Lutron GRX-3506-A-WH, GRX-3504-A-WH Installation Manual

Page 1
Chinese
PLEASE LEAVE FOR OCCUPANT
3000 Series Installer’s Guide
Models 3100 and 3500
LUTRON-Quality Systems
In the U.S., Canada and the Caribbean: .......................................................1-800-523-9466
In Mexico, Central and South America:........................................................1-610-282-3800
In Europe:...................................................................................................44-207-702-0657
In the U.K.: ......................................................................................................0800-282-107
In France: ..................................................................................................33-1-44-70-71-86
In Germany:................................................................................................49-309-710-4590
In Japan:..........................................................................................................03-5405-7333
In Hong Kong:.......................................................................................................2104-7733
All others:.....................................................................................................1-610-282-3800
Website address: ...........................................................................................www.lutron.com
E-mail: ...................................................................................................product@lutron.com
LIMITED WARRANTY
Lutron will, at its option, repair or replace any unit that is defective in materials or manufacture within one year after purchase. For warranty service, return unit to place of purchase or mail to Lutron at 7200 Suter Rd., Coopersburg, PA 18036-1299, postage pre-paid.
This warranty is in lieu of all other express warranties, and the implied warranty of merchantability is limited to one year from purchase. This warranty does not cover the cost of installation, removal or reinstallation, or damage resulting from misuse, abuse, or improper or incorrect repair, or damage from improper wiring or installation. This warranty does not cover incidental or consequential damages. Lutron’s liability on any claim for damages arising out of or in connection with the manufacture, sale, installation, delivery, or use of the unit shall never exceed the purchase price of the unit.
This warranty gives you specific legal rights, and you may also have other rights which vary from state to state. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you.This product may be covered by one or more of the following U.S. patents: 4,797,599; 4,803,380; 4,835,343; 4,893,062; 4,924,151; 5,038,081: 5,191,265; 5,430,356; 5,463,286; 5,530,322; 5,949,200; 5,990,635; 6,091,205; 6,380,692; DES 310,349; DES 311,170; DES 311,371; DES 311,382; DES 311,485; DES 311,678; DES 313,738; DES 317,593; DES 335,867; DES 344,264; DES 370,663; DES 378,814; D387,736; D412,315; D412,491; D422,567; D436,930; D453,742; D456,783; D461,782 and corresponding foreign patents. U.S. and foreign patents pending. Lutron, GRAFIK Eye, Tu-Wire, and Hi-lume are registered trademarks; Hi-Power 2
46, Eco-10, LIAISON, and Designer
are trademarks of Lutron Electronics Co., Inc. All other trademarks are the property of their respective owners. © 2002 Lutron Electronics Co., Inc.
Questions? Need technical assistance?
Safety standards listed above apply to one or more products in the GRAFIK Eye product line. Consult factory for specific information.
English
Español Français
Português
NederlandsDeutsch
Chinese
Italiano
LUTRON
®
Page 2
Page 2
Preparation
1. Mount Wallbox. Use standard U.S. wallbox, 3 1/2 in. (87 mm) deep is
strongly recommended, 2 3/4 in. (68 mm) deep minimum. Always allow at least 4 1/2 in. (110 mm) clearance above and below the faceplate to ensure proper heat dissipation.
2. Pull Wires. Use the rearmost knockouts when pulling wires into the wallbox.
This will provide the most clearance when mounting the Control Unit.
3. Remove Cover.Remove the Control Unit’s cover and hinged faceplate by
pulling outward at each corner.
STEP 1: Installing Control Units
This section shows how to install Control Units and make sure they are properly operating all connected loads.
Please read Appendix B: Special Mounting Considerations before installing!
DANGER! GRAFIK Eye lighting controls must be installed by a qualified electrician in accordance with all applicable
regulations. Improper wiring can result in personal injury or damage to GRAFIK Eye lighting controls or other equip­ment. Always turn off circuit breaker/MCB or remove main fuse from power line before doing any work. To avoid overheat­ing and possible damage to equipment, do not install dimming devices to dim receptacles, motor-operated appliances, or fluorescent lighting not equipped with Lutron Hi-lume
®
, Eco-10™, or Tu-Wire®Electronic Dimming Ballasts. In dimmed magnetic low-voltage circuits, you can prevent transformer overheating and failure by avoiding excessively high current flow: Do not operate GRAFIK Eye lighting controls with any lamps removed or burned out; Replace any burned out lamps immediately; Use only transformers that incorporate thermal protection or fused primary windings. This lighting control is designed for residential and commercial use. GRAFIK Eye Controls are designed for indoor use only.
CAUTION! First test loads for short circuits.
1. Turn power OFF at the breaker/MCB panel or fuse box.
2. Connect standard light switch between live lead and the load wire to test circuit.
3. Turn power on and check for short or open circuits: If load does not operate, circuit is
open. If the breaker/MCB trips (fuse blows or opens), circuit is shorted. Correct short or open circuits and test again.
Load Types
The Control Units can control incandescent, halogen (tungsten), magnetic low-voltage, and neon/cold cathode load types. Electronic low-voltage and fluorescent load types can be controlled with an appropriate interface.
All Electronic Low-Voltage (ELV) lighting used with the Electronic Low-Voltage Interface must be rated for reverse
phase-control dimming. Before installing an ELV light source, verify with the manufacturer that their transformer can be dimmed. When dimming, an Electronic Low-Voltage Interface MUST be used with the Control Unit.
Not all zones need to be connected; however, connected zones must have a load of at least 25W (40W for AU and CE
models).
No zone may be loaded with more than 800W (1200 for AU models).
Unit must not carry more than 16A of total lighting load (10A for CE models).
Wallbox Size/Max. Unit Load
100-127V
230V 220-240V
3102/3502 2-Gang U.S/1200W/VA 4-Gang U.S†/10A 2-Gang U.S/1600W/VA 3103/3503 3-Gang U.S/1500W/VA 4-Gang U.S†/10A 3-Gang U.S/2400W/VA 3104/3504 4-Gang U.S/2000W/VA 4-Gang U.S†/10A 4-Gang U.S†/3000W/VA
3106/3506 4-Gang U.S/2000W/VA 4-Gang U.S†/10A 4-Gang U.S†/3000W/VA
† Lutron P/N 241-400 or 241-691 (old work metal wallbox).
Installation instructions. First, turn power off.
HOT/LIVE
NEUTRAL
SWITCH
LOAD
2
3
0
V
˜
L
U
T
R
O
N
5
0
/
6
0
H
z
L
O
A
D
P
E
R
Z
O
N
E
:
4
0
-
8
0
0
W
M
A
X
U
N
I
T
L
O
A
D
:
1
0
A
,
2
3
0
0
W
P
r
e
s
e
t
L
i
g
h
t
i
n
g
C
o
n
t
r
o
l
L
I
V
E
T
E
R
M
I
N
A
L
S
A
T
R
E
A
R
D
O
N
O
T
W
IR
E
L
IV
E
U
.
K
.
0
7
1
-
7
0
2
-
0
6
5
7
U
.
S
.
A
.
(
6
1
0
)
2
8
2
-
3
8
0
0
C
O
O
P
E
R
S
B
U
R
G
,
P
A
U
S
A
1
8
0
3
6
G
R
X
-
3
1
0
4
-
C
E
U
P
M
a
d
e
i
n
U
.
S
.
A
.
1
2
V
S
E
L
V
O
U
T
P
U
T
!
C
B
E
5
1
4
5
-
0
4
9
G
R
X
-
Z
Model Number
3.5 in (87 mm)
3.75 in. (95 mm)
7.9 in. (200 mm)
Page 3
Page 3
Line Voltage/Mains Wiring
Important Wiring Notes!
Use properly certified cable for all line voltage/mains cables and Class 2/PELV cables.
In Europe, acceptable types of cable include HAR certified cable with insulated cores enclosed in a sheath. This cable
must bear the appropriate certification mark pertaining to national wiring rules for fixed installations. If certified cable with insulated cores enclosed in a sheath is used for the Power cables, the Class 2/PELV wiring can be any of the specified cables in Appendix A: More about Class 2/PELV Wiring.
Proper short-circuit and overload protection must be provided at the distribution panel. You can use up to a 20A (16A
for AU, and 10A for CE models) maximum circuit breaker/MCB or equivalent (tripping curve C according to IEC60898/EN60898 is recommended) with adequate short-circuit breaking capacity for your installation.
Install in accordance with all local and national electrical codes.
CAUTION! Do not connect line voltage/mains cable to Class 2/PELV terminals.
Earth/Ground terminal connection must be made as shown in wiring diagrams.
Do not mix different load types on the same zone!
Fluorescent and electronic low voltage loads require interfaces. Zone loads that exceed 800W/VA (1200W/VA for AU
models) and total unit loads that exceed the unit capacity require power boosters.
Wire the Control Unit
1. Strip 1/2 in. (12 mm) insulation from all wires in wallbox and connect them to appropriate terminals on the back of the
Control Units. The recommended installation torque is 9.0 in.-lbs. (1.0 N●m) for line voltage connections and 10 in.­lbs. (1.3 N
m) for the earth/ground connection. Each power terminal can accept up to two #12 AWG (2.5 mm2) wires
(does not apply to Class 2/PELV terminal block).
GRX-CE Models*
* For phase-to-phase and delta-feed wiring, please contact Lutron.
GRX-3106/3506*, GRX-3106-AU/3506-AU*
For permanently installed incandescent or iron core transformer low voltage incandescent fixtures only.
ZONE 4
ZONE 2
ZONE 6
SSA
PELV ONLY
1 2 3 4
COM 12V MUX MUX
GRX-3106-CE
230V~50/60Hz ZONE CAPACITY: 40-800W UNIT CAPACITY: 10A, 2300W
ZONE 3
L
ZONE 1
ZONE 5
N
LOAD 2
LOAD 4
LOAD 6
2 2.5 mm
2
2 2.5 mm
2
2 2.5 mm
2
EARTH/GROUND FROM DISTRIBUTION PANEL
NEUTRAL FROM DISTRI­BUTION PANEL
INPUT POWER FROM DISTRIBUTION PANEL
LOAD 1
LOAD 3
LOAD 5
HOT/ LIVE
N
DISTRIBUTION PANEL
2 2.5 mm
2
2 2.5 mm
2
2 2.5 mm
2
2 2.5 mm
2
ZONE 4
ZONE 6
HOT/LIVE
SSA
CU WIRE ONLY
ZONE 2
Class 2
1 2 3 4
ZONE 3
ZONE 5
NEUTRAL
ZONE 1
USA CLASS 2 IEC PELV
HOT/
LIVE
N
LOAD 2
LOAD 4
LOAD 6
LOAD 1
LOAD 3
LOAD 5
DISTRIBUTION PANEL
NEUTRAL FROM DISTRIBUTION PANEL
INPUT POWER FROM DISTRIBUTION PANEL
EARTH/GROUND FROM DISTRIBUTION PANEL
2 #12 AWG
2 #12 AWG
2 #12 AWG
2 #12 AWG
2 #12 AWG
2 #12 AWG
2 #12 AWG
Page 4
Class 2/PELV Wiring
Page 4
LINE VOLTAGE/MAINS CABLE
CLASS 2/PELV
TERMINAL
CLASS 2/PELV CABLE
1.0 in. (25 mm)
3/8 in.
(9.5 mm)
LINE VOLTAGE/MAINS CABLE
Testing: Do the lights work?
1. Restore Power.
2. Press Scene 1 button on front of the GRAFIK Eye
Control Unit. The Scene 1 LED will light.
3. Press zone or to raise or lower the light levels.
Make sure that the Control Unit is dimming all connected loads. Refer to Appendix C: Troubleshooting, or call Lutron.
Connect Class 2/PELV wiring only if your project has Wallstations and/or more than one Control Unit.
Use recommended cable as specified in Appendix A: More About Class 2/PELV Wiring.
Use the rearmost knockouts when pulling wires into the wallbox. This will provide the most clearance when mounting the Control Unit.
1. Strip 1 in. (25 mm) of insulation from the Class 2/PELV
cable.
2. Strip 3/8 in. (8 mm) of insulation from each wire.
3. Connect the Class2/PELV wires to the Class 2/PELV terminal block. Make sure no bare wire is ex-
posed after making connections. The recommended installation torque is 3.5 in.-lbs. (0.4 N
m) for Class
2/PELV connections.
4. The Class 2/PELV cable and terminal block should be separated from line voltage/mains cables by at least 1/4 in. (7 mm).
Mounting
1. Mount as shown using the four screws provided. (When
mounted in the wallbox, the Class 2/PELV cable and ter­minal block should remain separated from the line volt­age/mains cables.)
2. Reattach the faceplate to the Control Unit by pushing in­ward at each corner
GRAFIK Eye Control Unit
FADE TEMPORARY
MASTER
ZONES
ZONE 1 ZONE 2
M S
00
2.Adjust light level of each Zone.
3.Repeat for each Scene.
For more setup options, refer to the literature supplied with your GRAFIK Eye, or call Lutron Electronics Co., Inc.
P/N 500-8723
U.S.A., Canada, Caribbean
Toll Free: (800) 523-9466 International: 1-610-282-3800
Europe
Freephone: 0800 282107 (U.K.) International: 44-171-702-0657
Hong Kong
Tel: 2104-7733 International: 852-2104-7733
Singapore
Tel: 65 487 2820
Lutron Worldwide Locations
ZONE 1
Internet: www.lutron.com
Scene button
Off button
HINGED COVER
ZONE LABEL
LIGHT LEVEL LED BARGRAPH
ZONE RAISE/LOWER BUTTONS
INFRARED WIRELESS
REMOTE CONTROL RECEIVER
FACEPLATE
INSTRUCTION LABEL
FADE WINDOW (IF ‘S’ IS LIT, TIME IS IN SECONDS, IF ‘M’ IS LIT, TIME IS IN MINUTES)
MASTER RAISE/LOWER
FADE BUTTONS
SCENE BUTTONS
SCENE 1 SCENE2 SCENE 3 SCENE 4 OFF
SCENE INDICATOR LEDs
STEP 2: Setting Up GRAFIK Eye Control Units
Scene 1 button
OFF
Zone intensity raise and lower buttons
Scene 1 LED
1
2
3
4
ZONE 1 ZONE 2
ZONE 3 ZONE 4
ZONE 5 ZONE 6
FADE TEMPORARY
M S
ZONES
MASTER
Page 5
Page 5
To enter setup mode: Press and hold the Scene 1 and
OFF button for about three seconds, until the scene LEDs start cycling.
To exit setup mode: Exit setup mode the same way you entered it. Press and hold the Scene 1 and OFF but­ton for about 3 seconds, until scene LEDs stop cycling. The Control Unit is out of setup mode; back in normal operating mode.
In setup mode, the FADE window displays the setup codes. To scroll through the menu of setup codes, press the FADE  or  buttons.
Identifying the Load Type for each Zone
1. Enter setup mode. Press and hold Scene 1 and OFF
buttons for about 3 seconds, until scene LEDs cycle.
2. Check for LS in FADE window. (LS is the first code to appear when you enter setup mode. For the LS mode, ZONE LEDs turn on from top to bottom.)
3. Set each zone’s load type. Press ZONE  and until ZONE LEDs match the load type connected to each zone. Refer to chart on next page.
4. Exit setup mode. Press and hold Scene 1 and OFF buttons for about 3 seconds, until scene LEDs stop cy­cling.
In the 6-Zone Control Unit shown here:
Zone 5 is set for incandescent or magnetic low-voltage.
Zone 6 is set for neon/cold cathode.
This section shows how to set up a GRAFIK Eye Control Unit, including:
Identifying the load type for each zone of lighting
connected to the Control Unit.
Setting up the scenes to create the desired light-
ing effects, and make sure the Control Unit is working correctly.
To set up the GRAFIK Eye Control Unit, enter the “setup mode” and use the menu of setup codes that appear in the FADE window. Step-by-step instruc­tions for using the setup codes are on the following pages.
How to Enter and Exit Setup Mode
The following is a list of the setup codes and their descrip­tions:
Lutron ships GRAFIK Eye Control Units with all zones set for incandescent/halogen (tungsten) lighting. If your pro­ject has non-incandescent loads, change all non-incan­descent zones to the correct load type.
SET EACH ZONE’S LOAD TYPE
CHECK FOR LS
ENTER (EXIT) SETUP MODE
ZONE LEDs
FADE TEMPORARY
MASTER
ZONES
ZONE 5 ZONE 6
M S
LS
TO ENTER (EXIT) SETUP MODE:
PRESS AND HOLD FOR ABOUT 3 SECONDS UNTIL LEDs CYCLE (STOP CYCLING)
LEDs
SCROLL THROUGH SETUP CODES
Code
Sd
Sc
A-
LS* LE
Stands for
Save Options
Scene
Address
Load Select Low End
Description
Select from several save options (Pg. 8) Set unaffected zones and set any of the 16 scenes (Pg. 8) Identify Control Units when setting up system commu­nications (Pg. 9) Identify load type (Pg. 5) Set low end trim (Pg. 7)
* When you enter setup mode, this code appearsfirst.
■ If you press FADE , you will see A-, Sc, then Sd.
If you press FADE , you will see LE.
3
ZONE 5 ZONE 6
FADE TEMPORARY
LS
M S
ZONES
MASTER
2
1
,
4
Page 6
How to Set up Lighting Scenes
Page 6
Incandescent, Halogen (tungsten)
1. Set all zones connected to HP Dimming Modules as shown—no matter what load type they are (including non-dim or switching). The HP can be used to switch non-capacitive ballasts. To fine-tune the dimming of these “HP-powered” zones, you must adjust high­and low-end trim on the HPs as described in the In­struction Sheet supplied with the unit. Do NOT use HPs with generator-supplied line/mains voltage.
2. All electronic low-voltage (ELV) lighting used with the Electronic Low-Voltage Interface (ELVI) must be rated for reverse phase control dimming. Before installing an ELV light source, verify with the manufacturer that their transformer can be dimmed. When dimming, an ELVI MUST be used with the 3000 Series Control Unit.
3. Any zones set for Lutron Hi-lume or Eco-10 fluorescent lighting must have GRX-FDBI or GRX-TVI Fluorescent In­terfaces. Consult Lutron for more information.
4. Please note that the Tu-Wire Compact Fluorescent, unlike other fluorescent load types, does not require an FDBI in­terface. This load type is not available in GRX-CE models.
5. Use non-dim for any lights to be switched on and off only—not dimmed (unless using HP Dimming Module).
Fluorescent non-dim loads with electronic or magnetic
ballasts must: use a GRX-TVI Interface and be set for non-dim mode, or use an HP 246™Dimming Module and be set for HP 246 Dimming Module loads.
What is a Scene?
* The S and M indicators under the FADE window show
whether FADE is “M”inutes or “S”econds. To set FADE in minutes, you press FADE
to scroll through 1—59 sec-
onds . . . the M lights. FADE is now expressed in minutes. To get back to seconds, press FADE
until the window
shows “S”econds. The FADE-in time from OFF to any Scene is factory-set at 3 seconds.
Note: Control Unit must be in Sd mode. See Page 8 for
more information regarding Save Options.
To set up scenes 1 through 4:
1. Select a scene. Press the Scene button for the scene you want to adjust. (First button for Scene 1, second button for Scene 2, and so on.) Note that the last button is the “Off” Scene. You do not set intensities for this button.
2. Set each zone’s light levels. Press ZONE  and to adjust each ZONE to the right visual intensity for this scene. To program scenes 5 through 16, or for more precise zone intensity adjustment with a GRAFIK Eye 3500 Control Unit, refer to page 7.
3. Set scene’s FADE-in time. Press FADE  and to make FADE-in time anything from 0—59 seconds or 1—60 minutes*. (FADE-in time is how long it takes the lights to adjust to the new levels when the scene is selected.)
Repeat this process to set up each of the remaining scenes. Note that you can also set up a “FADE-to-off” time. Press the OFF button and adjust FADE as desired.
Scenes are the preset light levels and fade times stored in the Control Unit. To create a scene, set the appropriate intensity for each ZONE. To recall a scene, simply press one of the buttons. The first button calls up Scene 1; the second, Scene 2; and so on. The last button turns lights Off. For example, typical scene settings for a living room might be:
Scenes 1—4 can be selected on the Control Unit. However, all Control Units are capable of storing up to 16 scenes. Scenes 5 through 16 can be selected using Wallstations.
Magnetic Low Voltage
HP 2
46
Loads
1
(120V
supply only)
Electronic Low Voltage
2
Hi-lume
or Eco-10 Fluorescent
3
Tu-Wire
Compact Fluorescent
4
Neon/Cold Cathode
Non-dim
5
(last on, first off)
Non-dim
5
(first on, first off)
SET THE LIGHT LEVEL OF EACH ZONE
SET SCENE’S FADE-IN TIME
SELECT A SCENE
FADE TEMPORARY
MASTER
ZONES
ZONE 5 ZONE 6
M S
SCENE 1 SCENE 2 SCENE 3 SCENE 4 OFF
2
ZONE 5 ZONE 6
FADE TEMPORARY
ZONE
ZONES
M S
MASTER
3
1
Page 7
Page 7
How to Adjust Light Levels Temporarily
How to Set Low-end Trim—OPTIONAL
If necessary, adjust the low-end trim to achieve uniform low-intensity dimming and to eliminate flicker (especially with neon/cold-cathode and fluorescent loads).
1. Enter setup mode. Press and hold Scene 1 and OFF buttons for about 3 seconds, until scene LEDs start cycling.
2. Select LE (low end) by pressing FADE once. All zones go to their lowest possible dim levels and only their bottom LED is lit*.
3. Adjust zone’s lights for low-end trim. Use ZONE and to dim the zone’s lights as much as possible without causing flicker. Repeat this process for any other zones that require low-end trim.
4. Exit setup mode. Press and hold Scene 1 and OFF buttons until scene LEDs stop cycling.
Note: The ZONE LED bargraph does not change while
you make low-end trim adjustments. The bar­graph remains set to its lowest level in this mode.
Advanced Scene Programming Options—OPTIONAL
Control Unit must be in either Sd or Sb mode. See Page 8 for more information regarding Save Options.
To adjust an entire scene:
Press the appropriate scene button. Press MASTER  or  to raise or lower the intensity of all zones.
To adjust a zone:
If the TEMPORARY LED is not already lit, press the TEMPORARY ZONES button. The TEMPORARY LED above the TEMPORARY ZONES button will light. Press ZONE  or  to adjust any zone’s intensity.
Note: These adjustments are temporary and remain
only until a new scene selection occurs.
* Except zones set for non-dim. For these, all zone LEDs are lit, and you
cannot adjust the low-end trim.
SELECT FLASHING Sc/I
SET SCENE’S FADE-IN TIME
SELECT SCENE
ENTER (EXIT) SETUP MODE
ADJUST ZONE INTENSITY
ADJUST ZONE’S LIGHT FOR LOW-END TRIM
SELECT LE
ENTER (EXIT) SETUP MODE
FADE TEMPORARY
MASTER
ZONES
ZONE 5 ZONE 6
M S
TEMPORARY LED
MASTER RAISE/LOWER
SCENE BUTTONS
ZONE INTENSITY RAISE/LOWER BUTTONS
Programming Scenes 5 through 16.
1. Enter setup mode. Press and hold Scene 1 and OFF buttons about 3 seconds until scene LEDs start cycling.
2. Select Sc (the code for scene setup) by pressing FADE twice. Sc and 1 (Scene 1) will alternately flash in the FADE window.
3. Select scene. Press MASTER  or to select the scene to be programmed.
4. Adjust ZONE-intensity. Press ZONE  or to adjust zone’s intensity (GRX-3500 units will display exact percentage light output — press again to adjust light levels in 1% increments).
5. Set scene’s FADE-in time. Press and hold the TEMPORARY ZONES button. The current FADE-in time is displayed. Adjust using the FADE  and  while still holding the TEMPORARY ZONES button.
6. Exit setup mode. Press and hold Scene 1 and OFF buttons until LEDs stop cycling.
3
ZONE 5 ZONE 6
FADE TEMPORARY
LE
ZONES
M S
MASTER
2
4
1
,
2
ZONE 1 ZONE 2
FADE TEMPORARY
Sc
ZONES
M S
MASTER
5
3
6
1
,
4
Page 8
Page 8
How to Set an “unaffected zone” — OPTIONAL
You can set up a zone to be “unaffected” when a certain scene is selected. (The unaffected zone’s light levels remain unchanged when the new specified scene is selected.)
1. Enter setup mode. Press and hold Scene 1 and OFF buttons about 3 seconds until scene LEDs start cycling.
2. Select Sc (the code for scene setup) by pressing FADE twice. Sc and I (for scene 1) will alternately flash in the FADE window.
3. Select scene. Press MASTER  and to select the scene that will have the unaffected zone.
4. Program any ZONE as unaffected. Press ZONE twice and then hold until all the bargraph LEDs go out and the middle LED light. (It may take up to 10 seconds after the last LED goes out until the middle LED lights.) This zone’s light levels will no longer be affected when this scene is selected. Note that you can set up several zones to be unaffected in a scene.
5. Exit setup mode. Press and hold Scene 1 and OFF but­tons until LEDs stop cycling.
The GRAFIK Eye 3000 Series Control Units allow selection of several different Save Options. Follow these steps to access the Save Options.
1. Enter setup mode. Press and hold Scene 1 and OFF buttons for about 3 seconds until scene LEDs start cy­cling.
2. Select Sd. Press FADE until Sd is displayed in the FADE window.
3. Select Save Options. Press MASTER  and to se- lect between the Save Options: Sd Save by Default. Changing a zone’s intensity level
or fade time permanently changes the preset scene. To temporarily change a light level, see “How to ad­just light levels temporarily” on Page 7.
Sb Save by Button. TEMPORARY ZONES LED is nor-
mally ON and all intensity and fade changes are tem­porary unless the TEMPORARY ZONES LED is turned OFF with the TEMPORARY ZONES button.
Sn Save Never. TEMPORARY ZONES LED is perma-
nently ON and cannot be turned OFF. In this mode, all intensity changes are temporary.
4S Four Scenes. This only allows the four Scene but-
tons, OFF button, IR receiver and the MASTER  or to operate. All other buttons on the Control Unit are disabled.
bd Button Disable. All buttons on the Control Unit are
disabled. IR Receiver, and Wallstations are still func­tional. (Setup mode is still accessible by repeating Step 1.)
4. Exit setup mode. Press and hold Scene 1 and OFF but­tons until scene LEDs stop cycling.
ENTER (EXIT) SETUP MODE
SELECT SAVE OPTION
SELECT Sd
How to Set Save Options — OPTIONAL
SELECT SCENE
ENTER (EXIT) SETUP MODE
SELECT FLASHING Sc/I
PRESS ZONE TWICE AND THEN HOLD UNTIL MIDDLE LED TURNS ON
2
ZONE 5 ZONE 6
4
FADE TEMPORARY
Sc
ZONES
M S
MASTER
3
5
1
,
2
ZONE 5 ZONE 6
FADE TEMPORARY
ZONES
M S
MASTER
3
1
,
4
Page 9
Press Scene 1 button . . .
Page 9
STEP 4: Setting Up System Communications
This section shows how to set up communications between Control Units. For specific, step-by-step instructions about setting up communications for each type of GRAFIK Eye Wallstation, please refer to the instructions included with each Wallstation.
Assign each GRAFIK Eye Control Unit in your project a unique system address (A1 through A8). To assign an address:
1. Enter setup mode. Press and hold Scene 1 and OFF buttons about 3 seconds, until scene LEDs cy­cle.
2. Select A- (the address display). Press FADE once, A- appears in the FADE window.
3. Assign a unique address. Press MASTER once, the next “free” (unassigned) address automat­ically appears in the FADE window. This will be the Control Unit’s address. (If you are working on the first Control Unit in the project, AI will appear.)
4. Exit setup mode. Press and hold Scene 1 and OFF buttons about 3 seconds, until the LEDs stop cycling.
5. Repeat steps 1 through 4 for each GRAFIK Eye Control Unit.
First check Class 2/PELV wiring. Before you set up communications, make sure your Class 2/PELV system interconnections are working.
1. Select Scene 1 (press the top button) on one of the Control Units.
2. Is Scene 1 selected on all other Control Units? YES: Class 2/PELV wiring is OK. Proceed. NO: Class 2/PELV wiring has a miswire. Check for loose
connections, shorted or crossed links. Refer to Ap­pendix A for details on Class 2/PELV wiring.
OR
GRAFIK Eye Control Unit has been addressed to other than A- (factory default). See below for more information on addressing Control Units.
Assign Addresses to GRAFIK Eye Control Units
SELECT A-
ASSIGN A UNIQUE ADDRESS
ENTER (EXIT) SETUP MODE
. . . all other Scene 1 LEDs light!
IMPORTANT!
IMPORTANT WIRING NOTES!
Review Appendix A BEFORE wiring!
Please refer to the Installation Instructions included with each Wallstation/Control before installing.
Wallstations/Controls must be installed by a qualified electrician.
Wallstations/Controls use Class 2 or PELV wiring methods as applicable in your locale.
Using Class 2 wiring methods: Wallstations/Controls must be connected in accordance with the 1996 National
Electrical Code, Article 725-54(a), (1) Exception No. 3 or the Canadian 1994 CE Code Handbook, Rule 16-212, Subrule (4). Check with your local electrical inspector to comply with local codes and wiring practices.
Using PELV wiring methods: Wallstations/Controls that are connected to terminals 1—4 must always meet the
requirements of DIN VDE 0100 Part 410 and IEC 60364-4-41 for PELV circuits. See “What is PELV?” in Appendix A.
Wallstations/Controls must be mounted in a wallbox. Please refer to instruction sheet included with each
Wallstation/Control to determine wallbox requirements.
STEP 3: Installing Wallstations/Controls
ZONE 5 ZONE 6
3
2
FADE TEMPORARY
A-
ZONES
M S
MASTER
1
,
4
Page 10
1. Put A1 in setup mode. Press and hold Scene 1 and OFF buttons for about 3 seconds, until LEDs cycle.
2. Identify the Control Units to “listen” (A2 and up to 6 others). Press and hold the Scene 1 button for about 3 seconds until LEDs flash in unison, showing that these Control Unit(s) are “listening” to A1. (To make a “listening” Control Unit not listen to A1: Put A1 in setup mode, then press the “listening” Control Unit’s OFF button until the LEDs stop flashing.)
3. Take A1 out of setup mode. Press and hold Scene 1 and OFF buttons for about 3 sec­onds, until LEDs on A1, and all other linked Control Unit(s), stop cycling. You have set up communications in one direction between A1 and all “listening” Control Units.
4. To complete the two-way communication, reverse the process described above: Put A2 in setup mode; then make A1 (and any other Control Units) “listen”; then take A2 out of setup mode.
Selecting a scene on A1 . . .
Page 10
A3
4 zones
6 zones
6 zones
A2
A1
A1 “listens” . . . . . . when A2 “talks”
LEDs flash LEDs cycle
A1 “talks” . . .
LEDs cycle
. . . A2 “listens”
LEDs flash
Set up Communication between 2 or more Control Units
This page explains how to use 2­way communications to set up lighting effects for more than six zones (the maximum number of zones any one 3000 Series Control Unit can operate). When you set up two-way com­munications between Control Units, selecting a scene at any one of these Units automatically activates the same scene in the others. By linking eight 6-Zone Control Units, you can create scenes that control the intensity of up to 48 zones. This “large­zone” capability is ideal for large spaces with dramatic lighting that changes frequently (e.g., churches).
For example: 16-Zone Control
. . . Activates the same scene on A2 and A3.
Linked by two-way communications, these Control Units act like a 16-Zone Control Unit. Note that you must set up communications both ways among all Control Units:
A1 “talks” to A2 and A3 –– and “listens” to them as well.
A2 “talks” and “listens” to A1 and A3.
A3 “talks” and “listens” to A1 and A2.
Make sure you have addressed the Control Units (as described on page 9) before set­ting up two-way communications.
Set up communications in one direction . . .
. . . then the other.
Page 11
Appendix A: More about Class 2/PELV Wiring
This appendix explains the Class 2/PELV wiring used to carry communications be­tween GRAFIK Eye Control Units and Wallstations. Lutron requires that you connect (daisy-chain) all GRAFIK Eye 3000 Series Control Units and Wallstations with two twisted pair for operation. If shielded wire is used, the drain wires must be connected to each other or to Terminal D, if present. Drain wires should not be connected to Earth/Ground.
One pair is for the low-voltage power wiring that enables each GRAFIK Eye
Control Unit to supply power to up to three Wallstations. Connect this twisted pair to terminals 1 (COMMON) and 2 (12VDC). Terminate the 12VDC power to ensure that each Control Unit powers no more than three Wallstations.
The second pair is for a data link (up to 2000 ft. or 450 m long) that enables
Wallstations to communicate with GRAFIK Eye Control Units. Connect this twist­ed pair to terminals 3 (MUX) and 4 (MUX) of every Control Unit and
Wallstation. Each twisted pair in the Class 2/PELV wiring link should consist of two #18 AWG (1.0 mm2) stranded conductors.
Lutron offers a one-cable, low-voltage solution: P/N GRX-CBL-346S
(non-plenum), or GRX-PCBL-346S (plenum).
Recommended unshielded cables:
For non-plenum installations, use (2) Belden 9470, (1) Belden 9156, or (2) Liberty 181P/2C-EX-GRN, or equivalent.
For plenum installations, use (2) Belden 82740, or equivalent.
Wallstation circuits are classified as Class 2 circuits (U.S.A) and PELV circuits (IEC). Unless otherwise specified, the voltages do not exceed 24VAC or 15VDC. As Class 2 circuits, they comply with the requirements of NFPA 70
®
, National Electrical Code®(NEC®). As PELV circuits, they comply with the requirements of IEC 60364-4-41, VDE 0100 Part 410, BS7671:1992 and other equivalent standards. When installing and wiring to these Wallstations, follow all applicable national and/or local wiring regulations. External circuits connected to input, output, RS232, DMX512, and other communication terminals of Wallstations, must be supplied from a Listed Class 2 source or comply with the requirements for PELV circuits as applicable in your country.
The GRAFIK Eye 3000 Series Control Unit Class 2/PELV circuit is 12VDC.
What is PELV?
In countries that abide by the IEC regulations, PELV is commonly referred to as Protective Extra-Low Voltage. A PELV cir­cuit is an earthed circuit in which the voltage cannot exceed 50VAC or 120V ripple-free DC. The power source must be supplied by a safety isolating transformer or equivalent.
IMPORTANT WIRING NOTE!
Proper separation is required between the Line Voltage/Mains cables and PELV cables. Use certified cable for all Line Voltage/Mains cables and PELV cables. Cable bearing HAR or national certification marks are acceptable, provided it covers all applicable wiring regulations for fixed installations. See Important Wiring Note on Page 3.
See Important Wiring Notes on Page 12. Each Control Unit can power up to three Wallstations. If you need to power more than three Wallstations from one Control Unit, install an external 12VDC power supply (Lutron P/N GRX-12VDC).
Page 11
EACH TERMINAL CAN ACCEPT
2 #18 AWG (1.0 mm
2
) WIRES
CLASS 2/PELV POWER WIRING:
2: 12VDC
1: COMMON
WALLSTATION WALLSTATION WALLSTATION
GRAFIK Eye
3000 SERIES
CONTROL UNIT
DATA LINK: 4: MUX
3: MUX
A Control Unit with up to three Wallstations
EACH TERMINAL CAN ACCEPT 2 #18 AWG (1.0 mm
2
) WIRES
CLASS 2/PELV POWER WIRING: 2: 12VDC 1: COMMON
2 TWISTED PAIRS #18 AWG (1.0 mm
2
)
DATA LINK: 4: MUX 3: MUX
Maximum of 1000 ft. (300 m) between the GRAFIK Eye Control Unit and the third Wallstation. For longer distances, use an external Class 2/PELV rated 12VDC power supply (Lutron P/N GRX-12VDC).
123456
4
3
2
1
4 3 2 1
123456
123456
4 3 2 1
4 3 2 1
123456
4 3 2 1
Page 12
Page 12
A1
A2
A3
A1 powers a only—terminal 2 connection terminates at a.
A2 and A3 have
their own power supplies—no terminal 2 con­nection.
b
c
d
e
f
g
A4
A3 powers b, c, and d.
Total Class 2/PELV wiring length is 2000 ft. (600 m).
Maximum length of t-tap is 8 ft. (2.5 m).
A4 power e, f, and g— no terminal 2 connection between d and e.
a
Up to 8 Control Units and 16 Wallstations
IMPORTANT WIRING NOTES!
1. Daisy-chain the terminal 1, terminal 3, and terminal 4 connections to all Control Units and Wallstations. Each Control
Unit has its own power supply. Terminate the terminal 2 connection (12VDC power) so that:
Each Control Unit supplies power to a maximum of three Wallstations.
Each Wallstation receives power from only one Control Unit.
2. Lutron recommends that all connections be made in the Control Unit’s wallbox. Remote connection must be in a switchbox or junction box with a maximum wire length of 8 ft. (2.5 m) from the link to the connected unit.
Note: Do not allow Class 2/PELV wires to contact line/mains wires. Refer to Class 2/PELV wiring on Page 4.
IMPORTANT WIRING NOTES!
1. Daisy-chain the terminal 1, terminal 2, terminal 3, and terminal 4 connections to all Control Units and Wallstations.
The Control Unit has its own power supply.
2. Each Control Unit can power up to three Wallstations. If you need to power more than three Wallstations from one Control Unit, install an external 12VDC power supply as described later in this section.
3. Lutron recommends that all connections be made in the unit wallbox. Remote connection must be in a switchbox or junction box with a maximum wire length of 8 ft. (2.5m) from the link to the connected unit.
Note: Do not allow Class 2/PELV wires to contact line/mains wires. Refer to Class 2/PELV wiring on Page 4.
Installing an External Power Supply
Install an external Class 2/PELV rated 12VDC power supply as shown on Page 13. This power must be Class 2/PELV rated and be a regulated supply rated for at least 50 mA per Wallstation on the link. It can supply power to up to 16 Wallstations, enabling you to use up to 16 Wallstations with one Control Unit.
Use an external power supply if you need to power more than 3 Wallstations from a single Control Unit or if your wire lengths exceed maximums. Power supplies do not boost data line signals. The distance limitation for the data line is 2000 ft. (450 m). Make sure you review the manufacturer’s instructions before installing.
Lutron offers a 12VDC transformer for 120V applications. Please ask for P/N GRX-12VDC.
IMPORTANT WIRING NOTES!
1. Connect the +12VDC wire from the power supply to the terminal 2 connection on all Wallstations. Do not connect this
wire to any Control Units on the link. Be sure that the terminal 1 connection is made to all Wallstations and Control Units.
2. Lutron recommends these maximum distances from the external 12VDC power supply to the sixteenth Wallstation:
#18 AWG (1.0 mm
2
) wire: 300 ft. (90 m). #12 AWG (2.5 mm2) wire: 1000 ft. (300 m).
Note that the allowable maximum distance depends on the number of Wallstations in the system. Please see Application Note W14 or consult Lutron Technical Support for more detailed information.
1 2 3 4
4
3
2
4
1
3
2
1
4 3 2 1
1 2 3 4
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4 3 2 1
4 3 2 1
4 3 2 1
4 3 2 1
Page 13
Page 13
Appendix B: Special Mounting Considerations
Wallbox Mounting
Spacing of the GRAFIK Eye 3000 Series Control Unit
When mounting multiple GRAFIK Eye 3000 Series Control Units near each other, the following spacing and ventilation guidelines are required for proper operation.
1. All GRAFIK Eye 3000 Series Control Units MUST be mounted in a standard U.S. Wallbox. These are available from Lutron.
For two-zone Control Units, Power Boosters, Fluorescent
Interfaces, and Electronic Low-Voltage Interfaces, use two P/N 241-519 single-gang wallboxes.
For three-zone Control Units, use three P/N 241-519 single-gang
wallboxes.
For four-zone (or larger) Control Units, use one P/N 241-400
four-gang wallbox.
Note: All GRX-CE Control Units mount in one P/N 241-400 four-
gang wallbox.
2. All GRAFIK Eye 3000 Series Control Units, Power Boosters, Fluorescent Interfaces, and Electronic Low-Voltage Interfaces MUST have 4 1/2 in. (11 cm) of space above and below the faceplate to dissipate the heat caused by normal operation.
Panel Mounting
The enclosure must be in accordance with all local and national
electrical codes.
Lutron does not recommend using a door to enclose the front of
a panel, since this restricts airflow to the GRAFIK Eye 3000 Series Control Units and Interface Devices.
If mounting multiple GRAFIK Eye 3000 Series Control Units or
Interface Devices in an enclosure:
1. Ambient temperature within an enclosure MUST remain
between 32°—104° F (0°—40° C).
2. If not mounting in a metal enclosure, all units MUST be
mounted in a wallbox. Refer to Wallbox Mounting above.
To improve heat dissipation of Interface Units, (i.e., NGRX-PB,
GRX-ELVI, etc.), remove the faceplate from the unit.
IMPORTANT NOTE:
GRAFIK Eye 3000 Series Control Units and Interface Devices, such as NGRX-PB, dissipate heat when operating.
Obstructing these units can cause malfunction to both the Control Unit and the Interface Device if ambient temperature does not remain between 32°—104° F (0°—40° C).
LIMITED BY PHYSICAL SIZE OF UNIT. MUST BE ABLE TO OPEN FRONT COVER.
4 1/2 in. (11 cm) MINIMUM
4 1/2 in. (11 cm) MINIMUM
4 1/2 in. (11 cm) MINIMUM
FDBI
ELVI
PB
4 3 2 1
4 3 2 1
3 2 1
4
LUTRON
LUTRON
CLASS 2/PELV TERMINALS ON BACK OF UNIT
1 TWISTED PAIR
#18 AWG (1.0 mm
2
) OR LARGER
2 TWISTED PAIR
#18 AWG (1.0 mm2) OR LARGER
WALLSTATION WALLSTATION
16 WALLSTATIONS (MAXIMUM)
COMMON
(+) 12VDC
1 #18 AWG
(1.0 mm2)
TO POWER SOURCE
GRX-12VDC
Page 14
ASIAN HEADQUARTERS
Lutron Asuka Co., Ltd. 2nd Floor, Kowa Shibakoen Bldg. 1-1-1111, Shibakoen Minato-ku, Tokyo 105-0011 Japan TOLL FREE: (0120) 083417 (Japan) Tel: (03) 5405-7333; International 81-3-5405-7333 Fax: (03) 5405-7496; International 81-3-5405-7496
Lutron Electronics, Co., Inc., reserves the right to make improvements or changes in its products without prior notice. Although every attempt is made to ensure that this information is accurate and up to date, please check with Lutron to confirm product availability, latest specifications and suitability for your application.
©2002 Lutron Electronics Co., Inc.
Made and printed in U.S.A 11/02 P/N 032-118
®
WORLD HEADQUARTERS
Lutron Electronics Co. Inc. 7200 Suter Road Coopersburg, PA 18036-1299 U.S.A. TOLL FREE: (800) 523-9466 (U.S.A., Canada, Caribbean) Tel: (610) 282-3800; International 1 610 282-3800
Fax: (610) 282-3090; International 1 610 282-3090
EUROPEAN HEADQUARTERS
Lutron EA Ltd. Lutron House 6 Sovereign Close Wapping London, E1W 3JF, United Kingdom FREEPHONE: 0800-282107 (U.K.) Tel: (207) 702-0657; International 44 207 702-0657
Fax: (207) 480-6899; International 44 207 480-6899
Appendix C: Troubleshooting
If the GRAFIK Eye lighting controls in your project aren’t working as specified . . .
Review carefully the GRAFIK Eye submittal documentation prepared for your project — especially the project’s One-
Line Diagram, which gives an overview of the wiring and shows how all GRAFIK Eye equipment connects. The GRAFIK Eye Designer™software, which produces such one-line diagrams, is available from Lutron.
If necessary, call Lutron.
Problem
Cause Remedy
Unit does not turn lights on
Unit does not control load ZONE control does not work
1 or more zones are “full­on” when any scene is on and zone intensity is not adjustable (and zone is not a non-dim)
A ZONE control affects more than one zone
Wallstation does not func­tion properly
Faceplate is warm
Unit does not allow scene changes or zone adjustments
Breaker/MCB is off Long fade time Low zone settings Miswire System short circuit System overload
Miswire Disconnected wires Burned-out lamps
Miswire
Shorted triac
Miswire
Miswire or loose con­nection Wallstation not set up properly
Normal
Unit may be set to an optional Save Option.
Switch breaker/MCB on. Set FADE time to 0 seconds. Use zone for each scene. Check wiring (refer to wiring details). Find and correct shorts in fixtures and/or wallbox. Make sure lighting loads don’t exceed Unit’s maximum rated load.
Check wiring (refer to wiring details). Connect zone wires to loads (refer to wiring details). Replace bad lamps.
Make sure loads are connected to the right zones (refer to wiring details). Replace Control Unit.
Check wiring (refer to wiring detail).
Check and tighten loose connections at Class 2/PELV ter­minals on Unit and Wallstations (refer to Appendix A). Confirm programming.
Solid-state controls dissipate about 2% of the connected load as heat.
Refer to Page 8 for Save Options.
Loading...