Lumineux 401580, 401582, 401581-M3, 401580-M3, 401582-M3 Installation Instructions

Hatherton
EE
A
G
Multi 3CCT Bulkhead
IP65
3CCT
INSTALLATION INSTRUCTIONS
12W, 16W & 20W
110^
BESA
Lm/W
5 YR
Warranty
Hatherton
READ THESE INSTRUCTIONS
THOROUGHLY BEFORE
INSTALLATION KEEP THESE
INSTRUCTIONS FOR
FUTURE REFERENCE.
IMPORTANT:
This product must be installed
by a qualifi ed electrician or
accordance with current building
and IET wiring regulations.
BOX CONTENTS
This lighting  xture has been properly
packed to avoid damage during transit. Before commencing with the installation carefully inspect the
luminaire to con rm there is no damage. DO NOT INSTALL if any damage has occurred to the  xture
or any of its components.
• Light Fitting
• Instruction Manual
• Fixings
TOOLS REQUIRED
• Drill
• Screwdriver
• Cable
1 2
4
on
off
5
Electrical connection wiring
Grommet
Twist-lock
Geartray
NEUTRAL = Blue
EARTH = Green/Yellow
LIVE (SW) = Brown
3
6
on
off
Bulkhead
PLEASE READ THESE INSTRUCTIONS
BEFORE INSTALLATION.
WARNING: Risk of electric shock! Isolate the mains power before proceeding.
• Turn off the mains power before performing inspections, installation, or removal
• Verify that the supply voltage is correct by comparing it with the luminaire label information
• It is the installers responsibility to ensure installation is suitable for the total load of the luminaire(s). The supply cable, fuses/circuit brakers must be correctly rated for the electrical load and considering for any transient inrush currents that may occur
• Do not perform insulation strength or resistance tests on installed luminarie(s) connected
1. Remove the four screws securing the diffuser
2. Twist the locking tab to loosen and remove the geartray.
3. Drill appropriately sized holes through your chosen mounting points in the base
4. Install grommet to your chosen cable entry and pierce,
making a hole just large enough to make a tight  t
around the incoming mains cable. Carefully thread cable through grommet
5. Secure the  tting in place. Note: If protection against
ingress of moisture is required the heads of screws must be covered with a silicone or similar sealant
6. Wire as per diagram (5)
7. Please see overleaf for instructions on how to set all sensor versions
8. Replace the geartray and twist the locking tab to
secure in place, then re t the diffuser
9. Re-connect the mains supply
Manby Business Park, Manby, Lincolnshire, LN11 8UT Lumineux is a B&T Associates Ltd company.
Technical Helpline: +44 (0)1507 328031
^Lm/W  gures based on 4000K output.
www.lumineux.co.uk
1 Sec ON 1 Sec OFF
3 Sec ON 3 Sec OFF
3 Sec ON 1 Sec OFF
0.5 Sec ON
0.5 Sec OFF
Hatherton 3CCT Multi Bulkhead
DISPOSAL
Disassembly instructions for end of life disposal available on website.
Disposal of Electronic Equipment
WEEE Directive 2002/96/EC This
product falls within the scope of the Waste Electrical & Electronic Equipment Directive (WEEE), which means the product should not be disposed of as normal household waste. Please recycle where facilities exist or check with your Local Authority. RoHS – All components and materials used in
this product are RoHS 2002/95/EC
compliant.
Specications may change from time
to time. The information contained
in this leaet is for guidance only
and should not be considered as always accurate and should be treated as not representative.
MICROWAVE SENSOR SETTINGS
Detection Range: This determines the effective range of the motion.
Note that reducing the sensitivity will also narrow the detection range.
Hold Time Duration: This determines the time the tting remains at 100% illumination following motion detection.
Daylight Setting: This setting holds off the 100% light output should there be sufcient daylight.
STANDARD ON/OFF SENSOR
DETECTION AREA
1 2
ON ON 100%
OFF ON 75%
ON OFF 50%
OFF OFF 25%
HOLD TIME
3 4 5
ON ON ON 5S
OFF ON ON 30S
ON OFF ON 90S
OFF OFF ON 5Min
ON ON OFF 20Min
OFF OFF OFF 30Min
DAYLIGHT
6 7 8
ON ON ON 2Lux ON ON OFF 10Lux
OFF ON OFF 30Lux
ON OFF OFF 50Lux
OFF OFF OFF Disable
HATHERTON BULKHEAD DIMENSIONS
Part No. Description Watts L (mm) W (mm) H (mm) Weight
430180
430181
430182
Hatherton
Bulkhead
Hatherton
Bulkhead
Hatherton
Bulkhead
L
300 300 100
12W
300 300 100
16W
300 300 100
20W
W H
STEP DIM DRIVER SETTINGS
DETECTION AREA
1
I ON 100%
II OFF 50%
HOLD TIME
2 3
I ON ON 5S
II ON - 30S
III - ON 3min
IV - - 10min
DAYLIGHT SENSOR
4 5
I ON ON 5Lux
II ON - 15Lux
III - ON 30Lux
IV - - Disable
* Do not change output current unless instructed or this will void warranty.
STAND-BY PERIOD
6 7
I ON ON 0s
II ON - 30s
III - ON 10min
IV - - +∞
STAND-BY DIM
LEVEL
8
I ON 10%
II _ 25%
* OUTPUT CURRENT
S1 S2 S3
450mA ON ON ON
400mA ON - ON
380mA - - ON
350mA - ON -
320mA ON - -
300mA - - -
Installation Engineers Contact Details: Luminaire Reference / Location
Name:
Tel:
0Kg
0Kg
0Kg
Wiring instructions for units equipped
an with EMERGENCY function
Emergency lighting luminaries must be installed and maintained in accordance with the emergency lighting standard BS 5266-1
1. Connect incoming earth cable to ‘Earth’ terminal on connector block.
2. Connect incoming neutral cable to ‘Neutral’ terminal on connector block.
3. For the emergency unit to work correctly, please ensure that an uninterrupted permanent live feed is present and is connected directly to the ‘Permanent Live’ terminal of the mains terminal block. Please ensure there are no switches, PIRs etc within the permanent live feed, constant switching of the emergency pack could result in premature battery failure.
4. Connect incoming switched live cable to the terminal marked
“Switched Live”
NOTE: If there is no switch live feed and the unit has a microwave sensor, simply bridge across from the “Permanent Live” to the Switch Live” on the mains terminal block.
5. There should be a loose ying lead connected to the battery. This needs to be attached to the ying lead from the emergency control unit.
6. Following power up the green LED indicator should illuminate to indicate
charging. If power to the unit is disrupted or isolated, the unit indicating
green LED will switch off, triggering the emergency LEDs to illuminate.
7. Please allow 24 hours charge before rst emergency test.
EMERGENCY FITTINGS ONLY. EARTH CONNECTION REQUIRED.
L - LIVE (SW) = Brown
- EARTH = Green/Yellow
N - NEUTRAL = Blue
L1 - PERMANENT LIVE (PL) = Black
WARRANTY
This luminaire is warranted for a period of 5 years from the date of purchase**. The backup battery
pack in the emergency version is warranted for a period of 12 months. The warranty could be
invalidated should the light tting
not be installed according to these instructions, outside the scope of
the specication or the product
has been altered or tampered with in any way. Please see website for terms and conditions.
PRODUCT TEMP SPECIFICATION
Standard -20 to +40ºC
Emergency 0 to +30ºC
Revision 2 - March 2022
Luminaire Details: Full Recharge Duration 24 Hours Emergency Duration 3 Hours Lamp Type LED
ROUTINE TEST RECORD
Type Test
Signed Date Signed Date Signed Date Signed Date Signed Date
Functional 1 Functional 2 Functional 3 Functional 4 Functional 5 Functional 6 Functional 7 Functional 8 Functional 9
Functional 10
Functional 11
3hr Duration 12
** Please see our website for more detailed information on warranty.
Year 1 Year 2 Year 3 Year 4 Year 5
Self-Test EMERGENCY function
The self-test version of emergency is tted with control gear that will carry out periodic functional tests every 1 month and full duration test every 12 months.
Fault/Test/Status Reason
Battery fully charged
and operational
Battery Charging
Battery Failure
Duration Test Failure
Automatic Testing - Function 5 minute test (Every 30 days)
Automatic Testing -
Duration test is 3 hours
(every 12 months)
Standard daily use
Initial charge /
battery topping up
Battery is disconnected or
damaged/faulty
Maintenance check required
by qualied engineer
Self-testing in
operation
Self-testing in
operation
This product contains a light source of energy efciency Class E.