LOYTEC LROC-100 Installation Instructions Manual

LROC-100 Room Controller
LOYTEC
Installation instructions
Instructions de montage
Montageanweisung
Montagevoorschrift
max 50º C
RH
min 0º C
kg
0,350 kg
10 - 90 %
Instruzioni di montaggio
Instrucciones de montaje
Monteringsanvisning
15
60
13
89
USB-B
microSD
RESET
DISPLAY
POWER
1 2 3
-
24-35 VDC
+
24 VAC
~~
Connectors
POWER 1 Power supply input EARTH GND 2 Power supply input MINUS Can be connected to EARTH GND 3 Power supply input PLUS Must NOT be connect to EARTH GND FT 4 Input EARTH GND CEA-709 5 Input B 6 Input A LIOB-FT 7 Input EARTH GND CEA-709 8 Input B 9 Input A RS-485 10 Input GND EIA-485 11 Input + 12 Input EXT1 13 Input GND M-Bus 14 Input B KNX TP1 15 Input A
USB1 USB2
Ethernet2
2 x 10/100Base-T
2 x USB-A
-
Ethernet1
(RJ45)
DIAL
CEA-709
LIOB-FT EXT1
FT
4 5 6
7 8 9
B A
Connectors
USB1 USB-A USB Host USB2 USB-A USB Host USB-B USB-B PC Ethernet1 RJ45 10/100Base-T Ethernet2 RJ45 10/100Base-T microSD slot microSD card max. 2 GB
Buttons
RESET Reset DIAL Turn-and-Push Dial
B A
CEA-709
RS-485
1011 12
EIA-485
L-MBUSxx/LKNX-300
Weidmüller BLZP 5.08/03/180
131415
-
+
GND
M-Bus/KNX TP1 via
0.2 - 2.5 mm
7
B A
GND
2
Ethernet1
Ethernet2
FT EXT1
LIOB-FT
LINK ACT
PLC OPC
DISPLAY
Status LEDs
LINK GREEN Ethernet link ACT GREEN flashing Ethernet traffic PLC GREEN PLC normal operation RED flashing 2 Hz PLC overload OPC GREEN OPC client connected GREEN flashing OPC activity FT GREEN flashing fast Traffic on CEA-709 port GREEN flashing 1 Hz Not commissioned RED permanent CEA-709 port damaged RED flashing fast CEA-709 traffic overload LIOB-FT GREEN flashing Traffic on LIOB-FT port RED permanent LIOB-FT port damaged RED flashing fast LIOB-FT traffic overload RS-485 GREEN Modbus Master link GREEN flashing Modbus traffic ORANGE Modbus Slave Mode ORANGE flashing Modbus traffic Slave RED permanent Modbus port damaged RED flashing fast Modbus traffic overload GREEN flashing fast Traffic on BACnet port GREEN flashing 1 Hz Not commissioned RED permanent BACnet port damaged RED flashing fast BACnet traffic overload EXT1 GREEN M-Bus/KNX link GREEN flashing M-Bus/KNX activity RED permanent M-Bus/KNX port damaged RED flashing fast M-Bus/KNX traffic overload
RS-485
Install the cover
LOYTEC
http://192.168.1.254 User: admin Password: loytec4u
Please update the firmware of the device first, see www.loytec.com/support/download
LOYTEC
1
7.5
25
35
35 mm x 7.5 mm DIN rail (EN 50022, BS 5584, DIN 46277-3)
Node ID of CEA-709 Port 1 FT
Node ID of CEA-709 Port 2 LIOB-FT
Node ID of LIOB-Connect
Virtual (Node) ID of CEA-852 port (Ethernet)
MAC address of CEA-852 Ethernet port
Serial number of the device
Document 88077601 06/2015 Printed in Austria Data is subject to change
LOYTEC electronics GmbH
810000F12A06
NID1
810000F12A09
NID2
810000F12A0A
NID3
810000F12A0B
VID1
000AB00FF002
MAC1
SER#
006101810000F12A07
LROC-100
MADE IN EC
W12/2013
Date Code
http://www.loytec.com
support@loytec.com