EMERGENCY LIGHTING TESTING
Months 1 to 11 inclusive – Function Test, interrupt the permanent/UnSwitched supply and check the luminaire operates in Emergency mode at reduced output
Month 12 (Annual) – As months 1 to 11 but for a full 3 hour duration
Luminaire Ref / Location: ........................................ In Case of difficulty, contact the Installation Engineers:- Tel: .........................................................
LBM290X11E40 Duration 3 Hours Lamp Type - LED
INITIAL USE AND ROUTINE TESTING
From initial install the downlight will require up to 24 hours for the batteries to be fully charged and provide the rated 3HR duration in Emergency mode. Then following subsequent Emergency use, from full discharge will take approx. 14hrs to fully recharge batteries.
It is important that the luminaire is routinely tested to ensure the batteries are conditioned and also to fully comply with BS5266. A function test should be conducted every month with an annual test of the full 3hr duration. Records can be kept on the adjacent table.
It is recommended that batteries are replaced every 4 years to ensure the optimum charging cycle is maintained.
Fifth Year
Signed Date
Month Tes t
1 Function 2 Function 3 Function 4 Function 5 Function 6 Function 7 Function 8 Function 9 Function 10 Function 11 Function Annual Full Test
First Year
Signed Date
Second Year
Signed Date
Third Year
Signed Date
Fourth Year
Signed Date
WARRANTY
Products are protected by warranty for a period of 3 year warranty from date of purchase against defects in material and workmanship (unless otherwise stated). Should a product fail to perform as described within the warranty period it will be repaired or replaced with the same or equivalent product by Luceco, free of charge provided that you: (1) return the product to us with shipping charge prepaid, (2) provide us with proof of the original date of purchase and (3) quote our return authorization number
Repaired or replaced products will be returned to you with shipping charges prepaid. Replacement products may be refurbished or contain refurbished materials. If in our sole discretion, we are unable to repair or replace a defective product, we will refund the purchase price of the product
This warranty will not apply if in our judgment, the product fails due to damage in shipment, handling, storage, accident, abuse or misuse, or if it has been used in a manner not conforming to our product instructions, has been modified in any way, or has any serial number removed or defaced. Repair or attempted repair will void this warranty. Our maximum liability under the terms of this warranty is limited to the purchase price of the product covered by the warranty
The warranty is given under English Law. If any part of this warranty is deemed unenforceable (including any provision in which we exclude our liability to you) the enforceability of any other parts of the warranty will not be affected. These terms do not reduce your statutory rights
LED IP65
Mosi Emergency Bulkhead
PART CODE: LBM290W11E40, LBM290B11E40
SPECIFICATIONS
Suitable for use with Mains voltage of 220-240V AC
This product must be disconnected before insulation
resistance testing of the lighting circuit
Check for electrical cables and pipes before installation
3HR
EMERGENCY
NOTE – To comply with regulations, installation must be carried out by qualified electrician and in accordance with the current IEE Wiring Regulations (BS7671) and Building Regulations.
ENSURE ELECTRICAL SUPPLY IS DISCONNECTED/ISOLATED BEFORE COMMENCING INSTALLATION
To maintain the IP65 rating of the bulkhead, a suitable 20mm cable gland should be used in conjunction with rubber insulated cable to ensure the supply cable is sealed in the gland. Failure to use a gland and/or rubber insulated cable may result in water ingress
IP65
RATED
>
SUGGESTED METHOD OF INSTALLATION
The bulkhead is designed for mounting in any of the following options: –
• Surface Wall Mounting
• Surface Ceiling Mounting
1. Surface mounted options may use rear cable entry for flush mounting or there is facility for surface Conduit ‘besa’ box mounting or side conduit entry. (Image 1)
2. With the method of mounting chosen, remove the front Diffuser, by undoing the three front Screws. (Image 2)
3. To remove LED tray, loosen two retaining screws, and twist tray clockwise and remove. (Image 3)
4. This Bulkhead can be mounted on ceilings and vertical walls. Ensure the mounting surface is suitable for installation. Once mounting points are decided, drill out mounting holes and any cable entry points needed.
5. Cable Entry Points must be drilled out with a 20mm bit, cleaned of any loose burrs and fitted with a suitable IP65 gland, if the IP65 rating is to be maintained. Otherwise the IP rating would be reduced.
1
cable entry
points
4
CRI
80
3
year
3
GUARANTEE
2
cable entry
points
loosen
screws here
loosen
screws here
THESE TERMS AND CONDITIONS ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE
For further details, terms and conditions and online registration please see www.luceco.co
UK -
Non UK -
Tech Help Line
0845 194 7584
+44 (0)1952 238 100
Stafford Park 1 TF3 3BD ENGLAND
Luceco is a registered trade mark of Nexus Industries Ltd.
BG Electrical Ltd
Visit our website at
www.luceco.co
Page 4
UK -
Non UK -
Tech Help Line
0845 194 7584
+44 (0)1952 238 100
BG Electrical Ltd
Stafford Park 1 TF3 3BD ENGLAND
Luceco is a registered trade mark of Nexus Industries Ltd.
Page 1
Visit our website at
www.luceco.co
Installation & Operating Instructions
Installation & Operating Instructions
WIRE UP
With the bulkhead securely fixed in the desired position, make the electrical connection to the terminal block, observing the correct polarity. (Image 5)
Note – the bulkhead is a class II construction and does not require an earth connection, but a earth termination point is fitted and for emergency versions, 2no. Live connections (Switched [SL] and UnSwitched [L] required)
5
FOR EMERGENCY VERSIONS
The battery requires connecting before use, connect the two push connectors between driver and battery. This is to stop the battery being live during installation. (Image 6)
From initial installation the integral batteries will require 24hours to reach full charge status
Once the electrical connections have been made, the gear tray can be fitted back into position and secured by twisting Anti-clockwise and tightening the 2no. Fixing screws.
Re-fit the front diffuser and tighten 3 securing screws. Turn on power and operate. (Image 7)
6 7
tighten
screws here
ADDITIONAL INFORMATION - EMERGENCY FUNCTION
Versions fitted with Emergency control gear provide a reduced light output in the event of a mains power failure to aid the safe evacuation of the area
By having a second Live (unswitched/permanent, marked L) power feed to the bulkhead, it can be switched ON/OFF as required and also will sense a power failure in the lighting circuit, regardless of the bulkhead being ON or OFF
Where a second live is not provided, when the bulkhead is switched off, the batteries will power the LED array, this will vastly reduce the life of the batteries and their ability to charge
TECHNICAL INFORMATION
Code Rated Voltage Power Current PF
LBM290W11E40-01 220-240V~ 50Hz 16W <80mA 0.8 3 Hr
LBM290B11E40-01 220-240V~ 50Hz 16W <80mA 0.8 3 Hr
Emergency Duration Battery
Emergency
Emergency
Ni-Cd SC1600mAh 3.6V
Ni-Cd SC1600mAh 3.6V
Lumens with no diffuser
1400 Llm 1100 Llm
1400 Llm 1100 Llm
Lumens with diffuser
ADDITIONAL INFORMATION - COMPONENT REPLACEMENT
The luminaire contains no user replaceable components other than the battery pack contained in Emergency versions
The battery has a 4year service life provided it is operated and maintained by regular testing, as detailed in this document. Failure to maintain or change the battery may result in reduced duration in Emergency mode
Battery specification - Ni-Cd SC1600mAh 3.6V
Environmental Protection W.E.E.E
This symbol is known as the “crossed-out wheelie Bin Symbol”. When this symbol is marked on a product or battery, It means that it should not be disposed of with your general household waste. Some chemicals contained within electrical/electronic products or batteries can be harmful to health and the environment. Only dispose of electrical/electronic/battery items in separate collection schemes, which cater for the recovery and recycling of materials contained within. Your co-operation is vital to ensure the success of these schemes and for the protection of the environment
EMERGENCY OPERATION
Following a full discharge, 12-14hours should be allowed for the batteries to re-charge
The Green LED charge indicator signifies that the batteries are charging and will remain illuminated when the bulkhead is switched off
UK -
Non UK -
Tech Help Line
0845 194 7584
+44 (0)1952 238 100
Stafford Park 1 TF3 3BD ENGLAND
Luceco is a registered trade mark of Nexus Industries Ltd.
BG Electrical Ltd
The batteries have a rated service life of 4years and should be checked and considered for replacement at that point
A record of routine testing should be kept to ensure Emergency luminaires are maintained and operated correctly