LST Y72221, IST200 Specification Sheet

Page 1
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27 OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
Ex-Sys200_DBL_LST_EN_0804.PDF • PAGE 1
ABuilding Safety. Building Security.
IS Optical Smoke Detector 2251EIS
Specifi cations
Ignition protection intrinsically safe
Ex classifi cation EEx ia IIB T5
Operating voltage Supply through loop voltage
Current consumption at 24V 330µA
Ambient temperature -25°C to +70°C
Relative humidity 5 – 95% (no condensation)
Dimensions ø × H 103 × 43 (mm)
Colour cream
Weight 110g
Approval BASEEFA03ATEX0157X LPCB 199m
Order number 241025
Order name IS Optical Smoke Detector/Anal./200/SS 2251EIS
The addressable Intrinsically Safe Optical Smoke Detec­tor 2251EIS (fi g. A) uses the scattered light principle and was developed for the detection of smoke particles in hazardous areas. The modern design of the sensing chamber allows to reliably evaluate the characteristics of fi re.
The proven ADM loop technology with System Sen­sor/200 protocol establishes a permanent communica­tion between the fi re detection control panel and the detector. That ensures a periodical function testing of the detector. In the control panel all types of fi res are detected by continuously comparing fi re patterns. Intelligent evaluation algorithms use the current condi­tion of the sensing chamber to predict the likely time
of the next maintenance. Thus the alarm threshold is automatically adjusted within the permissible range, de­pending on the contamination. With that, the constant response sensitivity of the detector is ensured for a long time.
The two LEDs with 360° visibility indicate the activated condition of the detector. The detector address is selec­ted with two decadic rotary switches, thus allowing to change the detector without additional tools.
A detector function test can be conveniently conducted using a magnet or test gas. The detector can be pro­tected against theft.
• Optical smoke detector
• Safety barrier with galvanic isolation
• Protocol interface for communication with the fi re detection control panel
• ATEX certifi ed
fi g. A
fi g. B
fi g. C
Page 2
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27 OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
Ex-Sys200_DBL_LST_EN_0804.PDF • PAGE 2
ABuilding Safety. Building Security.
Safety Barrier Y72221
The Safety Barrier Y72221 (fi g. B) is used for intrinsi­cally safe electric circuits. The built-in zener barrier and the safe galvanic isolation allow the connecton of fi re
detectors in hazardous areas. Due to the galvanic isola­tion, the earth leakage monitoring can remain activated in the fi re detection control panel.
Ignition protection intrinsically safe
Ex classifi cation EEx ia IIC T5
Operating voltage Supply through the detector line voltage
Ambient temperature -20°C to +60°C
Dimensions W × H × D 20 × 110 × 107.5 (mm)
Mounting TS35 DIN rail
Colour green
Weight 100g
Approval BASEEFA Nr.: BAS00ATEX7087
Order number 228006
Order name Safety Barrier/Anal./200/SS Y72221
The Protocol Interface IST200 (fi g. C) serves for the design of an intrinsically safe electric circuit in ADM loop technology. It allows the bidirectional data traffi c between fi re detection control panel and fi re detectors in hazardous areas via an ADM loop with System Sen-
sor/200 protocol. The interface is always used toge­ther with the Safety Barrier Y72221. The Surface Moun­ting Box SMB500 is required for mounting the protocol interface.
Protocol Interface IST200
Ignition protection intrinsically safe
Operating voltage Supply through loop voltage
Current consumption at 24V 14mA
Ambient temperature 0°C to +60°C
Relative humidity 5 – 95% (no condensation)
Dimensions W × H × D (without attaching sheet) 70 × 70 × 32 (mm)
Weight 155g
Order number 228007
Order name Protocol Interface/Anal./200/SS IST200
Specifi cations
Specifi cations