogen lamps only. Do not connect to receptacles, fluorescent fixtures, or motor-operated appliances. Use with core and coil (mag­netic) low-voltage transformers. Do not use to control a solid-state electronic low-voltage transformer. Call the
Lutron Technical
Support Center
for more information. Ask for Application Note 19: "Guide to Dimming Low-Voltage Lighting." Operation of a dimmed low-voltage circuit with all lamps removed or inoperative may result in current flow in excess of normal levels. To avoid possible transformer failure, Lutron strongly recommends the following: a. Do not operate dimmed low-voltage circuits without operative
lamps in place.
b. Replace burned-out bulbs immediately. c. Use transformers that incorporate thermal protection or fused
transformer primary windings in order to prevent transformer failure caused by excess current.
Electronic Low-Voltage Dimmers NTELV-Series
NTELV-300, NTELV-600 120 V~ 60 Hz These dimmers are for use with electronic transformer-supplied low-voltage lighting only. Do not connect to magnetic transformer­supplied low-voltage fixtures, receptacles, fluorescent fixtures, or motor-operated appliances. Some fixture manufacturers do not rec­ommend dimming their solid-state transformers. To determine if a fixture may be dimmed, consult Lutron or the fixture manufacturer. These dimmers are overload-protected. If more than the rated load is applied, power to the circuit will shut off until the dimmer cools. If this happens, remove excess load from the circuit.
Fan-Speed Controls NTFS-Series
NTFS-6E, NTFS-12E 120 V~ 60 Hz These controls are for use only with fan or blower units that are operated by shaded-pole or permanently-split capacitor motors. Use with other types of motors may damage equipment and void warranty. Use with fans marked "Suitable for use with solid-state fan-speed controls only." Set multi-speed fans to their highest setting before installing controls.
This product may be covered by one or more of the following U.S. patents: 5,038,081; 5,510,679; 6,310,439 and corre­sponding foreign patents. Lutron and Nova T* are registered trademarks of Lutron Electronics Co., Inc.The design of this product may be covered by one or more of the following U.S. trademark registrations: 1,617,349; 1,626,714; 1,624,489; 1,624,490; and 1,638,913. Original is a registered trademark of Hunter Fan Company, Memphis, Tennessee. NEC is a registered trademark of the National Fire Protection Association, Quincy, Massachusetts. © 2008 Lutron Electronics Co., Inc.
P/N 030-1030
Page 2
Wiring Diagrams
Wiring Diagram 5
Wiring Diagram 6
Wiring Diagram 7
= Indicates different
colored screw
Wiring Diagram 4
NOTE: Dimmers may be wired on either the line side or the load
side of the switch(es).
Live
Black
Red
Red
Green or
Bare
Ground
Dimmer
4-Way switch
3-Way Switch
Load
Neutral
Ground
Ground
120 V~
60 Hz
Live Black
Red
Yellow
Green or Bare
Ground
Fan
Light
Neutral
Control
120 V~
60 Hz
Live
Black
Green or Bare
Ground
White
Dimmer
Yellow
Red
Orange
Black
White
To Additional Ballasts
Neutral
120/277 V~
60 Hz
Orange
Black
White
Lutron Dimming Ballast
Lutron Dimming Ballast
Live
Black
Red or Yellow
Dimmer
White
Ground
Green or Bare
Load
Neutral
120/277 V~
60 Hz
Wiring
Model Number Diagram
NT-600, NT-1000, NT-1500, NT-2000, NTFTU-5A 1 NT-603P, NT-1003P, NT-1503P
Single-Pole 2 3-Way 3
4-Way 4 NTLV-600, NTLV-1000, NTLV-1500 1 NTLV-600-277, NTLV-1000-277 7 NTLV-603P, NTLV-1003P, NTLV-1503P
Single-Pole 2
3-Way 3
4-Way 4 NTELV-300, NTELV-600 7 NTFS-6E, NTFS-12E 5 NTFSQ 1 NTF-10, NTF-10-277 6
Wiring Diagram 1
Live Black
Control
Ground
Green or Bare
Load
Neutral
Black
120 V~
60 Hz
Wiring Diagram 2
Live
Red
Dimmer
Ground
Green or Bare
Load
Neutral
Black
120 V~
60 Hz
Red
Wiring Diagram 3
NOTE: Dimmers may be wired on either the line side or the load
side of the switch.
= Indicates different
colored screw
Live Black
Dimmer
Red
Red
Ground
3-Way Switch
Ground
Load
Neutral
Green or Bare
120 V~
60 Hz
Page 3
Control
Faceplate Adapter
Slider
Faceplate
Adapter Mounting Screws
Control Mounting Screws
Operation
Slide-to-Off Controls
Raise slider to increase light intensity. Lower slider to decrease light intensity and turn off.
Preset Dimmers
Push button in center of slider to alternately turn lights on to preset level (set by slider) or turn lights off. Raise slider to increase light intensity. Lower slider to decrease light intensity.
3-Way and 4-Way Switches
When switching power from remote location, lights will turn on to level set on dimmer (by slider), or turn off. Move slider up or down to turn lights on or off. Note, use only one dimmer per circuit.
Fluorescent Dimmers
Dimmers are factory calibrated and do not require low-end light adjustment. If lamps flicker or drop out at the minimum dimming level there may be an installation error. Continued use of the system in this mode will cause premature lamp failure. If this is occurring, call the
Lutron Technical Support Center
at: 1.800.523.9466.
To ensure proper dimming performance and full lamp life, fluores­cent lamps must be operated at full intensity for 100 hours prior to dimming.
Installation
If more than one control is to be installed in the same wallbox, review the Multigang Installation section (back page) before begin­ning. Lutron multigang faceplates are available for ganging multiple units.
1. Turn power OFF at circuit breaker or remove fuse.
WARNING: Wiring with power on may result in personal injury.
Damage to this product caused by wiring with power on voids warranty.
2. Remove faceplate and faceplate adapter from control to prevent
damage and to access mounting holes. Pull from top of face­plate to remove. Unscrew faceplate adapter. Set aside.
3. Wire control per appropriate wiring diagram (see previous page)
using wire connectors provided.
Note: Color names refer to the wire colors on the control.
4. Push wires into wallbox, allowing room for control to be inserted.
Do not pinch wires between wallbox and control.
5. Mount control to wallbox using control mounting screws provid-
ed. Controls must be mounted vertically. See stamp on control for correct positioning.
6. Mount adapter plate with adapter mounting screws provided
(see below).
7. Snap on slider and faceplate.
8. Turn power ON at circuit breaker or replace fuse.
Page 4
Lutron Electronics Co., Inc. 7200 Suter Road Coopersburg, PA 18036-1299 U.S.A. Made and printed in U.S.A. 10/08 P/N 030-1030 Rev. A
Multigang Installation
Multiple controls can be installed in a multigang wallbox or a series of interconnected wallboxes for a clean, consolidated appearance. Lutron multigang faceplates are available to complete the installation. Refer to instruction sheet supplied with multigang faceplates for installation. For new installations, controls can be ganged without removing side sections, but, to reduce the size of the multigang installation or to fit existing wallboxes, inner side sections must be removed. Because side sections are designed to dissipate heat, removing them derates the capacity of the control. Note: When ganging any combination of small and large controls, place all small controls on one end of the gang and all large controls on the other. Use the chart below to determine the size and rating of each control.
*
NT-2000 cannot have side sections removed.
Note: The Wallbox Requirement Charts on this sheet do not apply for the NT-2000. See the NT-2000 instruction sheet for the appropriate requirements.
Limited Warranty
(Valid only in U.S.A., Canada, Puerto Rico, and the Caribbean.)
Lutron will, at its option, repair or replace any unit that is defective in materials or manufacture with­in one year after purchase. For warranty service, return unit to place of purchase or mail to Lutron at 7200 Suter Rd., Coopersburg, PA 18036-1299, postage pre-paid.
THIS WARRANTY IS IN LIEU OF ALL OTHER EXPRESS WARRANTIES, AND THE IMPLIED WARRANTY OF MERCHANTABILITY IS LIMITED TO ONE YEAR FROM PURCHASE. THIS WARRANTY DOES NOT COVER THE COST OF INSTALLATION, REMOVAL OR REINSTALLA­TION, OR DAMAGE RESULTING FROM MISUSE, ABUSE, OR DAMAGE FROM IMPROPER WIRING OR INSTALLATION. THIS WARRANTY DOES NOT COVER INCIDENTAL OR CONSE­QUENTIAL DAMAGES. LUTRON’S LIABILITY ON ANY CLAIM FOR DAMAGES ARISING OUT OF OR IN CONNECTION WITH THE MANUFACTURE, SALE, INSTALLATION, DELIVERY, OR USE OF THE UNIT SHALL NEVER EXCEED THE PURCHASE PRICE OF THE UNIT.
This warranty gives you specific legal rights, and you may have other rights which vary from state to state. Some states do not allow the exclusion or limitation of incidental or consequential damages, or limitation on how long an implied warranty may last, so the above limitations may not apply to you. © 2008 Lutron Electronics Co., Inc.
Worldwide Technical and Sales Assistance
If you have questions concerning the installation or operation of these products, call the
Lutron Technical Support Center.
Please
provide exact model number when calling.
1.800.523.9466 (U.S.A., Canada, and the Caribbean) Other Countries call +1.610.282.3800 Fax +1.610.282.6311 Visit our web site at www.lutron.com
Remove inner side sections (shaded) only.
Do not remove outer side sections.
Side Sections Removed
(Derating Required)
Number of Small Controls
01234
0 0 1 1+1 4 4+1 Number 113568 of Large2467910 Controls 3 6 8 10 11 13
4 9 11 12 14 15
Note: When ganging an even number of small controls with side sections intact, use gangable 3 in x 2 in (76 mm x 51 mm) wallboxes. Space an additional wallbox 3/4 in (19 mm) apart from the other wallboxes. A 3/4 in (19 mm) chase nipple is recommended as a spacer between wallboxes. Example: Wallbox arrangement required for ganging 4 small controls with no side sections removed:
No Side Sections Removed
(Derating Not Required)
Remove inner side sections from controls. Using pliers, bend side sections up and down until they break off.
Single-gang wallbox
3/4 in (19 mm) space (use chase nipple or Lutron P/N “PLUS-ADPTR-3.5”)
Four-gang wallbox
Wallbox Gang Size Requirement Chart
Wallbox Gang Size Requirement Chart
Control Size and Derating Chart
Control No Sides 1 Side 2 Sides
Model
Size Removed Removed Removed
NT-600 S 600 W 500 W 300 W NT-1000 S 1000 W 900 W 700 W NT-1500 L 1500 W 1250 W 1000 W NT-2000
* L 1950 W
NTLV-600 S 600 VA/ 450 W 500 VA/ 400 W 300 VA / 200 W NTLV-600-277 S 600 VA/ 450 W 500 VA/ 400 W 300 VA / 200 W NTLV-1000 S 1000 VA/ 800 W 900 VA/ 700 W 700 VA / 550 W NTLV-1000-277 S 1000 VA / 200 W 900 VA/ 1000 W 700 VA / 800 W NTLV-1500 L 1500 VA/ 1200 W 1250 VA/ 1000 W 1000 VA/ 800 W NT-603P S 600 W 500 W 300 W NT-1003P S 1000 W 900 W 700 W NT-1503P L 1500 W 1250 W 1000 W NTLV-603P S 600 VA / 450W 500 VA / 400W 300 VA/ 200W NTLV-1003P S 1000 VA/ 800W 900 VA/ 200W 700 VA / 550W NTLV-1503P L 1500 VA / 1200W 1250 VA/ 1000W 1000 VA/ 800W NTELV-300 S 300 W 300 W 250 W NTELV-600 S 600 W 500 W 400 W NTFS-6E S 6 A 4.2 A 2.5 A NTFS-12E L 12 A 10 A 8.3 A NTFSQ S 1.5 A 1.5 A 1.5 A NTF-10 S 16 A 16 A 16 A NTF-10-277 S 8 A 8 A 8 A NTFTU-5A S 5 A 4 A 3.3 A NT-1PS S 20 A 20 A 20 A NT-3PS S 20 A 20 A 20 A NT-4PS S 20 A 20 A 20 A
Number of Small Controls
0123456
00123456 Number 11345678 of Large 235678910 Controls 35789101112
4 7 9 10 11 12 13 14
Loading...