
TM
IntelligentLEDLightingSystems
QUICK START INSTALLATION GUIDE
DMX - INTELLIGENT POWER CENTER (IPC)
LIGHTS & POWER: (Note all lights fixtures to be wired in series)
1) Identify dry, non-plenum location for IPC. Determine location & orientation of IPC and Break-Out
Modules. Note: Vertical orientation of IPC is best for cooling. Make sure DMX channel address
dials are visible and accessible. See page 6 of IPC specifications for optional acceptable
orientations.
2) Run wires from the Break-Out Module locations directly to the fixture locations.
3) Mount IPC to board w/ #8 screws or self-tapping screws or in an approved enclosure. Use approved
plenum enclosure if unit is located in plenum.
4) With typical 115Vac input, IPC consumes 2.7 amps. Standard 15 amp breaker can accommodate up
to 4 IPCs and a 20 amp breaker can accommodate up to 5 IPCs. If wiring only 4 or 5 IPCs, consider
powering from two separate circuits for redundancy.
Note: 115Vac = 2.7 Amps, 240 Vac = 1.1 A & 227 Vac = 1.0 A.
5) Provide service disconnect switch for IPCs if not in close proximity to electrical panel or as required
per code.
6) Provide line-voltage power to IPC and wire as specified on page 7 of IPC installation manual.
(Black to Line, White to Neutral & Green to Ground.)
7) Set channel address dials on IPC. (Suggestion: Set first address to match the number of channels on
the IPC. i.e. - start with channel 12 (=1x12) on first 12 channel IPC, channel 24 (=2x12) on second
12 channel IPC etc.) (Note: you can also start with any number and skip addresses for convenience.
i.e. – use 100’s for first floor and 200’s for second floor etc.) See page 10 of IPC Installation
Manual for Channel Dial addressing. Note direction of arrow head on dial and make sure dial is set
directly to number (otherwise all lights may come on or flash).
8) Wire IPC class 2 wires to Break-Out Modules. See Detail B4.09, B4.12, B6.09 or B6.12. (Black is
always Negative.)
9) Wire fixture home runs to the Break-Out Modules. See Detail B4.09, B4.12, B6.09 or B6.12.
(Black is always Negative.)
10) Wire light fixtures in series. Two fixtures per channel, typ. See Detail A1 & A2 for wiring fixtures
in series.
11) IMPORTANT: Keep track which fixtures are on which channel on a plan or spreadsheet.
12) Connect DMX control from IPC to IPC in series w/ Cat5 (RJ45) patch cables. Note either slot can
be used for input/output. Power to Trinity is not necessary for Cat5 DMX signal to pass through.
Note: Max distance between lighting control system and last IPC is 1,000 feet. Longer distances can
be achieved with the use of a repeater.
13) Install termination plug in last IPC in series.
Note: For complete and more technical installation instructions refer to the LumaStream Intelligent
Power Center Application and Installation Manual included with each unit.
LumaStream.com288722ndAvenueN,SuiteD,St.Petersburg,FL33713727.827.2805
Rev. - 09.30.12

4 Inch Recessed New
3. Remove Junction Box cover.
Construction LED Luminaire
Installation Instructions
OWNER/USER RESPONSIBILITIES: It is the responsibility of the contractor, installer, buyer, owner and user to install, maintain and operate this
luminaire in accordance with all applicable laws, building codes, regulations and local Electrical Safety Authority requirements. This product is only
to be installed by a qualified person.
WARNING
• Shut OFF power at fuse box or circuit breaker before installation.
• Turn power OFF before inspection or removal of LED light source.
Installation:
1. Pull on LED Trim Ring in direction shown to remove LED light
source from housing. Flip open one lever on each Wire Lever
Nut to disconnect wires.
and insert strain relief (not supplied) into hole. Flip open
Wire Lever Nut. Connect Class 2 constant current source:
Connect +Ve to RED. Connect –Ve to BLACK, by inserting
stripped wire into Wire Lever Nut. Close lever. OBSERVE
CORRECT POLARITY. Failure to do so will damage LED light
source. Replace Junction Box cover.
2. Extend bar hangers to fit between joists. Bar hanger foot aligns
with bottom of joist. Hammer pre-installed nails into joists.
When installing in drywall, cut 4-1/2” hole. If necessary, adjust
fixture for ceiling thickness by loosening hex screws then retighten.
BLACK to BLACK. OBSERVE CORRECT POLARITY. Failure to do
so will damage LED light source. Compress Flat Spring Clips
with fingers and insert into housing opening. Press upwards
until trim ring is flush against the ceiling.
LumaStream, Inc.
2887 22nd Ave. N
Saint Petersburg, FL
33713
T: 1-727-827-2805
Page 1 of 1
Disclaimer: LumaStream Inc. reserves the right to make changes without
further notice to any products herein to improve reliability, function, or
design. LumaStream does not assume any liability arising out of the
application or use of any product described herein; neither does it convey
any license under its patent rights, nor the rights of others.
info@lumastream.com
www.lumaStream.com
©2012 LumaStream, Inc.
All Rights Reserved
Doc No: 4.0 RI Installation
Revision: Feb-22-2012

4 Inch Recessed Re-Model
3. Pass junction box up into hole in ceiling
4. Re-connect LED light source to
LED Luminaire
Installation Instructions
OWNER/USER RESPONSIBILITIES: It is the responsibility of the contractor, installer, buyer, owner and user to install, maintain and operate this
luminaire in accordance with all applicable laws, building codes, regulations and local Electrical Safety Authority requirements. This product is only
to be installed by a qualified person.
WARNING
• Shut OFF power at fuse box or circuit breaker before installation.
• Turn power OFF before inspection or removal of LED light source.
Installation:
1. Pull on LED Trim Ring in direction shown to remove LED light
source from housing. Flip open one lever on each Wire Lever
Nut to disconnect wires.
housing and insert housing into ceiling. Press clips outwards
to hold housing in place. To remove from ceiling, pull clips
down and back into housing
2. Cut 4-3/8” hole in ceiling. Pull Class 2 wiring through hole in
ceiling. Remove Junction Box cover. Remove appropriate
knock-out and insert strain relief (not supplied) into hole. Flip
open Wire Lever Nut. Connect Class 2 constant current source:
Connect +Ve to RED. Connect –Ve to BLACK, by inserting
stripped wire into Wire Lever Nut. Close lever. OBSERVE
CORRECT POLARITY. Failure to do so will damage LED light
source. Replace Junction Box cover.
BLACK to BLACK. OBSERVE CORRECT POLARITY. Failure to do
so will damage LED light source. Compress Flat Spring Clips
with fingers and insert into housing opening. Press upwards
until trim ring is flush against the ceiling.
LumaStream, Inc.
2887 22nd Ave. N
Saint Petersburg, FL
33713
T: 1-727-827-2805
Page 1 of 1
Disclaimer: LumaStream Inc. reserves the right to make changes without
further notice to any products herein to improve reliability, function, or
design. LumaStream does not assume any liability arising out of the
application or use of any product described herein; neither does it convey
any license under its patent rights, nor the rights of others.
info@lumastream.com
www.lumaStream.com
©2012 LumaStream, Inc.
All Rights Reserved
Doc No: 4.0 RC Installation
Revision: Feb-22-2012