HomeWorks LQSE-4A5-230-DPRO LED+ Phase Adaptive Power Module
1
3691155b 1 01.15.21
PRO LED+ Phase Adaptive
Power Module
The DIN Power Module (DPM) family is a group of
CCI
modular products for the control of lighting loads and
motor loads.
This document describes the following product:
LQSE-4A5-230-D: 4-Zone DIN Power Module
for phase control dimming
of lighting loads
Features
Input
Entrada
Entrée
Tc > 70 ˚C
Prog
LQSE-4A5-230-D
LQSE-4A5-230-D
Zn 1 Zn 2 Zn 3 Zn 4
Opt
Def
1
2
+44.(0)20.7702.0657
3
220-240 V~ 50 / 60 Hz 10 A
lutron.com
H
M
L
• PRO LED+ Phase Adaptive Power Modules can be
used in a HomeWorks system using a QSX processor.
• Includes QS link for seamless integration of lights
and controls.
• An auto-detect mode is available to detect
and configure forward-phase or reverse-phase
(leading-edge or trailing-edge) dimming for
incandescent / halogen, electronic / magnetic lowvoltage and neon / cold cathode light sources.
• A locked forward-phase or reverse-phase (leadingedge or trailing-edge) mode is available.
• Controls dimmable LED loads. Refer to
www.lutron.com/ledtool for compatibility with
dimmable LED light sources.
• RTISS technology compensates for incoming mains
voltage variations such as changes in Root Mean
Square (RMS) voltage, frequency shifts (up to ± 2%
change in frequency /second), harmonics and
line noise.
• RTISS-TE technology allows for true instantaneous
voltage compensation for incoming mains voltage
variations. Only operates in reverse-phase (trailingedge) when "voltage-comp." is enabled.
• RTISS-ICM technology is able to withstand highinrush LEDs, bulb blowouts, and direct shorts.
• Provides air gap off (when all zones are off).
• Integral protection for common temporary over-current
and over-voltage conditions.
• LEDs on the module provide diagnostic information.
• Buttons on the module provide override control.
• Manual Override contact closure input (CCI).
• Power failure memory automatically returns the
outputs to the levels they were set to prior to a
power outage.
SPECIFICATION SUBMITTALPage
Job Name:
Model Numbers:
Job Number:
®
HomeWorks LQSE-4A5-230-DPRO LED+ Phase Adaptive Power Module
2
3691155b 2 01.15.21
System Example
Contact Closure Input
seeTouch
QS Wallstation
HomeWorks
Power Module
Zn 1
Zn 2Zn 3Zn 4
5 /16 in
4.4 in-lb
8 mm
•
m
0.5 N
CCI
COM
MUX
COM
MUX
Input | Entrada
HomeWorks QS
Entrée
Def
LQSE-4T5-120-D
Ta > 65 ˚C
Prog
HN
120 V~ 50 / 60 Hz
lutron.com
120 V~ 5 A ea
123
Opt
1
2
3
0-10 V-
50 mA
H
M
L
4
Adaptive Power
Module
CCI
Zn 1Zn 2Zn 3Zn 4
Input
Entrada
Entrée
Tc > 70 ˚C
Prog
LQSE-4A5-230-D
Opt
Def
1
2
3
+44.(0)20.7702.0657
220-240 V~ 50 / 60 Hz 10 A
lutron.com
H
M
L
220 - 240 V~ Control Power(4) Zone Outputs
HomeWorks
Panel
7 mm
0,28 in
L1
+24
COML2COM
CCI
HomeWorks
HQP7-2
24-36 V- 250 mA SELV NEC® Class 2
lutron.com +1.844.LUTRON1
+44.(0)20.7702.0657
L1: 24 V- 1.0 A L2: 24 V- 1.0 A
m
0,5 N
•
V+
V+
4,4 in-lb
MUX
MUX
MUX
MUX
COM
COM
HomeWorks QSX
Processor
1
===LED | DEL
x
TxR
QS Contact
Closure
Interface
QS Link
GRAFIK
Eye QS
Up to 100
total QS
devices
Sivoia QS
Shade / Drapery
Notes:
1
See "Output Zone Ratings" in “Specifications” section, for specific load types ratings.
SPECIFICATION SUBMITTALPage
Job Name:
Model Numbers:
Job Number:
®
HomeWorks LQSE-4A5-230-DPRO LED+ Phase Adaptive Power Module
3
3691155b 3 01.15.21
Specifications
Adaptive Power Module
Power
• 220 - 240 V~ 50/60 Hz
• 10 A maximum total input current.
• Lightning strike protection meets ANSI/IEEE standard
62.31-1980. Can withstand voltage surges of up to
6000 V and current surges of up to 3000 A.
• Contact Lutron for ungrounded delta feed applications.
Regulatory Approvals
• Lutron Quality Systems registered to ISO 9001.2015
• RoHS Compliant
• IEC/EN 60669-2-1
• CE marked
• Rated for 150 W of LEDi per IEC 60669
• Output must be directly connected to the load.
• Output breakers or switches must not be used.
• Run a separate neutral for each load circuit.
A common neutral connection is not recommended.
• Unit may be powered by Ground Fault Interrupter (GFI)
or Residual Current Circuit Breaker with Overload
(RCBO) protected circuit if required. Load circuit wiring
(from breaker to unit to load) must be run in its own
non-metallic conduit, or nuisance tripping may occur.
Maximum wire length between the unit and the load
must be less than 100 ft (30.5 m).
• For applications requiring 0–10 V- control, use Ten
Volt Interface (GRX-TVI) or the LQSE-4T10-D.
Environment
• See Mounting on page 6 for thermal specifications.
• Relative humidity: less than 90% non-condensing.
• For indoor use only.
Output Zone Ratings
• Each zone has no minimum load requirement.
• When programmed to "auto detect" mode, the
unit starts in reverse-phase (trailing-edge) and if
an incompatible load is detected, it will convert to
forward-phase (leading-edge).
• Internal relay provides an air gap off when all zones
are off.
• One load type per zone.
• Output must not be used to control receptacles. If
controlling plug-in lamps, installation must ensure a
method of preventing non-rated loads being plugged
into the unit.
• For applications requiring higher wattage ratings, use a
power booster (PHPM-PA-277/DV).
• For dimmable loads only. For applications requiring
switching control, use a GRX-TVI or the
LQSE-4S5-230-D.
SPECIFICATION SUBMITTALPage
Job Name:
Job Number:
Model Numbers:
®
HomeWorks LQSE-4A5-230-DPRO LED+ Phase Adaptive Power Module
LEDDEL
4
3691155b 4 01.15.21
Specifications (continued)
Output Zone Ratings (continued)
• No Derating is required when using a Lutron panel. See Lutron Specification Submittals 369788 at www.lutron.com
•
No Derating is required if all the conditions below are met:
– Calibration point maximum is 70 ºC (158 ºF)
– Room ambient temperature is between 0 ºC and 30 ºC (32 ºF and 86 ºF)
– Panel ambient temperature is between 0 ºC and 50 ºC (32 ºF and 122 ºF)
• 100 W Derating is required on all zones for a single module in a single non-ventilated DIN enclosure if:
– The room ambient temperature is between 30 ºC and 40 ºC (86 ºF and 104 ºF)
• 200 W Derating is required on all zones for a multiple row non-ventilated DIN enclosure if:
–
The room ambient temperature is between 30 ºC and 40 ºC (86 ºF and 104 ºF)
Each zone is rated for the following wattage and load types
Additional load type options are available in the HomeWorks software suite, some may require an interface. Contact Lutron for details.
B Refer to Lutron.com/ledtool for compatibility testing results. Using LED fixtures that are not tested can result in the fixtures not turning-on or poor dimming
quality. LED dimming performance can vary from fixture to fixture and cannot be guaranteed. Ratings listed refer to the LED input current/wattage, higher
ratings (up to the incandescent rating) can be achieved for specific LED fixtures based on Lutron testing results.
C Actual lamp wattage.
D
Only use iron core transformers intended for use with an electronic switch or dimmer per Clause 8.3 of IEC / EN 60669-2-1.
D
1.7 A (400 W)N/AN/A1.0 A (250 W)N /AN/A
800 VA
(525 WC)
100 W
Derating
700 VA
(525 WC)
200 W
DeratingNo Derating
600 VA
(450 WC)
500 VA
(375 WC)
100 W
Derating
400 VA
(300 WC)
200 W
Derating
300 VA
(225 WC)
SPECIFICATION SUBMITTALPage
Job Name:
Model Numbers:
Job Number: