Lutron lighting control Installation Manual

Simple, scalable, wireless
lighting control
Flexible control every step of the way
A simple wireless lighting control solution for new and existing commercial buildings.
Benefits
Vive wireless hub
DESIGN
The flexibility you need to design your building
Build your system from a full suite of products —
specify a simple occupancy sensor solution, or design a fully integrated lighting management system using the same suite of products
Easily match controls to the fixture package — switching, DALI, 0 –10V, Phase control, or any combination
Expand the system at any time — add control options, add new areas, easily upgrade software to add new features
INSTALL MAINTAIN
Wireless simplifies installation and reduces callbacks
Less wiring makes installation faster — reduce labour time by up to 70%
Setup is as simple as pushing a button or using your smart device — no manufacturer commissioning
required, further reducing time and labour cost (the Lutron services team is always available if you want some additional support)
Start small and expand at any time — with no new wiring — meet budget requirements and changing space needs
Eliminate callbacks — Lutron’s proven reliability helps you stay within budget and reduces your time on the job
1
Maximise productivity and building performance
Monitor, adjust, and manage your system from any smart device — easily adjust the lighting control
to accommodate building churn, improve occupant comfort, and enhance energy efficiency
Energy savings — lighting uses more electricity than any other building system. Lutron solutions can save up to 60%2 or more of that lighting energy
Minimise down time — wireless controls install quickly to minimise disruption to building occupants
Expand capability — add new controls or upgrade software at any time without replacing the existing system
Simpify integration — using BACnet protocol, connect with other building systems at the time of initial installation or whenever you expand the system
Vive software
The Vive wireless family gives you the right solution now and for years to come
Any budget
Area and sensor controls
Meet latest building regulations and standards
No factory setup required
When you choose Lutron solutions, you
can be confident that the system just works, and it will keep working.
2 | Lutron
For a list of sources please visit lutron.com/references. For a list of sources please visit lutron.com/references.
Lutron | 3
Energy-saving control strategiesScalable solutions — start small and grow
Vive wireless solutions offer a multi-strategy approach that accommodates your budget and performance needs now, and for the future of your building.
1 2 3 4
Combine lighting control strategies to maximise efficiency
What is the savings opportunity?
Lutron solutions can save 60%3 or more lighting energy.
Occupancy/vacancy sensing turns lights on when occupants are in a space and off when they
Occupied: On Vacant: Off
Full On Dim
80%
Max: 100% Max: 80%
Full On Dim
vacate the space.
Daylight harvesting dims electric lights when daylight is available to light the space.
High-end trim sets the maximum light level based on customer requirements in each space.
Personal dimming control gives occupants the ability to adjust the light level.
Potential savings
20 – 60%
Lighting
25 – 60%
Lighting
10 – 30%
Lighting
10 – 20%
Lighting
Single office space
Start by adding control in a single space and expand as budgets and occupant schedules allow.
Single floor
Expand to new areas or an entire floor at any time without reprogramming or replacing existing equipment. By connecting to a Vive wireless hub.
Multiple floors
Duplicate the success of one floor across other floors as your business expands or tenants change. Control can be independent on each floor, or linked via Vive wireless hubs.
Entire building
Vive offers seamless integration to other building management systems through BACnet.
7am: Dim 7pm: Off
Heating Cooling
Full On Dim
Saving
%
60
Before After
Saving
70
%
Scheduling provides pre-programmed changes in light levels based on time of day.
HVAC integration controls heating, ventilation, and air conditioning systems through contact closure, or BACnet protocol.
Load shedding automatically reduces lighting loads during peak electricity usage times.
System Optimisation Service from Lutron identifies important lighting control adjustments to save additional energy and create a more productive work environment on an ongoing basis.
10 – 20%
Lighting
5 – 15%
HVAC
30 – 50%
Peak Period
Variable
4 | Lutron Lutron | 5
For a list of sources please visit lutron.com/references.
Transform existing buildings with wireless lighting controls
Wireless controls and sensors
Simple-to-use software
Remotes
Occupancy and daylight sensors
Centralised control
and integration
Vive wireless hub
Lighting control modules
6 | Lutron
Demand
response
Wired/ Ethernet
BACnet
integration
API
integration
Communication protocols
Communicate via RF to control components
Vive software
Communicate via WiFi to smart devices
Communicate via wired Ethernet to Vive hub
Lutron | 7
Solutions for every space and budget
The right control in the right space
The Vive product family lets you personalise control to each space in your building without locking you into more or less control than you need
DESIGN
Simple switching
Classroom
Occupancy sensors control all lights together by switching lights on and off in response to room occupancy.
Simple switching
Remote | PowPak | Occupancy sensor
Area dimming and sensing
Open office
Dim a group of lights together while also providing manual control. Save additional energy with daylight harvesting.
Area dimming and sensing
Dimming module | Occupancy sensor | Daylight sensor | Pico remote
8 | Lutron
Lutron | 9
Flexible installation
INSTALL
Wireless Remote
Mount anywhere
No wires
Put it where it is most accessible
10 | Lutron
Wireless Load Control
Junction box or marshalling box
Easy Retrofit
PowPak modules mount on a standard junction box or marshalling box in the ceiling to control a group of lights
Wireless Daylight
Sensor
Ceiling mount
No wires
10 year battery life
Wireless Occupancy Sensor
Corner/Ceiling/wall mount
No wires
Easily mount it anywhere
Vive Wireless Hub
Add a Vive Hub to any job for simple
set-up, control and monitoring
Each hub wirelessly communicates with
devices in a 929 m2 (10,000 sq. ft.) area
Lutron | 11
Easy system programming
Simple setup and programming options with the Vive wireless hub
Mobile phone setup
INSTALL
For systems without a Vive wireless hub
Using Vive software on any smart device you can wirelessly con­nect system controls and program system settings — no ladder required. Lutron’s patent pending RF signal strength detection automatically finds nearby devices, making job setup faster.
Press and hold on
1
wireless device
Automatic device identification
2
Lutron patent-pending technology automatically finds and sorts the wireless devices closest to the control.
Push-button set up
Use simple button-press programming to select and associate wireless devices — it’s as easy as setting a station on your car radio.
PowPak
Press and hold for 6 seconds
Occupancy sensor
Press and hold for 6 seconds
It works! Sensor now talks
to the wireless dimmer
12 | Lutron Lutron | 13
Save energy and improve building performance
DATA: Energy savings and space utilization
Load Shed
Schedules
Scene Control
Light Control
MAINTAIN
Alerts
Quickly view and display energy-usage information to drive decision making and demonstrate savings.
Easily set lighting reduction levels that automatically respond during peak electricity usage times.
Use a 365 day calendar to auto­matically adjust lights based on time of day, including single day and holiday events.
Create and configure scenes to control individual devices, areas, or groups of areas on demand.
Directly adjust the light levels remotely from any smart device. Easily respond to occupant requests without needing to be in the physical space.
View proactive alerts that show issues such as low batteries or inactive devices to help improve building maintenance efficiency.
Seamlessly integrate with your building system
The BACnet/IP protocol is the primary means of integration. BACnet is embedded or native in the Vive wireless hub, which means no external interfaces or gateways are required in order to communicate with other systems.
API integration, native on the Vive hub, enables integration with third party devices, systems, and software. RESTful APIs are available over the ethernet.
Building/Energy Management Systems (BMS/EMS)
HVAC
14 | Lutron Lutron | 15
Energy Dashboards and Analytics Packages
API
ITAudio & Video
A smart building is now simple
Vive Vue software
MAINTAIN
Vive Vue software provides the ability to link multiple Vive hubs together in one software interface. Built with the simple, scalable, wireless building blocks of the Vive Wireless system, Vive Vue software delivers the advanced intelligence necessary for today’s smart buildings and the IoT. A smart building is now easier than ever to achieve.
Intuitive control
View status, control lights, and optimise your building quickly and efficiently with a graphical floorplan.
Optimise your space
Improve building layout based on actual occupancy and usage information. With space utilisation reports, you can quickly identify over-used and under-used spaces to improve building efficiency without expanding the building footprint.
Save energy purposefully
Energy reports allow you to view and monitor your energy savings. With trending energy information over time, and easily customisable reports, Vive Vue software helps you demonstrate the energy-saving advantages of wireless lighting control.
16 | Lutron Lutron | 17
Enterprise Vue – Connected campus
Manage data and operations for multiple Lutron lighting and blind control solutions
A single data and management platform for your connected buildings
The system interface delivers a simple, consistent user experience from any PC or tablet
Open, easy integration with BACnet and web APIs leverages the IoT to enhance smart-building performance
MAINTAIN
Enterprise Vue home screen
18 | Lutron Lutron | 19
Lutron security
Lutron reliability
Clear Connect wireless technology
We build security into the product and the process from conception
to installation, and through the lifetime of the system.
Everything we do is backed by Lutron’s first, and guiding, principle — Take Care of the
Customer with Superior Goods and Services. Every product, every system, and every solution is designed, manufactured and tested to work as expected.
Security by Design
When building any new system, Lutron utilises
a dedicated security team to ensure best practices are implemented. Security is built-in. It is not an afterthought or add on.
Examples of security features designed
into Vive include:
1. Isolated wired and wireless architecture which strictly limits the possibility of the Vive Wi-Fi or Clear Connect being used to access the corporate network to gain confidential information
3rd-Party Validation
Security is complicated. Lutron has a dedicated team of
internal experts, but we also leverage external experts to double- and triple-check our work.
1. Multiple external experts engaged during design process
2. 3rd-Party penetration testing to identify and fix potential vulnerabilities before they reach the field
Continuous Monitoring
All Lutron wireless products utilise Lutron patented Clear Connect wireless technology which operates in an uncongested radio frequency band. The result is ultra-reliable communication and smooth dimming performance with no flicker or delay. Other devices will not interfere with the Lutron lighting control system.
Clear Connect
868 MHz: Lutron Clear Connect wireless technology
Lutron devices operate in an uncongested frequency band, providing ultra-reliable operation.
2. A distributed security architecture — each hub has its own unique keys
3. Best practices for securing passwords, including salting and use of SCrypt recommended by the International Standards Organization (ISO)
4. AES 128-bit encryption for network communications
5. HTTPS (TLS 1.2) protocol for securing connections to the hub over the wired network
6. WPA2 technology for securing connections to the hub over the Wi-Fi network
and Improvements
Security is a constantly moving target. Lutron uses
a dedicated security team to continuously monitor the market for potential threats and, when needed, send out security patches to update installed systems.
Ongoing Support
Lutron has the resources you need to answer questions
about security when they arise.
1. IT deployment guides
2. Guidance from our world class 24/7 technical support organisation with IT expertise throughout the product lifecycle
20 | Lutron Lutron | 21
Lutron service and supportLutron technology and tools
XCT sensing technology
Lutron’s occupancy sensing will not leave occupants in the dark and eliminates callbacks
Lutron sensors provide exceptional prevention of false-ons and false-offs
Superior sensitivity — recognises the difference between fine human motion and background noise
Major Motion
Person walking 1 metre (3 feet)
Minor Motion
Movements like extending our arms
Setup the system yourself, or choose the right mix of support services.
Lutron offers a variety of flexible, scalable support options to meet the needs of your project and your budget.
Do it yourself Get a little help Leave the setup to us
Vive is designed to make
installation and setup easy. Instructions are included with the product, and comprehensive, online help is available 24/7.
Simple-to-follow videos and
product guides are just a click away.
If you’re looking for some extra
peace of mind, Lutron Services can be purchased in flexible blocks of time to provide just the right amount of support.
The Services Team can provide
training, walk you through setup for a specific project area, answer any other questions you have, or help finish setup by closing punch-list items.
If you prefer, the Lutron Services
Team can execute the full system setup.
Onsite setup — a Lutron-certified
service technician will perform the complete system setup at your project site.
If you are not sure what kind of support you need, Lutron can help.
Fine Motion
Small movements like flipping pages of a book
No False-on
Lights stay off when room is unoccupied
22 | Lutron Lutron | 23
Contact your local Lutron sales representative to discuss your project, or Lutron Customer Assistance
tel: +44 (0)20 7680 4481 | eatechnicalsupport@lutron.com | lutron.com/help (24/7 Technical Support)
Vive Wireless Application Guide
Wireless energy solutions at an affordable price
by
Break Room | New Construction
ASHRAE 90.1-2010
Control Functionality
Occupant Enters:
Lights do not automatically turn on when an occupant enters the space; lights must be turned on manually. Maximum light level is set to 80%.
When Occupied:
Manual: Occupant uses wall dimmer to set desired light levels for all lights.
Occupant Exits:
All lights automatically turn off 15 minutes after all occupants exit.
Add a Vive wireless hub to enable simple setup and re-zoning, system monitoring, timeclock functionality, and advanced integration.
Symbol Model Number Description Qty
RMJS-8T-DV-B PowPak dimming module with 0-10
V 1
LRF2-VKLB-P-WH
Radio Powr Savr wireless corner-mount vacancy sensor
1
PJ2-3BRL-GWH-L01 Pico wireless 3-button with raise/lower control 1
PICO-WBX-ADAPT Pico wallbox adapter 1
Code Notes: For break rooms with daylight, include a 0-10 V dimming module per zone and a daylight sensor. Want to add a Vive wireless hub for more features? Go to lutron.com/vive for complete compatibility and design details. This solution requires 0-10 V enabled ballasts and drivers by others.
Line-voltage wiring
Clear Connect RF Communication
Low-voltage
wiring
© 03/2017 Lutron Electronics Co., Inc.
I
P/N 368-4600 REV A
This solution requires 0-10 V enabled ballasts and drivers by others.
© 03/2017 Lutron Electronics Co., Inc.
by
Conference Room | New Construction
ASHRAE 90.1-2010
Control Functionality
Occupant Enters:
Lights do not automatically turn on when an occupant enters the space; lights must be turned on manually. Maximum light level is set to 80%.
When Occupied:
Automatic: Overhead lights dim/brighten based on daylight availability. There are two perimeter daylight zones. Manual: Occupant uses wall dimmer to set desired light levels for all lights.
Occupant Exits:
All lights automatically turn off 15 minutes after all occupants exit.
Add a Vive wireless hub to enable simple setup and re-zoning, system monitoring, timeclock
functionality, and advanced integration.
Symbol Model Number Description Qty
RMJS-8T-DV-B PowPak dimming module with 0-10
V 2
LRF2-DCRB-WH Radio Powr Savr wireless daylight sensor 1
LRF2-VKLB-P-WH
Radio Powr Savr wireless corner-mount vacancy sensor
1
PJ2-3BRL-GWH-L01 Pico wireless 3-button with raise/lower control 2
PICO-WBX-ADAPT Pico wallbox adapter 2
Line-voltage wiring
Clear Connect RF Communication
DZ 1 & DZ 2 = Daylight Zones
Low-voltage wiring
DZ 1 DZ 1
DZ 2 DZ 2DZ 2
DZ 1
For non-daylight conference rooms the lighting can be connected to a single 0-10 V dimming module. Want to add a Vive wireless hub for more features? Go to lutron.com/vive for complete compatibility and design details. This solution requires 0-10 V enabled ballasts and drivers by others.
© 03/2017 Lutron Electronics Co., Inc.
I
P/N 368-4602 REV A
by
Egress Corridor | New Construction
ASHRAE 90.1-2010
Control Functionality
Occupant Enters:
All lights automatically turn on to maximum light level. Maximum light level is set to 80%.
When Occupied:
Manual: Occupant uses wall switch to turn on, adjust, or dim all lights to low end. Manual control cannot fully shut off the lights. Minimum light level is set to 10%.
Occupant Exits:
All lights automatically go to minimum light level 15 minutes after all occupants exit.
Emergency Mode:
Lighting connected to emergency power turns on to full output.
Symbol Model Number Description Qty
RMJS-8T-DV-B PowPak dimming module with 0-10
V 1
LRF2-OHLB-P-WH
Radio Powr Savr wireless hallway occupancy sensor
1
PJ2-3BRL-GWH-L01 Pico wireless 3-button with raise/lower control 2
PICO-WBX-ADAPT Pico wallbox adapter 2
Clear Connect RF Communication
Line-voltage wiring
Low-voltage wiring
To emergency power
Code Notes: Verify that the egress fi xtures go to full output upon loss of control signal. For projects that require UL 924 compliance, provide an automatic load control relay (ALCR) per load controller connected to emergency fi xtures. Add a daylight sensor for corridors with daylight zones. Want to add a Vive wireless hub for more features? Go to lutron.com/vive for complete compatibility and design details. This solution requires 0-10 V enabled ballasts and drivers by others.
© 03/2017 Lutron Electronics Co., Inc.
I
P/N 368-4603 REV A
by
Open Offi ce | New Construction
ASHRAE 90.1-2010
Control Functionality
Occupant Enters:
All lights automatically turn on to 50% light level. Occupant turns on lights to maximum level manually. Maximum light level is set to 80%. Controlled receptacles automatically regain power when occupant enters.
When Occupied:
Automatic: Overhead lights dim/brighten based on daylight availability. There is one perimeter daylight zone. Manual: Occupant uses wall dimmers to set desired light levels for all lights.
Occupant Exits:
All lights automatically turn off 15 minutes after all occupants exit. 50% of all receptacles automatically turn off 15 minutes after all occupants exit.
Add a Vive wireless hub to enable simple setup and re-zoning, system monitoring, timeclock functionality, and advanced integration.
Symbol Model Number Description Qty
RMJS-8T-DV-B PowPak dimming module with 0-10
V 2
RMJS-20R-DV-B 20
A PowPak relay module 1
LRF2-DCRB-WH Radio Powr Savr wireless daylight sensor 1
LRF2-OCR2B-P-WH
Radio Powr Savr wireless ceiling-mount
occupancy sensor
4
PJ2-3BRL-GWH-L01 Pico wireless 3-button with raise/lower control 1
PICO-WBX-ADAPT Pico wallbox adapter 1
Line-voltage wiring
Clear Connect RF Communication
DZ 1 = Daylight Zone
Low-voltage wiring
DZ 1 DZ 1 DZ 1 DZ 1
Code Notes: For non-daylight open offi ces, all general lighting can be connected to a single 0-10 V dimming module. Want to add a Vive wireless hub for more features? Go to lutron.com/vive for complete compatibility and design details. This solution requires 0-10 V enabled ballasts and drivers by others.
© 03/2017 Lutron Electronics Co., Inc.
I
P/N 368-4604 REV A
The benefits: Simple to design
Design tools
Access to tools and resources at your fingertips.
Exclusive access and quick answers keep your project moving.
Designer+ for Vive
Lutron Designer+ for Vive is an intuitive, easy-to-use software tool that allows you to design a Lutron Vive lighting control system with visual “drag and drop” layout and connections. It also allows you to generate comprehensive system design documentation, including bills of materials, one-line diagrams, and sequence of operations. For free access please contact myLutronsupport@lutron.com.
Vive videos
Get access to Lutron Vive videos 24/7. Step-by-step setup, installation, and programming help whenever you need it.
YouTube — Lutron Vive Wireless
Create flexible designs
Use these simple documents to specify and design Vive wireless systems for common applications.
Application guide for typical installations
Simple room based graphical layouts demonstrate how to apply Vive components to different spaces in your building
Available online at lutron.com/vive-europe
Classroom | New Construction
ASHRAE 90.1-2010
DZ 1 DZ 1 DZ 1
2 2 2
1
1
2 2 2
1
2 2 2
21
Symbol Model Number Description Qty
RMJS-8T-DV-B PowPak dimming module with 0-10 V 3
LRF2-DCRB-WH Radio Powr Savr wireless daylight sensor 1
LRF2-VKLB-P-WH
PJ2-3BRL-GWH-L01 Pico wireless 3-button with raise/lower control 2
PICO-WBX-ADAPT Pico wallbox adapter 2
Control Functionality
Occupant Enters:
Lights do not automatically turn on when an occupant enters the space; lights must be turned on manually. Maximum light level is set to 80%.
When Occupied:
Automatic: Overhead lights dim/brighten based on daylight availability. There is one perimeter daylight zone. Manual: Occupant uses wall dimmers to set desired light levels for both general and white-board lights.
Occupant Exits:
All lights automatically turn off 15 minutes after all occupants exit.
P/N 368-4601 REV A
I
Add a Vive wireless hub to enable simple setup and re-zoning, system monitoring, timeclock functionality, and advanced integration.
Code Notes: For non-daylight classrooms, all general lighting can be connected to a single 0-10 V dimming module. Receptacle Control is required for Shop and Laboratory classrooms. Want to add a Vive wireless hub for more features? Go to lutron.com/vive for complete compatibility and design details.
Line-voltage wiring
Low-voltage wiring
Clear Connect RF Communication
DZ 1 = Daylight Zone
Radio Powr Savr wireless corner-mount vacancy sensor
by
Vive wireless specification typicals
1
Specifying wireless lighting control reduces design time and allows flexibility for changes during the project without the need to redesign. Vive Wireless Specification Typicals allow for quick and easy design of many applications. Simply copy and paste the typicals into drawing packages for complete design, layout, and BOM information.
24 | Lutron Lutron | 25
Available online at lutron.com/vive-europe
Vive training
Visit Lutron.com/LCIOnline —Sign up for free, online training modules with practice exercises that walk you through the Vive system.
For a list of sources please visit lutron.com/references.
Vive Wireless hub
Vive wireless hub
Dimensions
W: 165 mm (6.5") H: 38 mm (1.5") D: 71 mm (2.8")
Features and benefits
Communicates with controls on a floor using Lutron wireless Clear Connect technology (range radius of 22 m [71 ft])
Distributed system architecture
- Pico remote controls and sensors communicate directly with the load devices they control and must be located within 9 m (30 ft) of the device with which they are associated
Supports timeclock events based on both sunrise and sunset or fixed time-of-day
Integrated multi-colour LED provides feedback on what mode the hub is in
Two contact closure Inputs for integration with devices by others
Each hub provides an individual dashboard for its coverage area and allows you to link to other hub dashboards from the mobile application
API integration, native on the Vive hub, to enable integration with third party devices, systems, and software. RESTful APIs are available over the ethernet.
Proactive alerts to inform batteries are low or devices may not be working to ensure system operates as expected.
Scene control allows creating and configuring scenes to control individual devices, or groups of areas on demand and may be activated with the second contact closure input, API integration, or manual activation in the app.
Product options
How it works
All wireless devices to be associated to the Vive wireless hub must be within 22 m (71 ft) of the Vive wireless hub and must be on the same floor as the Vive wireless hub.
Vive Hub
Setup, Monitor and Control
Vive Hub
9 m (30 ft) 9 m (30 ft)
MaximumMaximum
22 m (71 ft)
Maximum
9 m (30 ft)
Maximum
RF coverage
9 m (30 ft)
Maximum
9 m (30 ft)
Maximum
30 m (100 ft)
Conference Room
PowPak Dimming Module
wireless hub
Vive hub power supply
Dimensions
W: 102 mm (4.0") H: 43 mm (1.7") D: 71 mm (2.8")
Vive wireless hub models
Starter (up to 75 devices)
HKS-0-FM Flush mount
Standard (up to 700 devices)
HKS-1-FM Flush mount
HKS-1-SM Surface mount
Premium with BACnet (up to 700 devices)
HKS-2-FM Flush mount
HKS-2-SM Surface mount
Notes:
A minimum distance of 3 m (10 ft) between Vive wireless hubs on the
same floor is required.
A corporate Wi-Fi network can interfere with the Wi-Fi on the Vive wireless hub. Where a corporate Wi-Fi network exists, it is recommended to connect the Vive wireless hub to the corporate network using the Ether net connection on the hub, and disable the hub’s Wi-Fi.
Vive wireless hub must be mounted a minimum of 3 m (10 ft) from a Wi-Fi router or access point.
Range with multiple Vive hubs
22 m (71 ft)
Maximum
30 m (100 ft)
30 m
(100 ft)
22 m (71 ft)
Maximum
Personal Control
Pico Remote Control
Sensors
Radio Powr Savr Occupancy Sensor
Open Office
PowPak
Note: Pico remote controls and sensors must be within 9 m (30 ft) of the load device they are controlling
Radio Powr Savr Daylight Sensor
Lutron | 2726 | Lutron
Load Controllers
PowPak relay module
Dimensions
W: 72 mm (2.89") H: 87 mm (3.44") D: 32 mm (1.25")
How to design and specify
One relay module
For each controlled lighting zone in the space
Control
Select appropriate model based on the size of the connected load
16 A: 3840 W or 6 A Motor
5 A: 1200 W
Contact closure output
For sending occupancy information to third-party equipment such as HVAC systems
Input 220/240 V
Product options
16 A models
RMKS-16R-DV-B
5 A models
PowPak dimming module with DALI control
Dimensions
W: 72 mm (2.89") H: 87 mm (3.44") D: 32 mm (1.25")
How to design and specify
One control module with DALI
For each controlled DALI lighting zone in the space
Control
Select appropriate model based on the number of connected drivers/ballasts
Input 220 – 240 V 50/60 Hz
DALI Link
Guaranteed Supply Current: 8 mA (4-driver/ballast model)
64 mA (32-driver/ballast model)
Maximum Supply Current: 250 mA
DALI-2 Certified
Product options
4-driver/ballast model
RMKS-DAL4-SZ
32-driver/ballast model
PowPaks
PowPak dimming module with 0 –10 V contr ol
Dimensions
W: 72 mm (2.89") H: 87 mm (3.44") D: 32 mm (1.25")
RMKS-5R-DV-B
How to design and specify
One dimming module with 0 –10 V control
For each controlled 0 –10 V lighting zone in the space
Control
8 A: 0 –10 V controlled fixtures and switches compatible
with third-party 0 –10 V fluorescent ballasts, LED drivers, and fixtures
220 – 240 V 8 AX switching and 60 mA of 0 –10 V LED
Input 220 – 240 V
0 –10 V Link
Communicates with up to 60 mA of fixtures
Product options
RMKS-DAL32-SZ
Using PowPak load controllers, switches, and dimmers with marshalling boxes
Marshalling Box
Power (L,N,G) + DALI (D1, D2)
PowPak
Electrical
Closet
8 A models with 0 –10 V control
RMKS-8T-DV-B
Power (L,N,G)
Distribution
Panel
28 | Lutron Lutron | 29
C
C
VAV
VAV
Damper open
Filter
Cooling coil
Supply fan
Damper closed
Load Controllers
PowPak contact closure output module
Dimensions
W: 72 mm (2.89") H: 87 mm (3.44") D: 32 mm (1.25")
How to design and specify
One contact closure output module
For each additional contact closure output you require
Product options
Standard
RMKS-CCO1-24-B Contact closure output
How it works
In response to information received from a Radio Powr Savr occupancy/vacancy sensor, the PowPak contact closure output module communicates room occupancy to the VAV terminal unit. By not heating o rcooling an unoccupied room, the electricity consumed by the HVAC system can be reduced.
In-line dimmer
Dimensions
46 mm (1.8")
W: H: 153 mm (6.0") D: 32 mm (1.25")
How to design and specify
One in-line dimmer
For each controlled phase dimmable LED, incandescent, halogen, or ELV lighting zone in the space.
Control
1 A / 150 W: LED 250 W: Incandescent, halogen, ELV loads
Input 220–240 V~ 50/60 Hz
Product options
In-line dimmer
RMKS-250NE Trailing edge capable, phase dimmable LED,
incandescent, halogen, ELV loads
30 | Lutron Lutron | 31
Occupied Unoccupied
Radio Powr Savr occupancy/vacancy sensor (ceiling mount)
PowPak contact closure output module
Remotes: Pico wireless remotes
Pico wireless remotes
3-button with raise/ lower
2-button with raise/ lower
Dimensions
3-button
2-button
How to design and specify
Select one 2-button Pico wireless remote to add a location with
ON/OFF control
Select one 3-button Pico wireless remote to add a location with
ON/OFF control and one preset
Select one 2-button with raise/lower Pico wireless remote to add a
location with ON/OFF and BRIGHTEN/DIM control
Select one 3-button with raise/lower Pico wireless remote to add a
location with ON/OFF, BRIGHTEN/DIM control and one preset
Note: Spaces with a PowPak relay or dimming module will not have
a local control in the room unless a Pico is added
Product options
2-button remotes
PK2-2BRL-TXX-L01 2-button with raise/lower
wireless remote
PK2-2B-TXX-L01 2-button wireless remote
How it works
No wires—put it where it’s most accessible
Pedestal mount for tabletop use
Surface mount anywhere with a wallplate
10-year battery life
Pico remote
W: 33 mm (1.28") H: 66 mm (2.60") D: 8 mm (0.33")
3-button remotes
PK2-3BRL-TXX-L01 3-button with raise/lower
wireless remote
PK2-3B-TXX-L01 3-button wireless remote
Pico wall mounted (in a wallplate) — Add a new point of control anywhere with absolutely no wires
Dim lights to reduce glare onscreen
Raise lights for readingvisibility
32 | Lutron Lutron | 33
(XX in the model number represents colour/finish code)
Remotes: Pico accessories
Pico wireless remotes
4-button 2-group control
Dimensions
W:
33 mm (1.28")
H: 66 mm (2.60") D: 8 mm (0.33")
4-button zone control
4-button scene control
How to design and specify
The Pico wireless remote is a flexible and easy-to-use device that
allows the user to control Lutron wireless load-control devices from anywhere in the space. This battery-operated control requires no external power or communication wiring.
Product options
4-button remotes
PK2-4B-TXX-L21P 2-group control
PK2-4B-TXX-L01 Zone control
PK2-4B-TXX-L31 Scene control
Custom-engraved models for Zone control keypads (-L01, -S01)
and Scene control keypads (-L31, -S31) are available but require a different set of button marking codes when ordering
Note: 2-Group (-L21, -S21, -LS21) and 4-Group Toggle (-L41)
controls are not offered with the custom engraving option).
Tabletop accessories
How to design and specify
Select one Pico pedestal for each tabletop location based on the
number of Pico remotes at each location
Product options
Tabletop accessories
L-PED1-XX pedestal for one Pico remote
L-PED2-XX pedestal for two Pico remotes
L-PED3-XX pedestal for three Pico remotes
How to design and specify
Select one Pico wallbox adapter for each Pico that you
would like wall mounted with a wallplate
Pico remote
Standard
Button Marking Codes
Zone Control
Lights -L01 -EL1
Blinds -S01 -ES1
Scene Control
Lights -L31 -EL2
Blinds -S31 -ES2
Engraving
Custom
Engraving
Wall-mount accessories
Pico wallplate adapter and wallplate
Dimensions
W:
89 mm (3.50")
H: 89 mm (3.50") D: 10 mm (0.38")
Product options
Wall-mount accessories
LPFP‑S1‑T X X International Pico
1 column wallplate
LPFP‑ S2‑T X X International Pico 2 column wallplate
Lutron | 3534 | Lutron
4.6m (15 ft)
4.6m (15 ft)
3.7 m (12 ft)
3.7 m (12 ft)
2.7 m (9 ft)
2.7 m (9 ft)
1.8 m (6 ft)
1.8 m (6 ft)
0.9m (3 ft)
0 m
(0 ft)
0.9 m (3 ft)
Ceiling
Floor
2.4m (8 ft) Ceiling
heigh
t
Sensors: Ceiling occupancy/vacancy sensors
Wireless occupancy/ vacancy sensors
Dimensions
W: 91 mm (3.57") H: 91 mm (3.57") D: 29 mm (1.13")
How to design and specify
A single occupancy sensor can communicate to all control
devices in the room
Use in small rooms or areas with medium to high partitions
For 2.4 m (8 ft) ceilings: 44.9 m2 (484 ft2)
For 3.7 m (12 ft) ceilings: 62.4 m2 (676 ft2)
Settings adjustable to change behaviour including occupancy
to vacancy sensing, occupied and unoccupied levels
Timeout options include: 30 min, 15 min (default), 5 min
Product options
Ceiling-mount sensors
LRF3-OCR2B-P-WH Occupancy/vacancy
Sensor coverage diagrams
Ceiling mount, 360°
Floor view
Ceiling
2.4m (8 ft) Ceiling
heigh
t
Floor
4.6m
3.7 m
2.7 m
1.8 m
0.9m
0 m
(15 ft)
Top view
(12 ft)
(9 ft)
(6 ft)
(3 ft)
(0 ft)
0.9 m (3 ft)
1.8 m (6 ft)
2.7 m (9 ft)
3.7 m (12 ft)
4.6m (15 ft)
Coverage varies by ceiling height
Key:
Minor motion
Major motion
Sensor
Occupant
2.7 m (9 ft)
1.8 m (6 ft)
0.9m (3 ft)
0 m
(0 ft)
0.9m (3 ft)
1.8 m (6 ft)
2.7 m (9 ft)
Ceiling-mount sensor coverage chart (for sensor mounted in centre of room)
Radius of coverage at floor
Ceiling height
2.4 m (8 ft)
2.7 m (9 ft)
3.0 m (10 ft)
Maximum room dimensions for complete floor coverage
5.5 x 5.5 m (18 x 18 ft) 30.2 m2 (324 ft2) 4.0 m (13 ft)
6.1 x 6.1 m (20 x 20 ft) 37.2 m2 (400 ft2) 4.4 m (14.5 ft)
6.7 x 6.7 m (22 x 22 ft) 44.9 m2 (484 ft2) 4.9 m (16 ft)
Sensors
3.7 m (12 ft)**
7.9 x 7.9 m (26 x 26 ft) 62.4 m2 (676 ft2) 5.8 m (19 ft)
* Sensor mounting shown at 2.1 m (7 ft). Mounting height should be between 1.6 and 2.4 m (6 and 8 ft). ** 3.7 m (12 ft) is the maximum mounting height allowed.
36 | Lutron Lutron | 37
0 m (0 ft)
15.2 m (50 ft)
18.3 m (60 ft)
7.6 m (25 ft)
4.6 m (15 ft)
4.6 m (15 ft)
0 m (0 ft)
7.6 m (25 ft)
0 m
(0 ft)
15.2 m (50 ft)
15.2 m (50 ft)
10.7 m (35 ft)
0 m (0 ft)
10.7 m (35 ft)
Sensors: Wall-/Hall-/Corner-mount occupancy/vacancy sensors
Radio Powr Savr Wireless sensors
Dimensions
W: 46 mm (1.8") H: 110 mm (4.35") D: 34 mm (1.3 5")
How to design and specify
A single occupancy sensor can communicate to all
control devices in the room
Product options
Wall-mount sensors
Use in large open rooms with few tall obstructions
Coverage: 278.7 m2 (3,000 ft2)
LRF3-OWLB-P-WH Occupancy/vacancy
Corner-mount sensors
Use in medium to large open rooms with few tall obstructions
Coverage: 232 m2 (2,500 ft2)
LRF3-OKLB-P-WH Occupancy/vacancy
Sensor coverage diagrams
Wall mount*, 180°
139.4 m2 (1,500 ft2)—minor motion
278.7 m2 (3,000 ft2)—major motion
Top view
Corner mount*, 90°
113.8 m2 (1,225 ft2)—minor motion
232.3 m2 (2,500 ft2)—major motion
Top view
Key:
Minor motion
Major motion
Flexible armature mounting kit
Dimensions
W: 92 mm (3.62") H: 55 mm (2.18")
Hallway sensors
For a 1.82 m (6 ft) wide hallway: 15.24 m (50 ft) coverage
For a 3.0 m (10 ft) wide hallway: 45.72 m (150 ft) coverage
LRF3-OHLB-P-WH Occupancy/vacancy
Hallway*, long narrow field of view
Coverage varies by hallway width and length
Top view
3.0 m (10 ft)
1.5 m (5 ft)
0 m (0 ft)
1.5 m (5 ft)
3.0 m
(10 ft)
0 m (0 ft)
Hallway sensor maximum recommended length chart
(sensor centered within hallway)
Width of hallway Length of hallway
1.8 m (6 ft) or less 15.2 m (50 ft)
2.4 m (8 ft) 30.5 m (100 ft)
45.7 m (150 ft)
Sensors
3.0 m (10 ft) or more 45.7 m (150 ft)
* Sensor mounting shown at 2.1 m (7 ft). Mounting height should be between 1.6 and 2.4 m (6 and 8 ft). ** 3.7 m (12 ft) is the maximum mounting height allowed.
Lutron | 3938 | Lutron
Location for average size areas
Arrow points towards the area viewed by the sensor
(towards windows).
Location for narrow areas (corridors, private ofces)
Arrow points towards the area viewed by the sensor (away from window)
H
1-2 H
Bottom of sensor
H = Effective Window Height
3 ft (1 m)
Location for average size areas
Arrow points towards the area viewed by the sensor
(towards windows).
Sensors: Daylight sensors
Wireless daylight sensors
Dimensions
W: 41 m m (1.6") H: 41 mm (1.6") D: 17 mm (0.7")
How to design and specify
A single daylight sensor is capable of controlling:
- All PowPak switching zones
- All PowPak dimming modules with DALI or 0 –10 V control
Product options
Daylight sensor
LRF3-DCRB-WH Daylight sensor
* Sensor mounting shown at 7 ft (2.1 m). Mounting height should be
between 6 and 8 ft (1.6 and 2.4 m).
** 12 ft (3.7 m) is the maximum mounting height allowed.
Sensor coverage diagrams
Location for average size areas
Arrow points towards the area viewed by the sensor (towards windows).
Bottom of sensor
1-2 H
H
1 m (3 ft)
H = Effective Window Height
Bottom of sensor
Sensors
Location for narrow areas (corridors, private offices)
Arrow points towards the area viewed by the sensor (away from window).
40 | Lutron Lutron | 41
Lutron service solutions
Setup support services
4- & 8-Hour onsite blocks Additional setup support services
Available setup support services
Blocks of setup support time
Lutron Services Representatives can support the installation team
in setting up the system
Utilise the technician’s time in the way that best suits your needs:
training, punch list items, or complete programming independently
Mix and match onsite blocks of time and use them when you
need them during the construction timeline
Choose the amount of time you need
Product options
Blocks of setup support time
LSC-OS-PROG8-SP 8 hours of onsite setup support
LSC-OS-PROG4-SP 4 hours of onsite setup support
Additional setup support services
available with blocks and startup
Full-scope startup
Onsite Remote
Available startup services
Onsite full-scope startup
Lutron Service Representative onsite to ensure proper system
startup and configuration
Train facilities staff to best utilise and maintain the lighting
control assets
Reduce risk and keep your Installation team small by having
Lutron do the setup for you.
Includes a Commercial System Limited Warranty
Onsite startup enhancements available
Product options
Setup service models
Full scope startup
LSC-OS-SU-VIVE Onsite full-scope startup
Startup enhancements (Available with onsite full-scope startup)
LSC-PREWIRE Prewire visit
LSC-TRAINING Customer-site solution training
LSC-AF-VISIT Onsite scene and level tuning
LSC-WALK Onsite performance—
verification walk-through
LSC-AH-SU Startup performed at night or weekends
(weekend work available in certain locations)
LSC-SENS-LT Sensor layout & tuning
LSC-SPV-DOC System performance—
verification documentation
Service Solutions
42 | Lutron Lutron | 43
Lutron service solutions Vive Warranty & Technology Support
Operational services
Solution training System optimisation Onsite reconfiguration
Available Operational Services
Support from Lutron to maximise system potential
Reprogram the system as space needs change over time
Support retro-commissioning requirements
Pre-purchase with the system to capture costs in capital budget
Product options
Operational service models
Operational services
LSC-TRAINING Customer-site solution training
LSC-SYSOPT System optimisation service
LSC-OS-PROG8-EN 8 hours of onsite reconfiguration support
LSC-OS-PROG4-EN 4 hours of onsite reconfiguration support
Onsite services are also available for purchase after the system is in operation at hourly, half-day and full-day rates; contact Lutron at lscwarranty@lutron.com for more information.
Commercial System
Limited Warranty
The commercial system limited warranty offers 5 years of parts coverage, 2 years of first-available onsite/remote response time for system issues, and 24/7 technical support. Warranty included
with onsite full-scope startup & available with remote full-scope startup
Product options
Vive Limited Warranty
LSC-B2 Commercial System
2-Year Limited
Technology Support Plans (TSPs)
All Lutron Technology Support Plans provide 100% parts
and diagnostic labour coverage for up to 10 years. Optional response-time guarantees and preventive maintenance visits enable the coverage to be customized to meet the facility’s needs. TSPs are available for any Vive system; a warranty audit visit will be included with the purchase of a TSP when full-scope startup is not purchased.
Product options
Vive Technology Support Plans
LSC-SILV-IW Silver Level Technology
Support Plan
LSC-GOLD-IW Gold Level Technology
Support Plan
LSC-PLAT-IW Platinum Level Technology
Support Plan
LSC-WARR-AUD Warranty Audit Visit
Note: For detailed warranty and technology support plan descriptions see lutron.com/services
Vive Warranty information
Vive wireless solutions are all covered by a 5-year parts warranty with registration of the product. Additional technology support options are available to meet your project needs. See the options below.
Support Options Silver (TSP) Gold (TSP) Platinum (TSP)
Duration up to 10 years of coverage 100% Replacement Parts (5 yrs) Diagnostic Labour — First Available Response (2 yrs) Diagnostic Labour — 72-Hour Response Diagnostic Labour — 24-Hour Response Annual Preventive Maintenance Visit
Commercial System
Limited Warranty
Service Solutions
44 | Lutron Lutron | 45
Ordering Information
Model Number Description
Vive wireless hub
HKS‑0‑FM Starter Vive wireless hub, flush mount
HKS ‑1‑ FM Standard Vive wireless hub, flush mount
HKS ‑1‑ SM Standard Vive wireless hub, surface mount
HKS‑2‑FM Premium Vive wireless hub, flush mount
HKS‑2‑SM Premium Vive wireless hub, surface mount
H‑MOUNT‑SM Surface Mounting kit for hub
H‑MOUNT‑FM Flush mounting kit for hub
VIVE‑VUE Vive Vue license (1 per hub)
PowPak relay module
RMKS‑5R‑DV‑B 5 A relay
Model Number Description
Pico wireless remotes
PK2‑ 2BRL‑T X X‑L01 2-button with raise/lower
PK 2‑2B‑TXX‑ L01 2-button
PK2‑ 3 B R L‑T X X‑ L 01 3-button with raise/lower
PK 2‑3B ‑T X X‑L 01 3-button
PK 2‑4B ‑T X X‑L 21 4-button with 2 group control
PK 2‑4B ‑T X X‑L 01 4-button with zone control
PK 2‑4B ‑T X X‑L 31 4-button with scene control
(XX in the model number represents colour/finish code)
Pico accessories
L‑PED 1‑X X Pico wireless remote single pedestal
RMKS‑16R‑DV‑B 16 A relay
PowPak dimming module with 0 –10 V control
RMKS‑8T‑DV‑B Controls up to 30, 0 –10 V controlled fixtures
PowPak dimming module with DALI control
RMKS‑DAL4‑SZ Controls up to 4 DALI fixtures
RMKS‑DAL32‑SZ Controls up to 32 DALI fixtures
PowPak contact closure output module
RMKS‑CCO1‑24‑B One contact closure output
In-line dimmer
L‑PED 2‑X X Pico wireless remote double pedestal
L‑PED 3 ‑X X Pico wireless remote triple pedestal
(XX in the model number represents colour/finish code)
Pico Colours
Colours
White (AW)
Black (BL)
RMKS‑250NE Control for trailing edge capable, 1A / 150W of phase, dimmable LED, and 250W of incandescent, halogen, ELV loads
46 | Lutron Lutron | 47
Ordering Information
Model Number Description
Radio Powr Savr occupancy/vacancy sensors*
LRF3‑OCR2B‑P‑WH Ceiling-mount, 360° field-of-view, occupancy/vacancy sensor
LRF3‑OWLB‑P‑WH Wall-mount, 180° field-of-view, occupancy/vacancy sensor
LRF3‑OKLB‑P‑WH Corner-mount, 90° field-of-view, occupancy/vacancy sensor
LRF3‑OHLB‑P‑WH Hallway, occupancy/vacancy sensor
Radio Powr Savr daylight sensor
LRF3‑DCRB‑WH Ceiling-mount daylight sensor
Wallplates*
LPFP‑ S1‑TXX Pico 1 column wallplate
LPFP‑ S1‑TXX Pico 2 column wallplate
Model number Description
Vive Startup Services
LSC‑OS‑SU‑VIVE Onsite full-scope startup
LSC‑AH‑SU After hours startup
LSC‑SENS‑LT Sensor layout & tuning
LSC‑SPV‑DOC System performance-verification documentation
Vive Setup Support Services
LSC‑OS‑PROG8‑SP Onsite programming — 8-hour block
LSC‑OS‑PROG4‑SP Onsite programming —4-hour block
LSC‑PREWIRE Prewire visit
LSC‑TRAINING Customer-site solution training
LSC‑AF‑VISIT Onsite scene and level tuning
LSC‑WALK Onsite performance-verification walkthrough
* (XX in the model number represents colour/finish code)
Vive Operational Services
LSC‑TRAINING Customer-site solution training
LSC‑SYSOPT System optimisation service
LSC‑OS‑PROG8‑EN 8 hours of onsite reconfiguration support
LSC‑OS‑PROG4‑EN 4 hours of onsite reconfiguration support
Vive Limited Warranty and Technology Support Plans
LSC‑B2 Commercial system limited warranty
LSC‑SILV‑ IW Silver level technology support plan
LSC‑GOLD‑IW Gold level technology support plan
LSC ‑PL AT‑I W Platinum level technology support plan
LSC‑WARR‑AUD Warranty audit visit
48 | Lutron Lutron | 49
Notes
50 | Lutron
For a list of all Vive wireless solutions product model numbers
lutron.com/vive-europe
EUROPEAN HEADQUARTERS LUTRON EA LTD. 4TH FLOOR, 52 LEADENHALL STREET LONDON EC3A 2EB, UK
EUROPEAN EXPERIENCE CENTRE AND REGISTERED ADDRESS: 4TH FLOOR, 125 FINSBURY PAVEMENT LONDON EC2A 1NQ, UK
FREEPHONE: 0800 282 107 TEL: +44 (0) 207 702 0657 FAX: +44 (0) 207 480 6899 LUTRONLONDON@LUTRON.COM
© 12/2020 Lutron Electronics Co., Inc. I P/N 367-2597/EA REV P
Follow us on Twitter: @Lutron_EU
Loading...