
5.5~18.5kW(200V), 5.5~90kW(400V)
AC Variable Speed Drive
H100 Troubleshooting Manual
Read this manual carefully before servicing or inspecting this equipment.
Keep this manual within easy reach for quick reference.

1
Quick Reference Table
The following table listed situations frequently encountered while working with inverters. Refer to
the typical situations to quickly and easily locate solutions to your questions.
I want to review recent fault trip and warning histories.
The motor is producing too much heat.
The cooling fan is not working.
I want to know how I can keep the inverter when I am not using it.
I want to initialize all parameters.
I want to terminate the inverter.
I want to review the input/output module.
I want to change the fan when it exceeded the replacement period.
I want to change the carrier frequency.
I cannot set the parameters.
The motor is not working.
The motor stops when it is connected to the load or accelerated.

2
Contents
INTRODUCTION 3
Manual Composition 3
PRODUCT IDENTIFICATION 4
ASSOCIATION MANUAL 4
SAFETY INFORMATION 5
REVISION RECORD 7
1
BASIC CHECKLIST 8
Before you think it failed 8 1.1
Basic Operations 10 1.2
Parameter Change 14 1.3
Carrier Frequency Change 14 1.3.1
Initializing All Parameters 16 1.3.2
Read and Write Parameters 17 1.3.3
Fault Trip Monitoring 18 1.4
2
TROUBLESHOOTING 21
Trips and Warning 21 2.1
Failure/Warning List 21 2.1.1
Troubleshooting Fault Trips 25 2.1.2
Troubleshooting Other Fault 30
2.2
3
MAINTENANCE 35
Regular Inspection List 35 3.1
Daily Inspections 35 3.1.1
Annual Inspections 36 3.1.2
Bi-Annual Inspections 37 3.1.3
Check Input/Output Module 38 3.1.4
Replace Cooling FAN 42 3.1.5
Storage and Disposal 44 3.2
Storage 44 3.2.1
Disposal 44 3.2.2

3
Introduction
Manual Composition
1.1 Before you think it failed
1.2 Basic Operations
1.3 Parameter Change
1.3.1 Carrier Frequency Change
1.3.2 Initializing All Parameters
1.3.3 Read and Write Parameters
1.4 Fault Trip Monitoring
2.1 Trips and Warning
2.1.1 Failure/Warning List
2.1.2 Troubleshooting Fault Trips
2.2 Troubleshooting Other Fault
3.1 Regular Inspection List
3.1.1 Daily Inspections
3.1.2 Annual Inspections
3.1.3 Bi-Annual Inspections
3.1.4 Check Input/Output Module
3.1.5 Replace Cooling FAN
3.2 Storage and Disposal
3.2.1 Storage
3.2.2 Disposal
This section explains troubleshooting
fault trips and other common faults.
If problems are not solved, please
contact your vendor or LSIS.
This section provides information
on how to maintain the inverters on
a regular basis for different time
periods.
When there is a problem in the
inverter, please check the
input/output module. This is the
basic method to check the
hardware.
This section covers check points
when there is a problem in the
inverter.
Then check the parameter settings
using basic operations and the trip
records.

The H100 75/90 kW, 400 V inverters satisfy the EMC standard EN61800-3 without installation of optional EMC
filters.
Association Manual
H100 user manual can be downloaded through LSIS homepage.
Link : http://www.lsis.com/support/download/

5
Safety Information
Read and follow all safety instructions in this manual precisely to avoid unsafe operating conditions,
property damage, personal injury, or death.
Safety symbols in this manual
Indicates an imminently hazardous situation which, if not avoided, will result in severe injury or
death.
Indicates a potentially hazardous situation which, if not avoided, could result in injury or death.
Indicates a potentially hazardous situation that, if not avoided, could result in minor injury
or property damage.
Do not open the cover of the equipment while it is on or operating. Likewise, do not operate
the inverter while the cover is open. Exposure of high voltage terminals or charging are to the
external environment may cause an electric shock. Do not remove any covers or touch the
internal circuit boards (PCBs) or electrical contacts on the product when the power is on or
during operation. Doing so may cause serious injury, death or serious property damage.
Do not open the cover of the equipment even when the power supply to the inverter has been
turned off unless it is necessary for maintenance or regular inspection. Opening the cover
may lead to an electric shock even when the power supply is off.
The equipment may hold charge long after the power supply has been turned off. Use a multi-
meter to make sure that there is no voltage before working on the inverter, motor, or motor
cable.

This equipment must be grounded for safe and proper operation.
Do not supply power to a faulty inverter. If you find that the inverter is faulty, disconnect the
power supply and have the Inverter repaired.
The Inverter becomes hot during operation. Avoid touching the Inverter until it has cooled
down to avoid burns.
Do not allow external objects, such as screws, metal chips, debris, water, or oil to get inside
the Inverter. Allowing external substances inside the Inverter may cause the Inverter to
malfunction or ignite fire.
Do not operate the Inverter with wet hands. Doing so may cause electric shock.
Do not modify the interior structure/components of the Inverter. Doing so will void the
warranty.
The Inverter is designed for 3-phase motor operation. Do not use the Inverter to operate 3-
phase motor.
Do not place heavy objects on top of electric cables. Doing so may damage the cable and
cause an electric shock.

8
1
Basic Checklist
Before you think it failed 1.1
Installed
Environment /
Input/Output
voltage
Is the installed location appropriate?
Does the environment meet the inverters operating conditions?
Does the power source match the inverter’s rated input?
Is the rated output of the inverter sufficient to supply the equipment?
Is the circuit breaker installed on the input side of the inverter?
Is the circuit breaker correctly rated?
Are the power source cables correctly connected to the R/S/T terminals
of the inverter?
(Caution: Connecting the power source to the U/V/W terminals may
damage the inverter)
Are the motor output cables connected in the correct phase rotation
(U/V/W)?
(Caution: Motors will rotate in reverse direction if three phase cables are
not wired in the correct rotation)
Are the cables used to connect power terminals correctly rated?
Is the inverter grounded properly?
Are the power terminal screws and the ground terminal screws tightened
to their specific torques?
Are the overload protection circuits installed correctly on the motors (if
multiple motors are running using one inverter)?
Is the inverter separated from the power source by a magnetic contactor
(if a braking resistor is in use)?
Are advanced-phase capacitors, surge protection and electromagnetic
interference filters installed correctly?
(These devices MUST NOT be installed on the output side of the
inverter)

Are STP (shielded twisted pair) cables used for control terminal wiring?
Is the shielding of the STP wiring properly grounded?
If 3-wire operation is required, are the multi-function input terminals
defined prior to the installation of the control wiring connections?
Are the control cables properly wired?
Are the control terminal screws tightened to their specified torques?
Is the total cable length of all control wiring less than 165ft (50m)?
Is the total length of safety wiring less than 100ft (30m)?
Are optional cards connected correctly?
Is there any debris left inside the inverter?
Are there any cables (contacting adjacent terminals) creating a potential
short circuit risk?
Are the control terminal connections separated from the power terminal
connections?
Have the capacitors been replaced if they have been in use for more
than 2 years?
Has a fuse been installed for the power source?
Are the connections to the motor separated from other connections?

1. Basic Checklist
10
Basic Operations 1.2
Key Functions
Refer to the following illustration to identify part names and functions
Operation Keys
The following table lists the names and functions of the keypad’s operation keys.
Used to switch between modes.
Used to select, confirm, or save a parameter value.
[Up] key
Switch between codes or increase or decrease parameter values.
[Down] key
Switch between codes or increase or decrease parameter values.
Used to perform special functions, such as user code registration.
Used to cancel an input during parameter setup.
Pressing the [ESC] key before pressing the [PROG / ENT] key reverts the
parameter value to the previously set value.
Pressing the [ESC] key while editing the codes in any function group
makes the keypad display the first code of the function group.
Pressing the [ESC] key while moving through the modes makes the
4. HAND mode LED indicator
6. OFF mode LED indicator
10. AUTO mode LED indicator

keypad display Monitor mode.
Used to switch to HAND (local/manual) operation mode.
Used to switch to OFF (standby) mode or to reset the inverter faults.
Used to switch to AUTO (remote) operation mode.

Inverter Operating Status
Composition of Display
(1) Monitor Mode
(2) Parameter change display
Display Item List
The following table lists the functions and description of the keypad displays characters.
FieldBus communication option operation command
Application option operation command
Time Event operation command
Built-in 485 operation command
Terminal block operation command
V1 input frequency command
I2 input frequency command
Pulse input frequency command
Frequency command during UP operation
Monitor Mode Display Item 1
Monitor Mode Display Item 2
Monitor Mode Display Item 3
Initial Value at the Time
of Product Delivery
Inverter Operating Status
Rotational direction
Rotational direction

Frequency command during DOWN operation
(Up-Down operation)
Frequency command during STOP operation
(Up-Down operation)
FBus Option frequency command
Internal 485 frequency command
Multi-step frequency command
Multi
Function
Key Setting
Used to register parameters as a user group in the parameter
mode or delete parameters in the user group.
Inverter
Operating
Status
Software Over Current controlled
Hardware Over Current controlled

1. Basic Checklist
14
Parameter Change 1.3
Carrier Frequency Change 1.3.1
The following example demonstrates how to configure Carrier Frequency by modifying CON group 04
code(Carrier Frequency) from 3.00(Hz) to 10.00(Hz). You can configure the parameters for different
codes in any other group in exactly the same way.
Monitor Mode is displayed.
Shift to CON by using Mode key.
Shift to code 04 using Down key.
Press PROG.

Change the Carrier Frequency to 10 using Up key.
Press ENT.
The display come back to the initialization selection after
finishing Carrier Frequency Change
Adjust motor operational noise by changing carrier frequency settings. Power transistors (IGBT) in the
inverter generate and supply high frequency switching voltage to the motor. The switching speed in this
process refers to the carrier frequency. If the carrier frequency is set high, it reduces operational noise
from the motor, and if the carrier frequency is set low, it increases operational noise from the motor.
Below are advantages and disadvantages according to the sound of the inverter during operation.

1. Basic Checklist
16
Initializing All Parameters 1.3.2
You can initialize the parameter that has been changed by the user to the initial state at the time of
delivery. Not only the entire parameter but a group of the parameter mode can be selected and initialized.
Monitor mode is displayed.
Press the [MODE] key to move to the Config (CNF) mode.
Press the [Down] key to go to CNF-40 (Parameter Init).
Press the [PROG/ENT] key to configure the parameter
initialization options.

In the list of options, select ‘1(All Grp),’ and then press the
[PROG/ENT] key to perform parameter initialization.
The parameter initialization option is displayed again when the
initialization is complete.
Following parameter initialization, all parameters are reset to factory default values. Ensure that
parameters are reconfigured before running the inverter again after an initialization.
Read and Write Parameters 1.3.3
This is the function of copying the parameter saved in the inverter to the keypad and copying the
parameter saved in the keypad to the inverter.
Read and Write Setting Details
Copies the parameter in the inverter to the keypad. The existing parameters
saved in the keypad are all deleted.
Copies the parameter saved in the keypad to the inverter. The existing
parameters in the inverter are all deleted. In case of an error during
parameter writing motion, the previously saved data can be directly
used. If there is no data saved in the keypad, a message reading “ EEP
Rom Empty “ is displayed.
Because the parameters set in communication are saved in the RAM area,
they are all gone
if the inverter power is turned Off/On. If you set parameters in
communication and select Yes in CNF-48 Parameter Save,
the set parameters remain unchanged even if the inverter power is turned
Off/On.
* Available on LCD keypad only.

1. Basic Checklist
18
Fault Trip Monitoring 1.4
Failure during operation
If a fault trip occurs during inverter operation, the inverter enters
Trip mode automatically and displays the type of fault trip that
occurred.
Press the [Down] key to view the information on the inverter at the
time of fault, including the output frequency, output current, and
operation type.
If there were any fault trips that occurred previously, press the
[Right] key to display the fault trip information at the times of
previous fault trips.
When the inverter is reset and the fault trip is released, the keypad
display returns to the screen it was at when the fault trip occurred.

1. Basic Checklist
19
Multiple failures at a time
If multiple fault trips occur at the same time, the number of fault
trips occurred is displayed on the right side of the fault trip type.
Press the [PROG/ENT] key to view the list of all the fault trips.
The list of all the fault trips is displayed.
When the inverter is reset and the fault trip is released, the
keypad display returns to the screen it was at when the fault trip
occurred.

1. Basic Checklist
20
Saving and monitoring of failure history
In case of a failure during operation, the mode automatically
shifts to Trip Mode with the trip displayed.
If you press Reset or the terminal is entered, the failure above
is
Automatically saved and the display goes back to the place
before the failure.
Move to Trip Mode using Mode key.
The most recent failure is saved in Last-1 code.
Press Right key.
A previous failure is saved in Last-2 code.
If another failure occurs, what was in Last-2 moves to Last-3.

2. Troubleshooting
21
2
Troubleshooting
This chapter explains how to troubleshoot when the protective functions, fault trips, warning signals,
or a fault occurs while operating the inverter. If the inverter does not work as expected after
following the suggested troubleshooting steps, please contact the LSIS Customer Service Center.
Trips and Warning 2.1
The Inverter will stop operating or send out a warning signal when it detected a fault. The keypad
will show brief information of the trip and warning signal. If the model is using the LCD keypad, the
LCD will show detailed information.
The following is how the fault conditions are categorized.
• Level: After the fault is corrected, the trip or warning signal disappears. The fault is not saved
in the fault history.
• Latch: After the fault is corrected, the trip or warning signal disappears once the Inverter is
reset.
• Fatal: After the fault is corrected, the trip or warning signal disappears when conducted the
following procedure. Turn off the Inverter and wait until the charge indicator light goes off. Then,
turn on the Inverter. If the Inverter still failed, please contact the supplier or LSIS Customer
Service Center.
Failure/Warning List 2.1.1
The following table shows a list of faults and warning signals that can occur while operating H100.
Trip due to an external signal
Temperature sensor fault trip
ARM short current fault trip
Output open-phase fault trip

Input open-phase fault trip
Motor overheat fault trip
IO Board connection fault trip
Low voltage fault trip during
operation
Write parameter fault trip
Motor overload fault trip
Motor under load fault trip
Inverter overheating trip

Emergency stop fault trip
IO Board connection fault trip
Command loss fault trip warning
Inverter overload warning
Braking resistor braking rate
warning
Capacitor lifetime warning

Load curve tunning warning
Smart copier error warning
Auto tunning warning(Lsigma)
• In a latch type trip, the inverter cannot unlock the fault if the user does not reset the inverter, even if the
trip state is released after the trip occurs.
• In level type trip, the inverter can unlock the fault by itself if the trip state is unlocked after the trip
occurs.
• In a fetal type trip, there is no way to unlock the fault other than turning the inverter off then back on
after the trip occurs.

2. Troubleshooting
25
Troubleshooting Fault Trips 2.1.2
Refer to the following tables for solutions to fault trips or warnings.
Occurs when the motor load exceeds the value that was set
for the motor overload trip. Operation will resume after setting
PRT-20 at a value other than 0
The load is greater than the
motor’s rated capacity.
Make sure the motor and inverter has the appropriate capacity ratings.
Replace the motor and inverter that has a bigger capacity.
The value set for overload trip
level (PRT-21) is too small.
Increase the setting value.
There is a fault with the output
module (IGBT).
Refer to 3.1.4 Check Input/Output Module to identify the fault cause of
the output module (IGBT).
DO NOT operate the inverter. Contact the retailer or the LSIS Customer
Service Center.
The mechanical brake of the
motor is operating too fast.
Check the mechanical brake.
The torque boost level is too high
Reduce the torque boost level.
Acc/Dec time is too short compared
to the load inertia (GD2).
Occurs when the motor load is less than the value that was
set for the motor underload level. Operation will resume after
setting PRT-27 at a value other than 0
There is a motor-load connection
problem.
Replace the motor and inverter with models with lower capacity.
The set value for underload level
(PRT-24) is less than the system’s
minimum load.
Reduce the set value for the underload level.
Occurs when the Inverter output current exceeds 180% of
the rated current.
Acc/Dec time is too short
compared to the load inertia
(GD2).
Inverter load is greater than the
rated capacity.
Replace the inverter that has a bigger capacity.
The inverter produced an output
while the motor was not
operating.
Operate the inverter after the motor stopped or use the speed search
function (CON-70).
The mechanical brake of the
Check the mechanical brake.

motor is operating too fast.
Output wiring is short-circuited /
Ground fault occurred.
Remove the short circuit. Check the motor for ground fault.
There is a problem in the wiring
between the inverter and the
motor.
Check the output wiring as well as the recommended specifications of
the wiring length, thickness, etc..
There is a fault with the output
module (IGBT).
Refer to 3.1.4 Check Input/Output Module to identify the fault cause of
the output module (IGBT).
DO NOT operate the inverter. Contact the retailer or the LSIS Customer
Service Center.
Occurs when voltage rate of the DC circuit is higher than the
specific value..
The input voltage is too high.
Check whether the input voltage is higher than the specified value.
The actual DC link voltage is
different from the value on the
display.
Need to inspect the Hardware.
Contact the retailer or the LSIS Customer Service Center.
Acc/Dec time is too short
compared to the load inertia
(GD2).
There is a generative load at the
inverter output.
Occurs when the DC circuit voltage is lower than the
specified value.
The input voltage is too low.
Check whether the input voltage is lower than the specified value.
The actual DC link voltage is
different from the value on the
display.
Need to inspect the Hardware.
Contact the retailer or the LSIS Customer Service Center.
There is a problem with the input
(R, S, T) wiring.
The magnetic contactor
connected the power source is
faulty..
Replace the magnetic contactor.
A load greater than the power
capacity is connected to the
power system. (welder, direct
motor connection, etc.)

Occurs when the DC circuit voltage is lower than the specified
value during inverter operation
The input voltage has decreased
during the operation.
Check whether the input voltage is lower than the specified value.
An input phase-loss has occurred.
The magnetic contactor
connected the power source is
faulty..
Replace the magnetic contactor.
Occurs when there is excessive current than the specific
value due to a ground fault in the output. The ground fault
detection current is different per inverter capacity.
Ground fault occurred in the
output lead.
Separate the output wiring and check whether the ground fault is
present. Remove the ground fault
There is a problem in the wiring
between the inverter and the
motor.
Check the output wiring as well as the recommended specifications of
the wiring length, thickness, etc. Replace it if necessary.
The insulation of the motor is
damaged.
Decrease the carrier frequency value.
Motor
overheat
fault trip
Occurs depending on the inverse time (delay) to prevent
overheat of the motor due to overload. Operation will resume
after setting PRT-40 at a value other than 0.
The motor has overheated.
Reduce the load or operation frequency.
The inverter load is greater than
the rated capacity.
Replace the inverter that has a bigger capacity.
The value for electronic thermal
protection (ETH) is too low.
Set the ETH level appropriately.
The inverter has been operating
at low speed for a long time.
Replace the motor that supplies extra power to the cooling fan.
Output
open-phase
fault trip
Occurs when one of the three output phases is phase open.
Operation will resume after setting PRT-05 bit 1 to 1.

There is a problem with the
magnetic contactor in the output.
Check the magnetic contactor on the outside.
The output wiring is faulty.
Input openphase fault
trip
Occurs when one of the three input phases is phase open.
Operation will resume after setting PRT05 bit 2 to 1.
There is a problem with the
magnetic contactor in the input.
Check the magnetic contactor on the input side.
The input wiring is faulty.
The DC condenser needs to be
replaced.
Replace the DC condenser.
Contact the retailer or the LSIS Customer Service Center.
Occurs when the overload time equivalent to 60% of the inverter
overheat protection (inverter IOLT) level, is accumulated. Set the
digital output terminals or relay (OUT-31–35 or OUT-36) to ‘6
(IOL)’ to receive the inverter overload warning output signals.
The load is greater than the motor’s
rated capacity
Replace the motor and inverter that has a bigger capacity..
The torque boost level is too
high.
Reduce the torque boost level.
Occurs when the temperature of the heat sink exceeds the
specific value.
There is a problem with the
cooling system.
Check whether there are any external substances (dust, etc.) in the air
inlet, outlet or vent.
The cooling fan has been
operating for a long time
Change the cooling fan. (Refer to 3.1.5 Replace cooling fan)
The ambient temperature is too
high.
Keep the ambient temperature below 50℃.
ARM short
current fault
trip
Occurs when the DC circuit in the inverter detects an
excessive short circuit current.

Acc/Dec time is too short
compared to the load inertia
(GD2).
Increase Acc/Dec time.
Output lead is short circuit.
There is a problem in the wiring
between the inverter and the
motor.
Check the output wiring as well as the recommended specifications of
the wiring length, thickness, etc. Replace it if necessary.
There is a fault with the output
module (IGBT).
Refer to 3.1.4 Check Input/Output Module to identify the fault cause of
the output module (IGBT). DO NOT operate the inverter. Contact the
retailer or the LSIS Customer Service Center.
Temperature
sensor fault
trip
Occurs when an error is detected in the temperature sensor of
the Insulated Gate Bipolar Transistor (IGBT).
The ambient temperature is too
low
Keep the ambient temperature above -10 ℃
There is a fault with the internal
temperature sensor.
Contact the retailer or the LSIS customer service center.
Occurs when there is a problem with the cooling fan.
Operation will resume after setting PRT-79 to 0
There are external substances
blocking the air vent.
Remove the external substances.
The cooling fan needs to be
replaced.
Change the cooling fan. (Refer to 3.1.5 Replace cooling fan)

2. Troubleshooting
30
Troubleshooting Other Fault 2.2
Refer to the following tables for solutions other than fault trips or warnings.
Setting parameters is not working.
The inverter is operating (inverter mode).
Stop the inverter and change to program mode and set
the parameters.
The parameter access level is incorrect.
Check the correct parameter access level and set the
parameter.
The password is incorrect.
Check the password and disable the parameter lock by
setting CNF-52 to Unlock. Then set the parameter.
Check the power input to resolve the low voltage problem.
Then set the parameter
The motor does not rotate.
The setting of the operation command source is
incorrect.
Check the setting of the operation command source.
There is no power supplied to the R/S/T
terminals.
Check the connections of R/S/T and U/V/W terminals.
The charge lamp is turned off.
The operation command (RUN) is off.
Turn on the operation command (RUN).
Unlock the motor or lower the load level.
Operate the motor independently.
There is an input on the emergency stop signal.
Reset the emergency stop signal.
The wiring for the control circuit terminal is
incorrect.
Check the wiring for the control circuit terminal.
The input option for the frequency command is
incorrect.
Check the input option for the frequency command.
The input voltage or current for the frequency
command is incorrect.
Check the input voltage and current for the frequency
command.
The PNP/NPN mode is selected incorrectly.
The frequency command value is too low.
Check the frequency command value and set the
command that is above minimum frequency.
The [STOP/RESET] was pressed.
The motor was stopped normally so run the inverter.
The motor torque is too low.
Change the operation modes (V/F, IM Sensorless). If the
fault remains, replace the inverter that has bigger
capacity.

2. Troubleshooting
31
The motor rotates in the opposite direction to the command.
The wiring of the motor output cable is
incorrect.
Check whether the output side is wired correctly to the
phase (U/V/W) of the motor.
The rotation signal connection between the
control circuit terminal (forward/reverse rotation)
and the forward/reverse rotation control panel is
incorrect.
Check the forward/reverse rotation wiring.
The motor only rotates in one direction.
Reverse rotation prevention is selected.
Release/Remove the reverse rotation prevention setting
and resume operation.
The reverse rotation signal is not input even
though the 3-wire sequence was selected.
Check the input signal associated with the 3-wire
operation.
The motor is overheating.
The load is too high.
Reduce the load. Increase the Acc/Dec time.
Check the motor specifics and set to the correct values.
Replace the motor and inverter appropriate to load
capacity.
The ambient temperature of the motor is too
high.
Lower the ambient temperature.
The phase-to-phase voltage of the motor is
insufficient.
Use the motor that can withstand phase-to-phase voltage
surges, greater than the maximum surge voltage.
Only use motors suitable for inverter applications.
Connect the AC reactor to the inverter output (Set the
carrier frequency to 2kHz in code H39).
The motor fan stopped. / The external
substances are inside/blocking the fan.
Check the motor fan and remove any external substances
(dust, debris, etc.)

2. Troubleshooting
32
The motor stopped when accelerated or connected to load.
The load is too high.
Reduce the load.
Replace the motor and inverter appropriate to inverter
capacity.
The motor does not accelerate. / The acceleration time is too long.
The frequency command is too low.
Change the setting accordingly.
Reduce the load. Increase the acceleration time.
Check the status of the mechanical brake.
The acceleration time is too long.
Change the setting accordingly.
The properties of the motor and inverter
parameters are incorrect.
Change the parameters of the motor.
The stall prevention level during acceleration is
low.
Change the stall prevention level.
The stall prevention level during operation is
low.
Change the stall prevention level.
Starting torque is insufficient.
Change to vector control operation mode. If the fault still
exists, replace the inverter that has a bigger capacity.
Motor speed changes during operation.
There is high variance in the load.
Replace the motor and inverter that has a bigger capacity.
The input voltage changes.
Reduce the input voltage variance (standard deviation).
The motor speed changes at a specific
frequency.
Adjust the output frequency to avoid resonance.
The motor rotation is different from the setting.
The V/F pattern is set incorrectly.
Set a V/F pattern suitable for motor specification.

2. Troubleshooting
33
The deceleration time is too long even with the Dynamic Breaking resistor connected to the
motor.
The deceleration time is set too long.
Change the setting accordingly.
The motor torque is insufficient.
If there is no problem with motor parameters, this is due to
motor capacity. Replace the motor with a bigger capacity.
The load is higher than the internal torque limit
(based on the rated current) of the inverter..
Replace the inverter with a bigger capacity.
The control unit is not working or noise is generated when the inverter is in operation.
The switching inside the inverter caused noise.
Reduce the carrier frequency in CON-04.
Install a micro surge filer in the inverter output.
The earth leakage breaker is activated when the inverter is in operation.
The earth leakage breaker is activated due to
leaking current from the inverter.
Connect the inverter to the ground terminal.
Check the ground resistance is less than 100 Ω for 200V
and less than 10 Ω for 400V inverters.
Check the capacity of the leakage breaker and connect
properly based on the rated current of the inverter.
Reduce the carrier frequency in CON-04.
Make the cable length between the inverter and the motor
as short as possible.
The motor vibrates intensely and does not rotate normally.
The phase-to-phase voltage of 3-phase power
source is not balance.
Check the input voltage and stabilize the voltage.
Check and test the insulation of the motor.
The motor makes humming or loud noises.
There is resonance between the motor’s natural
frequency and the carrier frequency.
Reduce the carrier frequency in CON-04.

There is resonance between the motor’s natural
frequency and the inverter’s output frequency.
Slightly change the command frequency
Use the frequency jump function to avoid resonance.
The motor vibrates / hunts.
The frequency input demand was externally set
to analog command.
Change the input filter time constant if there are
interferences in the frequency command due to noise
from the analog input side.
The wiring between the motor and inverter is
too long.
Make sure that the total cable length between the inverter
and the motor is less than 150m (50m for motors rated
3.7kW and lower).
The motor does not stop completely when the inverter output stopped.
The motor cannot decelerate sufficiently due to
malfunction of the DC braking.
Adjust the DC braking parameter.
Increase the set value for DC braking current.
Increase the set value for the DC braking stopping time.
Free run stop was selected.
Change the stopping method to decelerating.
The output frequency does not reach the target frequency.
The target frequency is within the jump
frequency range.
Set the target frequency higher than the jump frequency
range.
The target frequency is higher than the upper
limit of the frequency command.
Set the upper limit of the frequency command higher than
the target frequency.
The stall prevention function is not working due
to high load.
Replace the inverter with a bigger capacity.
The cooling fan does not rotate.
The control parameter for the cooling fan is set
incorrectly.
Check the control parameter settings for the cooling fan in
ADV-64

3. Maintenance
35
3
Maintenance
This chapter covers regular inspections for different time periods, how to replace the cooling fan,
and how to properly store and dispose Inverters. The surrounding environment highly affects the
conditions of the inverters. Meaning, improper management will wear down the components and
lead to malfunction. In order to prevent this from happening, please follow the recommended
maintenance guidelines in this section.
Read all safety instructions in this manual before inspecting the product.
Make sure the power is off before cleaning the product.
Clean the inverters with dry cloths. Using wet cloths, water, solvents, or detergents may lead
to electric shock or damage to the product.
Regular Inspection List 3.1
Daily Inspections 3.1.1
Is the ambient
temperature and
humidity appropriate
within the range?
Is there any dust or
substances nearby?
Refer to
Installation &
Wiring in the
User Manual
Temperature:
10~40℃.
Humidity:
Below 50%
Thermometer,
hygrometer,
recorder
Is there any unusual
vibration or noise?
Are the input/output
voltages in the
normal range?
Voltage ratings
between R/S/T
phases in the
inverter’s
terminal block
Refer to Input and
Output standards in
the User Manual
Digital multimeter
/ Analog tester
Is there any internal
leakage?
Is the condenser
swollen (change in
shape)?
Is there any unusual
vibration or noise?
Check by
rotating the fan
manually when
the system is
turned off

Is the display value
normal?
Check the
display value on
the panel
Check the rated,
managerial value
Is there any unusual
vibration or noise?
Is there any unusual
smell (odor)?
Check for
overheat or
damage
Megger test
(between
input/output
terminals and earth
terminal)
Disconnect the
inverter wirings
and short
R/S/T/U/V/W
terminals.
Measure each
terminal to the
ground terminal
using a Megger.
(Refer to 3.1.4
Check
Input/Output
Module)
Are there any loose
parts in the device?
Are there any
evidence of
overheat?
Conductor
Connections
/Cables
Are there any
corroded cables?
Is there any damage
on the wire clothing?
Measure
electrostatic capacity
Measure with
capacity meter
Above 85% of the
rated capacity
Is there any
chattering noise
during operation?
Is there any damage
on the resistors?
Digital multimeter
/ Analog tester

Remove one
side and
measure
Must be within
±10% of the rated
resistance
Control /
Protection
circuit
Check imbalance of
output voltage
during operation
Measure
voltage
between output
terminal U/V/W
Phase-to-phase
voltage balance:
Within 4V for 200V
Within 8V for 400V
Digital multimeter
/ DC Voltemeter
Is there any error in
the display circuit
after the sequence
protection test?
Test inverter
output
protection at
both short and
open circuit
conditions
Circuit must work
according to the
sequence
Are there any loose
parts around the
fan?
Is the display value
normal?
Check the
command
values on the
display device
Specified values
and manageable
values must match
Bi-Annual Inspections 3.1.3
Megger test
(between
input/output
terminals and earth
terminal)
Disconnect the
cables for
terminals
U/V/ W and test
the wiring
Do not run the Megger (Insulation Resistance Test) on the control circuit as it may lead to damage
to the product.

3. Maintenance
38
Check Input/Output Module 3.1.4
How to check the diode module and IGBT module (5.5~30kW)
1) Disconnect all power cables (R,S,T) and motor output cables (U,V,W).
2) Before testing, check the discharge of electrolytic capacitor (DCP-DCN).
3) When the circuit is open, DMM will indicate high resistance (several MΩ). In some situations, the DMM
may display a closed circuit (low resistance) and then show high resistance due to the capacitors.
When the circuit is closed, the DMM shows resistance of several hundred kΩ or less.
4) Displayed values may not be constant as it depends on the module and tester type. The value
measured between the phases is acceptable if the standard deviation is approximately ±10%.

3. Maintenance
39
How to check the diode module and IGBT module (37~90kW)
1) Disconnect all power cables (R,S,T) and motor output cables (U,V,W).
2) Before testing, check the discharge of electrolytic capacitor (DCP-DCN).
3) When the circuit is open, DMM will indicate high resistance (several MΩ). In some situations, the DMM
may display a closed circuit (low resistance) and then show high resistance due to the capacitors.
When the circuit is closed, the DMM shows resistance of several hundred kΩ or less.
4) Displayed values may not be constant as it depends on the module and tester type. The value
measured between the phases is acceptable if the standard deviation is approximately ±10%.

3. Maintenance
40
Example) Checking diode module and IGBT module
Checking Diode D2
1) Measure the resistance of D2 by placing the red lead (positive terminal of DMM) on S phase
and the black lead (negative terminal of DMM) on P.
If the resistance indicated on DMM is several hundred kΩ or less, it is acceptable.
2) Measure the resistance of D2 by placing the red lead from the positive terminal of DMM on P
and the black lead from negative terminal of DMM on S phase.
If the resistance indicated on DMM is MΩ, it is acceptable.
3) Measure the resistance of other diodes in the same way.
Before testing, check the discharge of electrolytic capacitor (DCP-DCN).

3. Maintenance
41
Checking IGBT Tr6
1) Measure the resistance of Tr6 by placing the red lead (positive terminal of DMM) on N and the
black lead (negative terminal of DMM) on V phase.
If the resistance indicated on DMM is several hundred kΩ or less, it is acceptable.
2) Measure the resistance of Tr6 by placing the read lead (positive terminal of DMM) on V phase
and the black lead (negative terminal of DMM) on N.
If the DMM indicates several MΩ, it is acceptable.
3) Measure the resistance of other Tr in the same way.
Before testing, check the discharge of electrolytic capacitor (DCP-DCN).

3. Maintenance
42
Replace Cooling FAN 3.1.5
If the inverter continued to operate after the cooling fan trip took place, a protective function will be
activated due to overheat in the cooling fan. Increase in temperature may reduce the lifespan of
major components. Make sure to solve the problem in the cooling fan before operating the inverter.
If the cooling fan has been operating longer than its (optimal) replacement period, this may lead to
low performance of the inverter or the cause of inverter failure. The replacement period of the
cooling fans is 3 years. Replace the old cooling fans with the new one
Replacement of 5.5~30kW FAN
1) Remove the fan cover by pressing the hook located by the arrow
2) Disconnect the fan wire and remove the fan from the inverter.

3. Maintenance
43
Replacement of 37~55kW FAN
1) Remove ❶ screws to separate the fan bracket from the inverter.
2) Disconnect the fan wire and remove ❷ screws.
Replacement of 75~90kW FAN
1) Remove ❶ screws to separate the fan bracket from the inverter.
2) Disconnect the fan wire and remove ❷ screws.

Turn off the inverter before replacing the fan. There is a possibility of an electric shock due to
the charge voltage. Wait until the inverter is fully discharged to replace the fan. (The time to
discharge varies per capacity, in average 1~3 minutes after turning off the inverter).
Make sure the fan wire and connect is not touching the blades. If touched it leads to
malfunction of the inverter. Make sure the inverter is completely turned off before cleaning.
After replacing the fan, assemble the fan. Before using the inverter, turn on the inverter and
check the condition of the fan by its motion.
Be careful of the direction of the fan.
Storage and Disposal 3.2
Storage 3.2.1
Store the products in the following conditions listed below (if not used for a long period of time).
Store the product in the same appropriate environmental conditions as in operation.
If the product will be stored more than 3 months, keep the ambient temperature between -
10℃~30℃ to prevent degradation of the electrolytic capacitor.
The products should not be exposed to snow, rain, fog and dust.
When packing the inverter, include a dehumidifier (e.g. silica gel) to keep the ambient
temperature inside the package below 70% and prevent in contact with moisture.
If the products will be left in a humid or dusty environment (construction sites or control panel)
separate the products in a location that has the same appropriate environmental conditions as
in operation.
Disposal 3.2.2
Categorize the inverters as general industrial waste when disposing the product. Note that there
are recyclable raw materials in the product, such as packing materials and metalwork. For the sake
of conservation of energy and resources, recycle whenever possible. Depending on the country,
plastic may be recyclable. Please check the local environmental regulations for more details.
Capacitors lose their charging characteristics if not operated for a long time. In order to prevent
this from happening, turn on the product and allow the device to operate for 30~60 minutes once
a year. Note that operation should be conducted under no-load conditions.