Lutron AYF-103P-AL Installation Manual

Page 1
Preset Fluorescent Dimmer Installation Instructions
Please Leave for Occupant
Package Contents
Ariadni® Diva®
• Single-pole/3-way dimmer
• Mounting screws (2)
• Wire connectors: single-pole cap off (1,small) single-pole/3-way (6)
Important Notes
1. CAUTION: To reduce the risk of
overheating and possible damage to other equipment, do not use to control receptacles, motor-operated appliances, or transformer-supplied appliances.
2. These dimmers require a neutral
connection in the wallbox. If your wallbox does not have a neutral, one must be run. The dimmers will not operate without one.
3. When no “grounding means” exist within
the wallbox then the NEC® 2002, Article 404-9 allows a dimmer without a grounding connection to be installed as a replacement, as long as a plastic, noncombustible wallplate is used. For this type of installation, cap or remove the green ground wire on the dimmer and use an appropriate wallplate such as Lutron's Claro® or FassadaTM series wallplates.
4. Use with Lutron Hi-lume® FDB or Eco-
10TM Electronic Fluorescent Dimming Ballasts only. Do not use with any other ballasts.
Single-Pole/3-Way
120V Models: AYF-103P DVF-103P DVSCF-103P
5. Capacity:
Dimmer Approx. No. Max. Model of lamps Current*
AYF-103P 20 8A DVF-103P 20 8A DVSCF-103P 20 8A AYF-103P-277 40 6A DVF-103P-277 40 6A DVSCF-103P-277 40 6A
* As measured from incoming hot wire
(blue) on dimmer. To determine total load on the dimmer circuit, refer to ballast label. Each ballast has an associated input current. The total load is found by adding up all the ballast currents for all ballasts on the dimmer.
6. Use only the lamp types listed on the label of the ballast. Compact fluorescent lamps must have 4 pins for dimming.
7. AYF-103P, DVF-103P, and DVSCF­103P operate at 120V only. AYF-103P­277, DVF-103P-277, and DVSCF-103P­277 operate at 277V only.
8. In multi-phase applications, use a separate neutral for each dimmer circuit. If further information is necessary, contact the Lutron Hotline 1-800-523-
9466.
9. Do not use two dimmers in the same 3­way circuit.
10. Wire dimmer in accordance with all national and local electrical codes.
11. This dimmer is designed to operate in temperatures between 0°C and 40°C (32°F to 104°F).
12. The Diva® dimmer is compatible with designer-style and Lutron screwless Claro® wallplates. The Ariadni® dimmer is compatible with standard wallplates and Lutron FassadaTM wallplate. Wallplates are not included.
13. The wire connectors provided are suitable for copper wire only. They can be used to join one No. 18, 16, 14, 12, or 10 gauge wire with one or two No. 14 or 12 gauge wires.
14. Clean dimmer with a
only
. Do not use any chemical cleaners.
277V Models: AYF-103P-277 DVF-103P-277 DVSCF-103P-277
soft damp cloth
Page 2
Multigang Installations
Dimmers can be grouped together or with standard switches under a common wallplate. When ganging these dimmers, remove the inner side sections. No capacity derating is required for these dimmers.
Remove all inner side sections (shaded) in any ganged installation.
Do not remove outer side sections.
Before Installation
CAUTION: Check new installations for short circuits BEFORE installing the fluorescent dimmer. Turn power OFF at circuit breaker or fusebox. Connect a standard switch as shown in the Test Switch Wiring Diagram. Turn power ON. If lights do not come on, a break in the wiring exists. If the breaker trips, there is a short in the wiring. If necessary, turn power OFF and correct any wiring problems, recheck the circuit, then proceed to Installation. Warranty is void if dimmer is turned ON in a shorted circuit.
Installation
1. WARNING: Turn power OFF at circuit breaker or remove fuse.
ON
OFF
ON
OFF
ON
OFF
2. Remove test switch from wallbox.
4A. Single-pole wiring
(See Single-Pole Wiring Diagram)
• Connect the bare or green ground wire of the dimmer to the bare or green ground wire in the wallbox.
• Using a wire connector provided, cap off the violet wire. This wire is only used in a 3-way installation.
• Connect the white dimmer wire to the neutral wire in the wallbox.
• Connect the blue dimmer wire to the 120V or 277V supply (hot) wire.
• Connect the red dimmer wire to the wire going to the black wire of the ballasts.
• Connect the yellow dimmer wire to the wire going to the orange wire of the ballasts.
4B. 3-way wiring
(See 3-Way Wiring Diagram)
• Connect the bare or green ground wire of the dimmer to the bare or green ground wire in the wallbox.
• Connect the white dimmer wire to the neutral wire in the wallbox.
• Connect the blue dimmer wire to one of the two wires coming from the other switch location.
• Connect the violet dimmer wire to the second wire coming from the other switch location.
• Connect the red dimmer wire to the wire going to the black wire of the ballasts.
• Connect the yellow dimmer wire to the wire going to the orange wire of the ballasts.
5. Mount and align dimmer. Do not pinch wires.
3. Strip insulation or trim wires to expose 1/2" or 5/8" of wire: 1/2" for 10, 12, and 14 gauge. 5/8" for 16 and 18 gauge.
1/2"or 5/8"
6. Screw on faceplate.
7. Turn power ON.
ON
OFF
ON
OFF
ON
OFF
Page 3
Test Switch Wiring Diagram
To additional Lutron Dimming Ballasts
Standard
Switch
HOT
120V, 60Hz
or
277V, 60Hz
NEUTRAL
Single Pole Wiring Diagram
To additional Lutron Dimming Ballasts
ORANGE BLACK WHITE
ORANGE BLACK WHITE
Lutron Dimming Ballast
Lutron Dimming Ballast
Diva or Ariadni
Dimmer
Yellow
White
Red
Violet
Blue
Blue
Violet
White
Red
Green or Bare
Ground
Ground
Hot
120V, 60Hz
or
277V, 60Hz
Neutral
Green or Bare
Cap off
Yellow
3-Way Wiring Diagram
To additional Lutron Dimming Ballasts
3-way
Diva or Ariadni
Hot
120V, 60Hz
or
277V, 60Hz
Neutral
Switch
Ground
Blue
Violet
White
Dimmer
Yellow
Red
Green or Bare
Ground
Orange Black White
Orange Black White
Lutron Dimming Ballast
Lutron Dimming Ballast
Note: Wire location will vary by
product. Reference wires by color, not location.
Orange Black White
Orange Black White
Lutron Dimming Ballast
Lutron Dimming Ballast
Green or Bare
Yellow
White
Red
Violet
Blue
Note: Wire location will vary by
product. Reference wires by color, not location.
Ground
Page 4
Ariadni® Operation
Toggle switch turns lights on to preset level.
Slider moves up to brighten and down to dim lights to desired level.
True 3-way.
A 3-way dimmer and a standard 3­way switch provide preset switching from both locations and light level control from the dimmer.
Diva® Operation
Paddle switch turns lights on to preset level.
True 3-way.
A 3-way dimmer and a standard 3­way switch provide preset switching from both locations and light level control from the dimmer.
Slider moves up to brighten and down to dim lights to desired level.
Technical Assistance
If you have questions concerning the installation or operation of this product, call the
Support Center
exact model number when calling. (800) 523-9466 (U.S.A., Canada, and the Caribbean) Other countries call (610) 282-3800 Fax (610) 282-3090 Internet: www.lutron.com
Lutron Technical
. Please provide
Lamp Aging
Best dimming performance is achieved after new lamps have been aged (burned-in) by running at full intensity for at least 100 hours.
Minimum Light Level Adjustment
This unit is factory calibrated and does not normally require low-end light level adjustment. If lamps flicker or drop out at the minimum dimming level, there may be an installation error or the low-end light level may need to be reset. Continued use of the system in this mode will cause premature lamp failure. If this is occurring, call the
Support Center
Lutron Technical
at: 1-800-523-9466
Limited Warranty
Lutron will, at its option, repair or replace any unit that is defective in materials or manufacture within one year after purchase. For warranty service, return unit to place of purchase or mail to Lutron at 7200 Suter Rd., Coopersburg, PA 18036-1299, postage pre-paid.
THIS WARRANTY IS IN LIEU OF ALL OTHER EXPRESS WARRANTIES, AND THE IMPLIED WARRANTY OF MERCHANTABILITY IS LIMITED TO ONE YEAR FROM PURCHASE. THIS WARRANTY DOES NOT COVER THE COST OF INSTALLATION, REMOVAL OR REINSTALLATION, OR DAMAGE RESULTING FROM MISUSE, ABUSE, OR DAMAGE FROM IMPROPER WIRING OR INSTALLATION. THIS WARRANTY DOES NOT COVER INCIDENTAL OR CONSEQUENTIAL DAMAGES.
This warranty gives you specific legal rights, and you may have other rights which vary from state to state. Some states do not allow the exclusion or limitation of incidental or consequential damages, or limitation on how long an implied warranty may last, so the above limitations may not apply to you.
This product may be covered by one or more of the following U.S. patents: 4,803,380; 4,835,343; 4,876,498; 4,954,768; 5,207,317; 5,262,678; 5,359,231; DES 342,234; DES 364,141 and corresponding foreign patents. U.S. and foreign patents pending. Lutron, Ariadni, Claro, Diva, and Hi-lume are registered trademarks and Eco­10 and Fassada are trademarks of Lutron Electronics Co., Inc. NEC is a registered trademark of the National Fire Protection Association, Quincy, Massachusetts.
© 2003 Lutron Electronics Co., Inc.
Lutron Electronics Co., Inc. 7200 Suter Road Coopersburg, PA 18036-1299
Made and printed in the U.S.A. 10/03 P/N 031-159 Rev. C
Loading...