TYPICAL SPECIFICATIONS
Our Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the purchase
date. Any units or parts which prove defective during the warranty period will be replaced at our option when returned to our factory,
transportation prepaid. Motors are warranted by the motor manufacturer for a period of one year. Should motors furnished by
Greenheck prove defective during this period, they should be returned to the nearest authorized motor service station. Greenheck
will not be responsible for any removal or installation costs.
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.
Greenheck P.O. Box 410 • Schofield, WI 54476-0410 • Phone (715) 359-6171 • greenheck.com
Copyright © 2005 Greenheck Fan Corp. • DG Rev. 3 January 2005 SP
Typical Specifications
General: Make-up air unit shall be as
manufactured by Greenheck or approved equal
provided all specifications are met. Greenheck
Model DG equipment is used as the basis of
design. Performance to be as scheduled on plans.
Make-up air unit shall be ETL listed to ANSI Z83.4
and CAN 3.7.
Gas Train and Controls: Direct fired gas system
shall have a draw through design and field
adjustable burner baffles. Gas trains up to 400,000
Btu/hr shall include a direct spark ignition system.
Gas trains greater than 400,000 Btu/hr shall include
a pilot ignition system and shall have digital coded
fault indicator capability. Fault indicator shall
provide service history by storing codes for the last
five faults. Dual safety shutoff valves shall be
industrial duty and use 120 VAC control signals.
Temperature control shall incorporate a Maxitrol
electronic modulation control system.
Unit Casing and Frames: Unit shall be of internal
frame type construction of galvanized steel. All
frames and panels shall be G90 galvanized steel.
Where top panels are joined there shall be a
standing seam to insure positive weather
protection. All metal-to-metal surfaces exposed to
the weather shall be sealed. All components shall
be easily accessible through removable or hinged
doors.
Optional Insulation: Unit casing to be lined with
1 inch fiberglass insulation. Insulation in
accordance with NFPA 90A and tested to meet UL
181 erosion requirements and secured to unit with
water proof adhesive and permanent mechanical
fasteners. Double wall construction is optional.
Fan Section: Centrifugal fans shall be double
width, double inlet and forward curved. Fan and
motor shall be mounted on a common base and
shall be internally isolated. All blower wheels shall
be statically and dynamically balanced. Ground
and polished steel fan shafts shall be mounted in
permanently lubricated ball
bearings (up to size 118) or ball
bearing pillow blocks (size 120
and larger). Bearings shall be
selected for a minimum (L10) life
in excess of 100,000 hours at
maximum cataloged speeds.
Motors and Drives: Motors
shall be energy efficient,
complying with EPACT standards
for ODP and TE enclosures.
Motors shall be permanently
lubricated, heavy duty type,
matched to the fan load and
furnished at the specified voltage,
phase and enclosure. Drives shall
be sized for a minimum of 150% of driven
horsepower. Pulleys shall be cast and have
machined surfaces, 15 horse power and less shall
be supplied with an adjustable drive pulley.
Electrical: All internal electrical components shall
be prewired for single point power connection. All
electrical components shall be UL listed,
recognized or classified where applicable and
wired in compliance with the National Electrical
Code. Control center shall include motor starter,
control circuit fusing, control transformer for 24
VAC circuit and integral door interlocking
disconnect switch. Contactors, Class 20 adjustable
overload protection and single phase protection
shall be standard.
V-Bank Filter Section: Filters shall be mounted in
a V-bank arrangement such that velocities across
the filters do not exceed 550 feet per minute. Filters
shall be easily accessible through a removable
access panel.
Weather Hood: Weather hood shall be
constructed of G90 galvanized steel.