LOYTEC L-switch xp LS-xxCB EIA-709 Installation Instructions Manual

Installation instructions
L-switchXP LS-xxCB EIA-709 Router
Instructions de montage
Montageanweisung
Montagevoorschrift
Instrucciones de montaje
Monteringsanvisning
60
max 50º
C
min 5º C
0,220 kg
10 - 90
%
105
85
kg
RH
11
LOYTEC
0,5 - 2,5 mm
2
Euroclamp SH3-5.08
8
DIN TS35
EIA-709
Port
2
EIA-70
9
Port
1
1 2 3 4 5 6
15 16 17
~~
+-
12-35 VD
C
12-24 VAC
A
a
B
G b
H
40
Connector
s
1 EIA-709 input EARTH GND port
2
2 EIA-709 input B port
2
3 EIA-709 input A port
2
4 EIA-709 input EARTH GND port
1
5 EIA-709 input B port
1
6 EIA-709 input A port
1 15 Power supply input earth ground 16 Power supply input MINUS 17 Power supply input PLUS Do not connect to GN
D
40 RS-232 interface (DB9 male)
Status LEDs
A GREEN flashing fast
Traffic on port 2 GREEN flashing at 1 Hz Port 2 not commissioned RED permanent Port 2 damaged RED flashing fast Traffic overload on port 2
B GREEN flashing fast
Traffic on port 1 GREEN flashing at 1 Hz Port 1 not commissioned RED permanent Port 1 damaged RED flashing fast Traffic overload on port 1
G GREEN Power
H OFF Normal operatio
n
Buttons
a Rese
t
b Send service pin messag
e
Termination
(L-Term)
Document 88070202 09/2005 Printed in Austria Data is subject to change
LOYTEC
LOYTEC electronics GmbH
MADE IN AUSTRIA
W44/2004
LC-33CB
810000F12A07
810000F12A0
9
006101810000F12A0
7
NID1
NID2
SER#
Node ID of router on EIA-709 Port 1
Node ID of router on EIA-709 Port 2
Serial number of the device
Date Code
1 2 3 4 5 6 7
OFF ON
DIP3 Function (RS-485 version only)
ON Bit-rate auto detection on OFF Bit-rate auto detection of
f
DIP4 Must be OFF DIP5 Must be OFF DIP6 Must be OFF DIP7 Must be OFF
DIP1 DIP2 Function
ON
ON Smart switch mode ON OFF Repeater mode OFF ON Smart switch mode/ subnet learning OFF OFF Configured EIA-709 router
http://www.loytec.com
support@loytec.com
Loading...