LROC-100 Room Controller
Installation instructions
Instructions de montage
Montageanweisung
Montagevoorschrift
max 50º C
RH
min 0º C
kg
0,350 kg
10 - 90 %
Instruzioni di montaggio
Instrucciones de montaje
Monteringsanvisning
15
60
13
159
164
89
100

USB-B
microSD
RESET
DISPLAY
POWER
1 2 3
-
24-35 VDC
+
24 VAC
~~
Connectors
POWER 1 Power supply input EARTH GND
2 Power supply input MINUS
Can be connected to EARTH GND
3 Power supply input PLUS
Must NOT be connect to
EARTH GND
FT 4 Input EARTH GND
CEA-709 5 Input B
6 Input A
LIOB-FT 7 Input EARTH GND
CEA-709 8 Input B
9 Input A
RS-485 10 Input GND
EIA-485 11 Input +
12 Input
EXT1 13 Input GND
M-Bus 14 Input B
KNX TP1 15 Input A
USB1
USB2
Ethernet2
2 x 10/100Base-T
2 x USB-A
-
Ethernet1
(RJ45)
DIAL
CEA-709
LIOB-FT EXT1
FT
4 5 6
7 8 9
B A
Connectors
USB1 USB-A USB Host
USB2 USB-A USB Host
USB-B USB-B PC
Ethernet1 RJ45 10/100Base-T
Ethernet2 RJ45 10/100Base-T
microSD slot microSD card
max. 2 GB
Buttons
RESET Reset
DIAL Turn-and-Push Dial
B A
CEA-709
RS-485
1011 12
EIA-485
L-MBUSxx/LKNX-300
Weidmüller
BLZP 5.08/03/180
131415
-
+
GND
M-Bus/KNX TP1 via
0.2 - 2.5 mm
7
B A
GND
2

Ethernet1
Ethernet2
FT EXT1
LIOB-FT
LINK
ACT
PLC OPC
DISPLAY
Status LEDs
LINK GREEN Ethernet link
ACT GREEN flashing Ethernet traffic
PLC GREEN PLC normal operation
RED flashing 2 Hz PLC overload
OPC GREEN OPC client connected
GREEN flashing OPC activity
FT GREEN flashing fast Traffic on CEA-709 port
GREEN flashing 1 Hz Not commissioned
RED permanent CEA-709 port damaged
RED flashing fast CEA-709 traffic overload
LIOB-FT GREEN flashing Traffic on LIOB-FT port
RED permanent LIOB-FT port damaged
RED flashing fast LIOB-FT traffic overload
RS-485 GREEN Modbus Master link
GREEN flashing Modbus traffic
ORANGE Modbus Slave Mode
ORANGE flashing Modbus traffic Slave
RED permanent Modbus port damaged
RED flashing fast Modbus traffic overload
GREEN flashing fast Traffic on BACnet port
GREEN flashing 1 Hz Not commissioned
RED permanent BACnet port damaged
RED flashing fast BACnet traffic overload
EXT1 GREEN M-Bus/KNX link
GREEN flashing M-Bus/KNX activity
RED permanent M-Bus/KNX port damaged
RED flashing fast M-Bus/KNX traffic overload
RS-485
Install the cover
LOYTEC
http://192.168.1.254
User: admin
Password: loytec4u
Please update the firmware of the device first,
see www.loytec.com/support/download

35 mm x 7.5 mm DIN rail (EN 50022, BS 5584, DIN 46277-3)
Node ID of CEA-709 Port 1 FT
Node ID of CEA-709 Port 2 LIOB-FT
Node ID of LIOB-Connect
Virtual (Node) ID of CEA-852 port (Ethernet)
MAC address of CEA-852 Ethernet port
Serial number of the device
Document 88077601
06/2015
Printed in Austria
Data is subject to change
LOYTEC electronics GmbH
810000F12A06
NID1
810000F12A09
NID2
810000F12A0A
NID3
810000F12A0B
VID1
000AB00FF002
MAC1
SER#
006101810000F12A07
LROC-100
MADE IN EC
W12/2013
Date Code
http://www.loytec.com
support@loytec.com