Lutron H3DT528CU210 Installation Manual

Page 1
Ballast Installation Requirements
EcoSystemR / Hi-lumeR3D / H-Series
R
WARNING: Shock hazard.
May result in serious injury or
death. Disconnect power before servicing or installing.
Sockets Lutron and NEMAR recommend sockets complying with
IEC 60400. Inspect sockets for marks to ensure the socket complies with IEC 60400. Two examples of these marks are:
Sockets must have a
mark as well. Use Rapid Start sockets.
Z
Do NOT use Instant Start sockets.
See LutronR App Note #122 or NEMA doc LSD-34-2006.
Rapid Start (Rotary Locking
Rapid Start (Slide-In Variety)
Variety)
Socket Wiring:
Use 18 AWG (0.75 mm2) solid copper or tinned stranded wire. Refer to ballast label and socket manufacturer for proper strip length.
Make sure yellows are wired in parallel, not in series.
Correct Incorrect
E
and Q.
Rapid Start (Compact)
Lamp Wiring
Socket Lead Length Requirements:
Lamp Type Max. Length of Leads
(ballast to socket)
T5 Linear
T8 Linear
T8 U-Bend
T4 Compact
T5 Twin Tube
Lamps
Temperature: Avoid operating with cold air blowing directly on lamps. LutronR ballasts are
designed to strike the lamps when the lamp temperature is at a minimum of 50 ºF (10 ºC). See lamp manufacturer’s specifications for maximum lamp temperature
Ballast wire strip lengths:
For power, output, and digital terminals (E1, E2).
7 ft (2.1 m)
3 ft (1.0 m)
.
For control and sensor terminals.
t
5
e
I
k
I
I
T
c
T
o
A
S
C
Use Socket Tester (FDB-LSWT-T5/T8) to verify proper lamp holder wiring.
C
S
A
o
T
c
T
I
I
k
I
e
8
t
Ballast Mounting
Lamp Socket Wiring Tester
Mount ballast flush against fixture to provide best heat transfer. Also, avoid mounting ballast close to heat source such as fixture cover plate.
Correct
Lamp
Ballast
Side by side mounting
Ballast
Must be at least 6 in (150 mm) apart.
BalastoBallast
Ballast must be electrically grounded for
proper performance and to meet UL® & NEC®
requirements. Grounding should be
accomplished with paint piercing mounting
hardware to ensure electrical connection
through ballast enclosure and through fixture.
Ballast
When installing more than one ballast in a fixture, contact Lutron Technical Support at 1.800.523.9466 for specific guidelines to maximize performance.
Incorrect
Lamp
Ballast
Lamp
Ballast
Lamp
Ballast
Lamp
Ballast
Lamp Mounting Height Requirements:
Lamp Type Lamp Mounting Height
T8 Linear 1/8 in to 3/4 in (3.2 mm to 19.1 mm)
T5 Linear 1/16 in to 3/8 in (1.6 mm to 9.5 mm)
T5 TwinTube 1/16 in to 1/2 in (1.6 mm to 12.7 mm)
IMPORTANT:
Lamps must never touch ground plane and should be placed without obstruction.
Lamp
Mounting height
Ballast
Lamp Socket (side view)
Grounded metal
Warranty
For Lutron’s ballast warranty, please visit www.lutron.com. Lutron’s warranty does not cover costs or damages caused by misapplication or improper installation.
Solid copper 18 AWG
(0.75 mm2) wire
For proper wiring:
Follow wiring schematic on ballast.
EcoSystemR & Hi-lumeR 3D
Wiring to three lamps
BLU BLU YEL YEL
B/W B/W
RED RED
Striped
Blue
Yellow
Red
Power Wiring
Power Input (Line Voltage):
NEU. DH
Optional for
18-16 AWG (0.75 to 1.5 mm solid copper
To the EcoSystemR Link & up to 64 total ballasts
EC5 & EC3D only
2
)
EcoSystem IEC PELV/NEC
18-16 AWG (0.75 to 1.5 mm solid copper
Ballast Terminals
E1
NEU
HOT
DH
E2
Bus
LineLine
Class 2
R Link can be Class 1 or
R Class 2:*
E1SH E2
NOTE: IEC PELV/NECR Class 2 must be separated
*
from Class 1 and line voltage wiring by the following: 0.25 in (6 mm) or physical barrier. Please refer to App Note #142 for further information.
2
)
E1
NEU
HOT
DH
E2
Bus
Class 2
Sensor Wiring
Sensor Wiring IEC PELV/NECR Class 2 (EC5 only):
COM
Red
Black
White
Yellow
IR OCC
DAYLIGHT
White Orange Black
E1 E2
+20V +20V +20V Common Common Common IR Occ Daylight
22 AWG (0.25 mm2) solid wire. Do not exceed 100 ft (30 m) from sensor to ballast.
Connect only one sensor per input. Wire sensors to one ballast only.
NOTE: Sensor wiring only applies to EcoSystemR Ballasts.
*
EcoSystemR compact, Hi-lumeR 3D, and H-Series ballasts do not have connections for sensors.
NOTE: IEC PELV/NECR Class 2 must be separated from Class 1 and
*
line voltage wiring by the following: 0.25 in (6 mm) or physical barrier. Please refer to App Note #142 for further information.
J–can with occupancy sensor
Red
Black
Blue/ Gray
+20 V Common IR Occ Daylight
+20 V
22 AWG (0.25 mm2) solid
G–can with daylight sensor
Solid copper 22 AWG
(0.25 mm2) wire
H-Series
Note: Wired in parallel
EcoSystemR Link Wiring
Wire Gauge Digital Link Length (max)
12 AWG 2200 ft 14 AWG 1400 ft 16 AWG 900 ft 18 AWG 550 ft
Wire Gauge Digital Link Length (max)
4.0 mm2 828 m
2
517 m
2.5 mm
2
310 m
1.5 mm
2
207 m
1.0 mm
0.75 mm
2
155 m
G–can with wallstation
Red
Black
White
White Orange Black
E1 E2
+20V +20V +20V Common Common Common IR Occ Daylight
Lutron, EcoSystem, Hi-lume, and the Sunburst logo are registered trademarks of Lutron Electronics Co., Inc. NEC is a registered trademark of the National Fire Protection Association, Quincy, Massachusetts. UL is a registered trademark of Underwriters Laboratories, Inc. NEMA is a registered trademark and service mark of the National Electrical Manufacturers Association. The VDE Mark is registered, protected and recognized as a safety mark in more than 30 countries. The ENEC Mark is registered by the signatories in their own country.
Lutron Technical Support Hotline 1.800.523.9466 www.lutron.com
041-308a 09/2011