Lutron LQSE-4A5-120-D User Manual

®
HomeWorks LQSE-4A5-120-D PRO LED+ Phase Adaptive Power Module
1
3691126b 1 05.08.20
The DIN Power Module (DPM) family is a group of modular products for the control of lighting loads and motor loads.
This document describes the following product: LQSE-4A5-120-D: 4-Zone DIN Power Module
for phase control dimming of lighting loads
Features
• PRO LED+ Phase Adaptive Power Modules can be used in a HomeWorks system using a QSX processor.
• Includes QS link for seamless integration of lights and controls.
• An auto-detect mode is available to detect and configure forward-phase or reverse-phase dimming for incandescent / halogen, electronic / magnetic low-voltage and neon / cold cathode light sources.
• A locked forward-phase or reverse-phase mode is available.
• Controls dimmable LED loads. Refer to www.lutron.com/ledtool for compatibility with dimmable LED light sources.
• NEMA SSL 7A-2015 compliant for compatibility with solid state lighting.
• RTISS technology compensates for incoming line­voltage variations such as changes in Root Mean Square (RMS) voltage, frequency shifts (up to ± 2% change in frequency /second), harmonics and line noise.
• RTISS-TE technology allows for true instantaneous voltage compensation for incoming line-voltage variations. Only operates in reverse-phase when "voltage-comp." is enabled.
• RTISS-ICM technology is able to withstand high-inrush LEDs, bulb blowouts, and direct shorts
• Provides air gap off (when all zones are off).
• Integral protection for common temporary over-current and over-voltage conditions.
LQ SE- 4A5 -120 -D
• LEDs on the module provide diagnostic information.
• Buttons on the module provide override control.
• Manual Override contact closure input (CCI).
• UL
® 924 certified for use with a LUT-ELI emergency
lighting interface.
• Power failure memory automatically returns the outputs to the levels they were set to prior to a power outage.
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
®
HomeWorks LQSE-4A5-120-D PRO LED+ Phase Adaptive Power Module
2
3691126b 2 05.08.20
System Example
Contact Closure Input
Adaptive Power Module
120 V~ Control Power
800 W Adaptive load
500 W Adaptive load
500 W Adaptive load
500 W Adaptive load
HomeWorks
Palladiom Keypad
HomeWorks
Panel
Power Module
QS Contact Closure Interface
GRAFIK Eye QS
Zn 1
Zn 2Zn 3Zn 4
5 /16 in
4.4 in-lb
8 mm
m
0.5 N
CCI
COM
MUX
COM
MUX
0-10 V-
120 V~ 5 A ea
123
50 mA
H
Def
Opt
1
M 2 3
L
4
Input | Entrada
HomeWorks QS
Entrée
LQSE-4T5-120-D
Ta > 65 ˚C
120 V~ 50 / 60 Hz
Prog
lutron.com
HN
Up to 100
QS Link
7 mm 0,28 in
L1
+24
COML2COM
CCI
HomeWorks
HQP7-2
24-36 V- 250 mA SELV NEC® Class 2
lutron.com +1.844.LUTRON1
+44.(0)20.7702.0657
L1: 24 V- 1.0 A L2: 24 V- 1.0 A
m
0,5 N
===LED | DEL
x
TxR
V+
V+
4,4 in-lb
MUX
MUX
MUX
MUX
COM
COM
HomeWorks QSX Processor
1
1
1
1
Sivoia QS Shade / Drapery
total QS devices
Notes:
1
See "Output Zone Ratings" in “Specifications” section, for specific load types ratings.
SPECIFICATION SUBMITTAL Page
Job Name:
Model Numbers:
Job Number:
®
HomeWorks LQSE-4A5-120-D PRO LED+ Phase Adaptive Power Module
3
3691126b 3 05.08.20
Specifications
Adaptive Power Module
Power
• 120 V~ 50/60 Hz
• 16 A maximum total input current.
• Lightning strike protection meets ANSI/IEEE standard
62.31-1980. Can withstand voltage surges of up to 6000 V and current surges of up to 3000 A.
• Contact Lutron for ungrounded delta feed applications.
Regulatory Approvals
• Lutron Quality Systems registered to ISO 9001.2015
• cULus Listed
• NOM Certified
• ICES-5( B) / NMB-5(B)
• FCC Class B
® 924
• UL
• NEMA SSL 7A-2015
Environment
• See Mounting on page 6 for thermal specifications.
• Relative humidity: less than 90% non-condensing.
• For indoor use only.
Output Zone Ratings
• Each zone has no minimum load requirement.
• When programmed to "auto detect" mode, the unit starts in reverse-phase and if an incompatible load is detected, it will convert to forward-phase.
• Internal relay provides an air gap off when all zones are off.
• One load type per zone.
• Output must not be used to control receptacles. If controlling plug-in lamps, installation must ensure a method of preventing non-rated loads being plugged into the unit. An example is a dedicated receptacle with an alternate plug load such as a Duplex Dimming Receptacle (NTR-15-DDTR-WH) and Dimming Lamp Plug (RP-FDU-10-).
Output must be directly connected to the load.
• Output breakers or switches must not be used.
• Run a separate neutral for each load circuit. A common neutral connection is not recommended.
• Unit may be powered by Ground Fault Circuit Interrupter (GFCI) or Arc Fault Circuit Interrupter (AFCI) if required. If using a GFCI or an AFCI incorporating GFCI protection, maximum wire length between the power module and the load must be less than 100 ft (30 m). Load circuit wiring (from breaker to unit to load) must be run in its own non-metallic conduit, or nuisance tripping may occur.
• For applications requiring 0–10 V- control, use Ten Volt Interface (GRX-TVI) or the LQSE-4T5-120-D.
• For applications requiring higher wattage ratings, use a power booster (PHPM-PA-120-WH).
• For dimmable loads only. For applications requiring switching control, use a PHPM-SW-DV-WH interface or the LQSE-4S8-120-D.
• Works up to the output current rating with all dimmable LED drivers whose inrush current does not exceed NEMA410 standards for electronic ballast / driver.
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
®
HomeWorks LQSE-4A5-120-D PRO LED+ Phase Adaptive Power Module
4
3691126b 4 05.08.20
Specifications (continued)
Output Zone Ratings (continued)
No Derating is required when using a Lutron panel. See Lutron Specification Submittals 3691055 or 3691106 at www.lutron.com No Derating is required if all the conditions below are met:
• – Calibration point maximum is 158 ºF (70 ºC) – Room ambient temperature is between 32 ºF and 86 ºF (0 ºC and 30 ºC) – Panel ambient temperature is between 32 ºF and 122 ºF (0 ºC and 50 ºC)
100 W Derating is required on all zones for a single module in a single non-ventilated DIN enclosure if: – The room ambient temperature is between 86 ºF and 104 ºF (30 ºC and 40 ºC)
200 W Derating is required on all zones for multiple row non-ventilated DIN enclosure if: –
The room ambient temperature is between 86 ºF and 104 ºF (30 ºC and 40 ºC)
A, B
Each zone is rated for the following wattage and load types
Zone 1 Rating Zone 2, 3 and 4 Rating (per zone)
Load Type
No Derating
LED (reverse-phase)
Lutron Hi-lume A-series LTE
LED SSL7A-2015 (forward-phase) E400 W 400 W 400 W 200 W 200 W 200 W
Incandescent / Halogen, ELV 800 W 700 W 600 W 500 W 400 W 300 W
Neon / Co ld Cathode, MLV
B
F
D
6.6 A 5.8 A 5 A 4.2 A 3.3 A 2.5 A
4.0 A (20 drivers maximum)
800 VA (525 WC) 700 VA (525 WC) 600 VA (450 WC) 500 VA (375 WC) 400 VA (300 WC) 300 VA (225 WC)
100 W Derating
3.2 A (20 drivers maximum)
200 W Derating No Derating
2.4 A (20 drivers maximum)
:
3.0 A (13 drivers maximum)
100 W Derating
2.2 A (13 drivers maximum)
200 W Derating
1.4 A (13 drivers maximum)
A
Additional load type options are available in the HomeWorks software suite, some may require an interface. Contact Lutron for details.
B Works with all dimmable LED drivers whose inrush current does not exceed NEMA410 standards for electronic ballast/drivers. Refer to
www.lutron.com/ledtool for specific LED compatibility information and recommended LED light sources.
C Actual lamp wattage.
D
Only use iron core transformers intended for use with an electronic switch or dimmer per Clause 8.3 of IEC / EN 60669-2-1.
E
Complies with SSL7A-2015 when configured in the HomeWorks software suite to LED forward phase with low-end trim set to 10% and high-end trim set to 90%.
F
Load type must be set to "Hi-lume 1% 2-Wire LTE LED", with low-end trim = 32% and high-end trim = 78%. Setting the proper trim and load type is necessary to ensure optimal performance and 1% dimming capability.
SPECIFICATION SUBMITTAL Page
Job Name:
Model Numbers:
Job Number:
®
HomeWorks LQSE-4A5-120-D PRO LED+ Phase Adaptive Power Module
5
3691126b 5 05.08.20
Specifications (continued)
Out of Box Functionality
Terminals (Torque, wire gauge & type ratings)
• Mains wiring: 5 in-lbs (0.6 N•m)
14 AWG to 10 AWG (2.5 mm² to 4.0 mm²)
(single wire, solid or stranded)
• Zone wiring: 5 in-lbs (0.6 N•m)
14 AWG to 10 AWG (2.5 mm² to 4.0 mm²)
(single wire, solid or stranded)
• CCI wiring: 5 in-lbs (0.6 N•m)
20 AWG to 10 AWG (0.5 mm² to 4.0 mm²)
(single wire, solid or stranded) 20 AWG to 16 AWG (0.5 mm² to 1.5 mm²) (two wires, solid or stranded)
• QS Link: 5 in-lbs (0.6 N•m)
Power (terminal 1):
22AWG to 12AWG (0.25mm
2
to 2.5mm2)
(single wire, solid or stranded)
22 AWG to 18 AWG (0.25mm
2
to 1mm2)
(two wires, solid or stranded)
Data (terminals 3 and 4):
1 pair, twisted and shielded,
22 AWG to 12 AWG (0.25mm
2
to 2.5mm2)
(single wire, solid or stranded)
22 AWG to 18 AWG (0.25mm
2
to 1mm2)
(two wires, solid or stranded)
This section describes the default functionality when
the unit is first installed.
Manual Override Contact Closure Input (CCI)
• When the CCI is open, the unit will enter Manual Override Mode, which will turn on all loads to their manual override level and disable control of local zones and QS devices.
• When the CCI is closed or jumpered, zones will return to the settings or levels they were at prior to entering manual override mode. Note: Unit will process any sensor events received while in manual override mode after it exits manual override mode.
Normal Mode Operation
• By default each zone is set to an Auto Detect load type with ON and OFF control only. Each zone will turn load ON or OFF until it is configured via unit programming.
• Zone and raise/lower buttons on the unit can be used to:
– Turn loads ON and OFF. – Dim loads up and down.
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
®
HomeWorks LQSE-4A5-120-D PRO LED+ Phase Adaptive Power Module
6
3691126b 6 05.08.20
Mounting
• Unit is 12 DIN modules wide, 8.5 in (216 mm).
• Mount in a Lutron DIN panel (see Lutron Specification Submittal 3691055 or 3691106 at www.lutron.com) or in an IP20 (minimum) or NEMA Type 1 (minimum) enclosure with an integrated DIN rail (please refer to Lutron P/N 048466 at www.lutron.com).
• Mount unit in orientation shown.
• Mount to DIN rail by pressing unit onto rail with clips locked. To remove from rail, unlock clips using a sc rewd rive r.
• Mount in an accessible and serviceable location.
• Unit generates heat, maximum 75 BTUs / Hour.
• Mount unit such that all the conditions below are met:
– Room ambient temperature is between 32 ºF and 86 ºF
(0 ºC and 30 ºC)
– Temperature inside mounting panel, within 0.8 in
(20 mm) of unit, is between 32 ºF and 122 ºF (0 ºC and 50 ºC)
– Calibration point maximum: 158 ºF (70 ºC)
Locked
4 mounting clips on unit
Unlocked
Mechanical Dimensions
Left Side View
Calibration
point
3.54 in
(90 mm)
2.17 in
(55 mm)
2.75 in
(70 mm)
2.99 in
(76 mm)
Front View
8.50 in
(216 mm)
3.54 in
(90 mm)
SPECIFICATION SUBMITTAL Page
Job Name:
Model Numbers:
Job Number:
®
HomeWorks LQSE-4A5-120-D PRO LED+ Phase Adaptive Power Module
7
3691126b 7 05.08.20
Overview of Wiring Terminals
Contact
Closure
Input (CCI)
CCI
COM
MUX
QS
Link
MUX
COM
L
L
Mains
Input
N N N N N
Neutrals
Mains Wiring
Load
DL1 DL2 DL3 DL4
Zone
Zone
1
3
Zone
Zone
2
4
Phase Adaptive Outputs
SPECIFICATION SUBMITTAL Page
Job Name:
Model Numbers:
Job Number:
®
HomeWorks LQSE-4A5-120-D PRO LED+ Phase Adaptive Power Module
8
3691126b 8 05.08.20
Verify Wiring
• Apply power to loads to identify any load or wiring faults prior to connecting loads to unit.
• Reference the Lutron panel spec sheets 3691055 and 3691106 at www.lutron.com for alternate wiring verification method.
MUX
CCI
MUX
COM
COM
• To verify wiring:
1. Turn off power.
2. Connect loads directly to Line / Hot to bypass the unit and protect it from wiring faults.
3. Apply power, ensure the desired loads are powered and properly wired.
4. Turn off power and connect loads to DL terminals on unit for normal operation.
120 V~
Earth
Line / Hot
Neutral
L
L
N N N N N
DL1 DL2 DL3 DL4
SPECIFICATION SUBMITTAL Page
Job Name:
Model Numbers:
Job Number:
®
HomeWorks LQSE-4A5-120-D PRO LED+ Phase Adaptive Power Module
9
3691126b 9 05.08.20
Mains Voltage Wiring
Zone 1 Example
L L
N N N N N
Earth
Distribution
Panel
Line / Hot
(120 V~)
Neutral
Wiring from Distribution to Adaptive Power Module
• Turn off all circuit breakers or isolators feeding the Adaptive Power Module at distribution panel.
• Run line / hot, neutral, and earth (
) wires from a
120 V~ 50/60 Hz feed to the power module.
• Run a separate neutral for each load circuit.
DL1 DL2 DL3 DL4
Dim Hot
Neutral
Load
Mains Wiring and NECR Class 2 Separation
• Follow appropriate local and national codes to ensure proper separation.
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
®
HomeWorks LQSE-4A5-120-D PRO LED+ Phase Adaptive Power Module
10
3691126b 10 05.08.20
Wiring: Contact Closure Input
NECR Class 2 Contact Closure Input
• Contact Closure Input (CCI) wiring is NEC
® Class 2.
• Follow all applicable national and local codes for proper circuit separation and protection.
• Turn off all breakers or isolators feeding the unit at distribution panel before servicing unit.
• The CCI is a local control only and cannot control other units over the QS link. A maximum of 32 units may be connected in parallel to a Manual Override device if the event is intended to affect multiple devices.
CCI
Common
• When in manual override mode, all zone outputs will be at their programmed emergency light level
Note: Shown with pre-installed jumper.
(configurable for each zone, default is 100%). All sensors and controls are locked out.
• Contact closure input is normally closed (NC). The
CCI
COM
unit is shipped with a jumper pre-installed.
Note: The unit will default to Manual Override Mode if the CCI is left open. If no Manual Override Contact Closure Input is required, leave the wire jumper in the CCI terminals.
Job Name:
Job Number:
SPECIFICATION SUBMITTAL Page
Model Numbers:
®
HomeWorks LQSE-4A5-120-D PRO LED+ Phase Adaptive Power Module
11
3691126b 11 05.08.20
Wiring: QS Link
QS Link NECR Class 2 Wiring
• Follow all applicable national and local codes for proper circuit separation and protection.
• Link communicates using NECR Class2 wiring.
• Wiring may be daisy chained or T-tapped.
• Do NOT connect terminal 2.
QS Link Wiring Options
MUX
MUX
COM
(1) COM
(2) Do Not Connect Teminal 2
(3) MUX
(4) MUX
Daisy-Chain Wiring Example
T-Tap Wiring Example
Palladiom Keypads
1
Control
Link
Length
Less than 500ft (153m)
500ft (153m) to 2000ft (610m)
Palladiom Keypads
Wire Gauge (for terminals)
Power (terminals 1 and 2): 1 pair 18AWG (1.0mm
Data (terminals 3 and 4): 1 pair 22AWG (0.5mm
2
)
2
), twisted
and shielded*
Power (terminals 1 and 2): 1 pair 12AWG (4.0mm
Data (terminals 3 and 4): 1 pair 22AWG (0.5mm
2
)
2
), twisted
and shielded*
QSE-CI-DMX
Available from
Lutron
in one cable:
GRX-CBL-346S
GRX-CBL-46L
1
Unit does not consume or supply PDUs on
the QS link. Do not connect the 24 V- wire to unit.
Note: 24 V- wire must bypass the unit if other devices on the link consume PDUs.
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
QSE-CI-DMX
Model Numbers:
)Lutron, Lutron, GR AFIK Eye, Hi-lume, H omeWorks, Palladiom, RTIS S Equipped, RTISS-TE, and Sivoia are trademarks or registered trad emarks of Lutro n Electronics Co., Inc. in the US and/or oth er countries.
All prod uct names, logos, and brands a re property of their respective owners.